General information
product brand nameSITOP
product type designationPSU100D
product designationPower supply SITOP
type of current supply24 V/14.6 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage 1 at AC100 ... 120 V
supply voltage 2 at AC200 ... 240 V
input voltage 1 at AC90 ... 132 V
input voltage 2 at AC180 ... 264 V
at 50 Hz240 V
at 60 Hz100 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputYes
overvoltage overload capability1.25 × Vin rated, 500 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingat Vin = 115/230 V
at rated input voltage 100 V6.8 A
at rated input voltage 240 V3.4 A
current limitation of inrush current at 25 °C maximum60 A
I2t value maximum4.5 A²·s
fuse protection typeT10AH250V (internal)
fuse protection type in the feederRecommended miniature circuit breaker: from 16 A characteristic B, from 20 A characteristic B (for North America)
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableYes; via potentiometer
adjustable output voltage21.6 ... 26.4 V
relative overall tolerance of the voltage1 %
on slow fluctuation of input voltage0.5 %
on slow fluctuation of ohm loading0.5 %
maximum200 mV
display version for normal operationGreen LED for 24 V OK
type of signal at output-
behavior of the output voltage when switching onOvershoot of Vout < 10 %
response delay maximum1.5 s
maximum30 ms
rated value14.6 A
rated range0 ... 14.6 A; +50 ... +70 °C: Derating 2.0%/K
supplied active power typical350 W
bridging of equipmentNo
efficiency
efficiency in percent87 %
at rated output voltage for rated value of the output current typical46.8 W
closed-loop control
relative control precision of the output voltage load step of resistive load 50/100/50 % typical10 %
load step 50 to 100% typical20 ms
load step 100 to 50% typical20 ms
protection and monitoring
design of the overvoltage protection< 33.6 V
property of the output short-circuit proofYes
design of short-circuit protectionElectronic shutdown, automatic restart
response value current limitation16.06 ... 25.55 A
typical9 A
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum0.75 mA
EMC
for emitted interferenceEN 55032 Class B
for mains harmonics limitationNo
for interference immunityEN 55035
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus (UL 62368-1, CSA C22.2 NO 62368-1-14), File E151273
UKCA markingYes
EAC approvalNo
NEC Class 2No
BISYes; R-61003204
CB-certificateYes
MTBF at 25 °C700 000 h; according to SR-332, 100% full load (24 V, 14.6 A), input voltage: 115 V / 230 V AC
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
ULhazloc approvalNo
FM registrationNo
standards, specifications, approvals marine classification
shipbuilding approvalNo
American Bureau of Shipping Europe Ltd. (ABS)No
French marine classification society (BV)No
Det Norske Veritas (DNV)No
Lloyds Register of Shipping (LRS)No
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total1 480.9 kg
during manufacturing16.6 kg
during operation1 463.7 kg
after end of life0.25 kg
ambient conditions
during operation-25 ... +70 °C; with forced convection (ventilator); The device is not recommended to be placed on low thermal conductive surface (e. g. plastics).
during transport-40 ... +85 °C
during storage-40 ... +85 °C
relative humidity with condensation according to IEC 60068-2-38 maximum20 ... 90% without condensation
connection method
type of electrical connectionscrew terminal
at inputL, N, PE: 1 screw terminal each for 0.75 ... 2 mm² single-core/finely stranded
at output+, -: 3 screw terminals each for 0.75 ... 2 mm²
for auxiliary contacts-
mechanical data
width × height × depth of the enclosure115 × 30 × 215 mm
fastening methodWall mounting
DIN-rail mountingNo
S7 rail mountingNo
wall mountingYes
net weight0.84 kg
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing16.6 kg
global warming potential [CO2 eq] / during operation1463.7 kg
global warming potential [CO2 eq] / after end of life0.25 kg
global warming potential [CO2 eq] / total1480.9 kg