Genel bilgiler
product brand nameSIMATIC
product type designationPM 1507
product designationS7-1500 Power Module
type of current supply24 V/8 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85... 132 V
input voltage 2 at AC170... 264 V
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency45... 65 Hz
wide range inputYok
overvoltage overload capability2,3 × Vin rated, 1,3 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingVin = 93/187 V
at rated input voltage 120 V3,7 A
at rated input voltage 230 V1,7 A
current limitation of inrush current at 25 °C maximum62 A
maximum3 ms
I2t value maximum12 A²·s
fuse protection typeT 6,3 A/250 V (not accessible)
fuse protection type in the feederRecommended miniature circuit breaker: 16 A characteristic B veya 10 A characteristic C
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledVar
product function output voltage stabilizedVar
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableYok
relative overall tolerance of the voltage1 %
on slow fluctuation of input voltage0,1 %
on slow fluctuation of ohm loading0,1 %
maximum50 mV
maximum150 mV
display version for normal operationLED green for 24 V OK; LED red for error; LED yellow for stand-by
behavior of the output voltage when switching onYok overshoot of Vout (soft start)
response delay maximum1,5 s
typical10 ms
rated value8 A
rated range0... 8 A
supplied active power typical192 W
on short-circuiting during the start-up typical35 A
at short-circuit during operation typical35 A
on short-circuiting during the start-up70 ms
at short-circuit during operation70 ms
bridging of equipmentVar
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent90 %
at rated output voltage for rated value of the output current typical21 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0,1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical2 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical3 %
load step 10 to 90% typical5 ms
load step 90 to 10% typical5 ms
maximum5 ms
protection and monitoring
design of the overvoltage protectionAdditional control loop, limitation (closed loop control) < 28,8 V
property of the output short-circuit proofVar
design of short-circuit protectionElectronic shutdown, automatic restart
response value current limitation8,4... 9,6 A
typical9 A
safety
galvanic isolation between input and outputVar
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3,5 mA
typical1,3 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingVar
UL onayıVar; cULus-Listed (UL 508, CSA C22.2 Yok. 142), File E143289
UKCA markingVar
EAC approvalVar
Regulatory Compliance Mark (RCM)Var
NEC Class 2Yok
BISVar; R-41183539
CB-certificateVar
MTBF at 40 °C1.362.918 h
standards, specifications, approvals hazardous environments
IECExVar; IECEx Ex nA nC IIC T3 Gc
ATEXVar; ATEX (EX) II 3G Ex ec nC IIC T3 Gc
ULhazloc approvalVar; cULus (ANSI/ISA 12.12.01, CSA C22.2 Yok.213) Class I, Div. 2, Group ABCD, T3, File E330455
UKEXVar
CCC for hazardous zone according to GB standardVar
FM registrationVar; Class I, Div. 2, Group ABCD, T4
standards, specifications, approvals marine classification
shipbuilding approvalVar
American Bureau of Shipping Europe Ltd. (ABS)Var
French marine classification society (BV)Var
Det Norske Veritas (DNV)Var
Lloyds Register of Shipping (LRS)Yok
ambient conditions
during operation0... 60 °C; with natural convection
in horizontal mounting position during operation0... 60 °C
in vertical mounting position during operation0... 40 °C
during transport-40... +85 °C
during storage-40... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5... 95% no condensation
connection method
type of electrical connectionScrew-/spring clamp connection
at inputL, N, PE: 1 screw terminal her biri for 0,5... 2,5 mm²
at outputL+, M: 2 spring-loaded terminals her biri for 0,5 to 2,5 mm²
removable terminal at inputVar
removable terminal at outputVar
mechanical data
width × height × depth of the enclosure75 × 147 × 129 mm
installation width × mounting height75 mm × 205 mm
top40 mm
bottom40 mm
left0 mm
right0 mm
fastening methodCan be mounted onto S7-1500 rail
DIN-rail mountingYok
S7 rail mountingVar
wall mountingYok
housing can be lined upVar
net weight0,74 kg
further information internet links
identification linkVar; acc. to IEC 61406-1:2022
additional information
other informationSpecifications rated input voltage ve ambient temperature +25 °C (unless otherwise specified)