General information
product brand nameSITOP
product type designationPSU100P
product designationPower supply SITOP
type of current supply24 V/5 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85 ... 132 V
input voltage 2 at AC170 ... 264 V
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputNo
overvoltage overload capabilityImplemented internally with varistor
buffering time for rated value of the output current in the event of power failure minimum40 ms
operating condition of the mains bufferingat Vin = 120/230 V
at rated input voltage 120 V2.25 A
at rated input voltage 230 V1.24 A
current limitation of inrush current at 25 °C maximum15 A
I2t value maximum0.6 A²·s
fuse protection typeT 3.15 A
fuse protection type in the feederRecommended miniature circuit breaker: from 6 A characteristic C/B
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableNo
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading0.2 %
maximum50 mV
maximum100 mV
display version for normal operationGreen LED: 24 V OK; red LED flashing: "overload/short-circuit"
type of signal at outputRelay contact (NO contact, rating 30 V AC/ 0.5 A; 30 V DC/1 A) for 24 V OK
behavior of the output voltage when switching onOvershoot of Vout < 3 %
response delay maximum1.5 s
typical22 ms
maximum100 ms
rated value5 A
rated range0 ... 5 A
supplied active power typical133 W
on short-circuiting during the start-up typical20 A
at short-circuit during operation typical20 A
on short-circuiting during the start-up50 ms
at short-circuit during operation50 ms
bridging of equipmentYes; Symmetric wiring required
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent90 %
at rated output voltage for rated value of the output current typical12.9 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.2 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical1 %
maximum2 ms
protection and monitoring
design of the overvoltage protection< 29 V
property of the output short-circuit proofYes
design of short-circuit protectionElectronic shutdown, automatic restart
typical5.5 A
maximum6 A
typical5 A
display version for overload and short circuitRed LED flashing for "overload/short-circuit"
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
typical1 mA
protection class IPIP67
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1)
EAC approvalYes
NEC Class 2No
CB-certificateNo
MTBF at 40 °C1 500 000 h
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
ULhazloc approvalNo
FM registrationNo
standards, specifications, approvals marine classification
shipbuilding approvalNo
American Bureau of Shipping Europe Ltd. (ABS)No
French marine classification society (BV)No
Det Norske Veritas (DNV)No
Lloyds Register of Shipping (LRS)No
ambient conditions
during operation-25 ... +60 °C; with natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 607213K6 without direct sunlight
connection method
type of electrical connectionscrew terminal
at inputL1, N, PE: Plug connector 7/8" (counterpart see "Operating Instructions (compact)")
at output+, -: Plug connector M12-L coded (counterpart see "Operating Instructions (compact)")
for auxiliary contactsAlarm signals: M12 plug-in connector 4-pin
removable terminal at inputYes
removable terminal at outputYes
mechanical data
width × height × depth of the enclosure120 × 181 × 60.5 mm
installation width × mounting height120 mm × 170 mm
top50 mm
bottom0 mm
left0 mm
right0 mm
fastening methodWall mounting
DIN-rail mountingNo
S7 rail mountingNo
wall mountingYes
housing can be lined upYes
net weight1.1 kg
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)