Genel bilgiler
product brand nameLOGO!Power
product type designationLOGO!Power
product designationPower supply LOGO!Power
type of current supply24 V/1,3 A
input
type of the power supply network1-phase AC veya DC
phase number1
voltage curve at inputAC/DC
minimum rated value100 V
maximum rated value240 V
initial value85 V
full-scale value264 V
input voltage at DC110... 300 V
at 50 Hz240 V
at 60 Hz100 V
line frequency50/60 Hz
line frequency47... 63 Hz
wide range inputVar
overvoltage overload capability300 V AC for 1 s
buffering time for rated value of the output current in the event of power failure minimum40 ms
operating condition of the mains bufferingVin = 187 V
at rated input voltage 120 V0,7 A
at rated input voltage 230 V0,35 A
current limitation of inrush current at 25 °C maximum25 A
I2t value maximum0,8 A²·s
fuse protection typeinternal
fuse protection type in the feederRecommended miniature circuit breaker: from 6 A characteristic B veya from 2 A characteristic C
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledVar
product function output voltage stabilizedVar
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableVar; via potentiometer
adjustable output voltage22,2... 26,4 V
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0,1 %
on slow fluctuation of ohm loading0,1 %
maximum200 mV
typical30 mV
maximum300 mV
typical50 mV
display version for normal operationGreen LED for output voltage OK
behavior of the output voltage when switching onYok overshoot of Vout (soft start)
response delay maximum0,5 s
typical100 ms
rated value1,3 A
rated range0... 1,3 A; +55... +70 °C: Derating 2%/K
supplied active power typical31,2 W
bridging of equipmentVar
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent86 %
at rated output voltage for rated value of the output current typical5,1 W
during no-load operation maximum0,3 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0,2 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical1 %
load step 10 to 90% typical1 ms
load step 90 to 10% typical1 ms
protection and monitoring
design of the overvoltage protection< 60 V
property of the output short-circuit proofVar
design of short-circuit protectionConstant current characteristic
typical1,7 A
when switching on150% Iout rated tipik 200 ms
in normal operationoverload capability 150% Iout rated tipik 200 ms
maximum1,7 A
measuring point for output currentVar; 50 mV =^ 1,3 A
safety
galvanic isolation between input and outputVar
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass II (without protective conductor)
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationnot applicable
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingVar
UL onayıVar; cULus-Listed (UL 508, CSA C22.2 Yok. 107,1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 Yok. 60950), File E151273, NEC class 2 (acc. to UL 1310)
EAC approvalVar
NEC Class 2Var; according to UL1310, File E151273
SEMI F47Var
BISVar; R-41188271
CB-certificateVar
MTBF at 40 °C3.094.996 h
standards, specifications, approvals hazardous environments
IECExYok
ATEXYok
ULhazloc approvalYok
FM registrationYok
standards, specifications, approvals marine classification
shipbuilding approvalVar
American Bureau of Shipping Europe Ltd. (ABS)Var
French marine classification society (BV)Var
Det Norske Veritas (DNV)Var
Lloyds Register of Shipping (LRS)Var
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationVar
total141,9 kg
during manufacturing2,3 kg
during operation139,5 kg
after end of life0,08 kg
Siemens eco profile (SEP)Siemens EcoTech
ambient conditions
during operation-25... +70 °C; with natural convection
during transport-40... +85 °C
during storage-40... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5... 95% no condensation
connection method
type of electrical connectionscrew terminal
at inputL, N: 1 screw terminal her biri for 0,5... 2,5 mm2 single-core/finely stranded
at output+, -: 1 screw terminal her biri for 0,5... 2,5 mm²
for auxiliary contacts-
mechanical data
width × height × depth of the enclosure36 × 90 × 53 mm
installation width × mounting height36 mm × 130 mm
top20 mm
bottom20 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15, direct mounting in different mounting positions
DIN-rail mountingVar
S7 rail mountingYok
wall mountingVar
housing can be lined upVar
net weight0,12 kg
additional information
other informationSpecifications rated input voltage ve ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing2,3 kg
global warming potential [CO2 eq] / during operation139,5 kg
global warming potential [CO2 eq] / after end of life0,08 kg
global warming potential [CO2 eq] / total141,9 kg