General information
product brand nameSIMATIC
product type designationPM 1507
product designationS7-1500 Power Module
type of current supply24 V/3 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85 ... 132 V
input voltage 2 at AC170 ... 264 V
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency45 ... 65 Hz
wide range inputNo
overvoltage overload capability2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingat Vin = 93/187 V
at rated input voltage 120 V1.4 A
at rated input voltage 230 V0.8 A
current limitation of inrush current at 25 °C maximum23 A
maximum3 ms
I2t value maximum1.3 A²·s
fuse protection typeT 3,15 A/250 V (not accessible)
fuse protection type in the feederRecommended miniature circuit breaker: 10 A characteristic B or 6 A characteristic C
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableNo
relative overall tolerance of the voltage1 %
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading0.1 %
maximum50 mV
maximum150 mV
display version for normal operationLED green for 24 V OK; LED red for error; LED yellow for stand-by
behavior of the output voltage when switching onNo overshoot of Vout (soft start)
response delay maximum1.5 s
typical10 ms
rated value3 A
rated range0 ... 3 A
supplied active power typical72 W
on short-circuiting during the start-up typical12 A
at short-circuit during operation typical12 A
on short-circuiting during the start-up70 ms
at short-circuit during operation70 ms
bridging of equipmentYes
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent87 %
at rated output voltage for rated value of the output current typical11 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical1 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical3 %
load step 10 to 90% typical5 ms
load step 90 to 10% typical5 ms
maximum5 ms
protection and monitoring
design of the overvoltage protectionAdditional control loop, limitation (closed loop control) at < 28.8 V
property of the output short-circuit proofYes
design of short-circuit protectionElectronic shutdown, automatic restart
response value current limitation3.15 ... 3.6 A
typical3.4 A
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
typical0.4 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
UKCA markingYes
EAC approvalYes
Regulatory Compliance Mark (RCM)Yes
NEC Class 2No
BISYes; R-41183539
CB-certificateYes
MTBF at 40 °C1 611 993 h
standards, specifications, approvals hazardous environments
IECExYes; IECEx Ex nA nC IIC T4 Gc
ATEXYes; ATEX (EX) II 3G Ex ec nC IIC T4 Gc
ULhazloc approvalYes; cULus (ANSI/ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455
UKEXYes
CCC for hazardous zone according to GB standardYes
FM registrationYes; Class I, Div. 2, Group ABCD, T4
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
French marine classification society (BV)Yes
Det Norske Veritas (DNV)Yes
Lloyds Register of Shipping (LRS)No
ambient conditions
during operation0 ... 60 °C; with natural convection
in horizontal mounting position during operation0 ... 60 °C
in vertical mounting position during operation0 ... 40 °C
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionScrew-/spring clamp connection
at inputL, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
at outputL+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
removable terminal at inputYes
removable terminal at outputYes
mechanical data
width × height × depth of the enclosure50 × 147 × 129 mm
installation width × mounting height50 mm × 205 mm
top40 mm
bottom40 mm
left0 mm
right0 mm
fastening methodCan be mounted onto S7-1500 rail
DIN-rail mountingNo
S7 rail mountingYes
wall mountingNo
housing can be lined upYes
net weight0.45 kg
further information internet links
identification linkYes; acc. to IEC 61406-1:2022
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)