General information
product brand nameSITOP
product type designationPSU8600
product designationPower supply SITOP PSU8600
type of current supply24 V/40 A
input
type of the power supply network3-phase AC
phase number3
voltage curve at inputAC
minimum rated value400 V
maximum rated value500 V
initial value320 V
full-scale value575 V
supply voltage at ACDerating 320 ... 360 and 530 ... 575 V
at 50 Hz400 V
at 60 Hz500 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputYes
buffering time for rated value of the output current in the event of power failure minimum15 ms
operating condition of the mains bufferingat Vin = 400 V; Prioritized supply of the output in case of power failure selectable via DIP switch (only in conjunction with CNX8600 expansion module)
at rated input voltage 400 V2.75 A
at rated input voltage 500 V2.2 A
current limitation of inrush current at 25 °C maximum14 A
I2t value maximum2.24 A²·s
fuse protection typenone
fuse protection type in the feederRequired: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
number of outputs1
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC5 ... 24 V
output voltage adjustableYes; via potentiometer or IE/PN interface
adjustable output voltage4 ... 28 V; Derating > 24 V: 4%/V; max. 960 W overall system
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0.2 %
on slow fluctuation of ohm loading0.1 %
maximum100 mV
maximum200 mV
display version for normal operation3-color LED for operating state device; LED for operating mode manual/remote; 4 LEDs for communication PROFINET; 3-color LED for operating state output
type of signal at outputRelay contact (changeover contact, contact current capacity DC 60 V/0.3 A) for "Operating state OK"
behavior of the output voltage when switching onNo overshoot of Vout (soft start)
response delay maximum1 s
type of outputs connectionsimultaneous switch-on of all outputs after device power-up or delay time of 25 ms, 100 ms, or "load-optimized" for sequential switch-on of the outputs via DIP switch configurable (only in connection with expansion module CNX8600)
maximum500 ms
rated value40 A
per output40 A
at output 1 rated value40 A
rated range0 ... 40 A; +50 ... +60 °C: Derating 2.5%/K; no derating in connection with expansion module CNX8600 and total load of the outputs at the basic device max. 480 W
supplied active power typical960 W
at short-circuit during operation typical120 A; only in operation without CNX8600 extension module
at short-circuit during operation25 ms
bridging of equipmentYes; suitable output characteristics via DIP switch can be selected
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent93 %
at rated output voltage for rated value of the output current typical72 W
during no-load operation maximum20 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical0.4 %
maximum10 ms
protection and monitoring
design of the overvoltage protectionmax. 35 V (max. 500 ms)
property of the output short-circuit proofYes
design of short-circuit protectionElectronic overload shutdown; optional constant-current operation can be selected via DIP switch
adjustable current response value current of the current-dependent overload release4 ... 40 A
type of response value settingvia potentiometer or IE/PN interface
of the excess currentIa >1.0...<1.5 x Ia threshold for 5 s permissible; Ia limit (= 1.5 x Ia threshold) for 200 ms permissible
of the current limitationIa limit (= 1.5 x Ia threshold) permissible for 5 s, afterwards Ia threshold continuous
in normal operationTotal system overloadable 150% Ia rated to 5 s/min
display version for overload and short circuit3-color LED for operating state device; 3-color LED for operating state output
design of the reset device/resetting mechanismvia sensor or IE/PN interface
remote reset functionnon-isolated 24 V input (signal level "high" at > 15 V)
interfaces
product function communication functionYes
design of the interfaceEthernet/PROFINET
design of the interface PROFINET protocolYes
OPC UAYes
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
EAC approvalYes
NEC Class 2No
SEMI F47Yes
BISYes; R-41188271
CB-certificateYes
MTBF at 40 °C235 118 h
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
ULhazloc approvalNo
FM registrationNo
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
French marine classification society (BV)No
Det Norske Veritas (DNV)Yes
Lloyds Register of Shipping (LRS)No
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total1 886.7 kg
during manufacturing62.2 kg
during operation1 823.2 kg
after end of life0.52 kg
ambient conditions
during operation-25 ... +60 °C; with natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionPlug-in terminals with screwed connection
at inputL1, L2, L3, PE: Plug-in terminal with 1 screwed connection each for 0.2 ... 4 mm² single-wire / fine stranded
at outputOutput: plug-in terminals with 2 screw connectors for 0.5 ... 10 mm²; 0 V: screw terminal with 3 screw connectors for 0.5 ... 10 mm² (max. 6 mm² with ferrule)
for auxiliary contactsRST (Reset): Plug-in terminal (together with alarm signal) with 1 screwed connection for 0.2 ... 1.5 mm²
for signaling contact11, 12, 14 (alarm signal): Plug-in terminal (together with Reset) with 1 screwed connection each for 0.2 ... 1.5 mm²
removable terminal at inputYes
removable terminal at outputYes
design of the interface for communicationPROFINET/Ethernet: two RJ45 sockets (2-port switch)
suitability for interaction modular systemYes
mechanical data
width × height × depth of the enclosure125 × 125 × 150 mm
installation width × mounting height125 mm × 225 mm
top50 mm
bottom50 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x15
DIN-rail mountingYes
S7 rail mountingNo
wall mountingNo
housing can be lined upYes
net weight2.6 kg
accessories
electrical accessoriesExpansion modules CNX8600, buffer modules BUF8600, module UPS8600
mechanical accessoriesDevice identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing62.2 kg
global warming potential [CO2 eq] / during operation1823.2 kg
global warming potential [CO2 eq] / after end of life0.52 kg
global warming potential [CO2 eq] / total1886.7 kg