General information
product brand nameSITOP
product type designationPSU6200
product designationPower supply SITOP PSU6200
type of current supply24 V/20 A
input
type of the power supply network1-phase AC or DC
phase number1
voltage curve at inputAC/DC
minimum rated value120 V
maximum rated value240 V
initial value85 V
full-scale value264 V
supply voltage at DC110 ... 240 V
input voltage at DC85 ... 275 V
at 50 Hz240 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputYes
overvoltage overload capability300 V AC for 30 s
buffering time for rated value of the output current in the event of power failure minimum25 ms
operating condition of the mains bufferingat Vin = 240 V
at rated input voltage 120 V4.4 A
at rated input voltage 240 V2.2 A
current limitation of inrush current at 25 °C maximum12 A
fuse protection type10 A
fuse protection type in the feederCircuit breaker from 6 A characteristic B to 16 A characteristic C or circuit breaker 3RV2011-1HA10 (setting 8A) or 3RV2711-1HD10 (UL 489)
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
number of outputs1
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableYes; via potentiometer
adjustable output voltage24 ... 28 V; max. 480 W (576 W up to 45°C)
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0.2 %
on slow fluctuation of ohm loading0.2 %
maximum80 mV
typical50 mV
maximum100 mV
typical60 mV
display version for normal operationGreen LED for 24 V OK
type of signal at outputElectronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface
behavior of the output voltage when switching onOvershoot of Vout approx. 3 %
response delay maximum0.5 s
typical100 ms
rated value20 A
rated range0 ... 20 A; 24 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical480 W
on short-circuiting during the start-up typical30 A
at short-circuit during operation typical30 A
parallel switching of outputscan be set with DIP switch
bridging of equipmentYes; switchable characteristic
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent95.5 %
at rated output voltage for rated value of the output current typical25 W
during no-load operation maximum2.6 W
closed-loop control
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical3 %
load step 10 to 90% typical0.5 ms
load step 90 to 10% typical0.5 ms
maximum1 ms
protection and monitoring
design of the overvoltage protection< 32 V
property of the output short-circuit proofYes
design of short-circuit protectionShutdown and periodic restart attempts
typical30 A
in normal operationoverload capability 150 % Iout rated up to 5 s/min
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
UKCA markingYes
EAC approvalYes
Regulatory Compliance Mark (RCM)Yes
NEC Class 2No
SEMI F47Yes
BISYes; R-41188271
CB-certificateYes
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
ULhazloc approvalNo
FM registrationNo
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
French marine classification society (BV)No
Det Norske Veritas (DNV)Yes
Lloyds Register of Shipping (LRS)No
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total614.4 kg
during manufacturing33.9 kg
during operation623.6 kg
after end of life0.56 kg
Siemens eco profile (SEP)Siemens EcoTech
ambient conditions
during operation-30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionpush-in terminals
at inputL1/+, L2/N/-, PE: push-in for 0.5 ... 4 mm² single-core/finely stranded
at output+1, +2, -1, -2, -3: push-in for 0.5 ... 6 mm²
for auxiliary contacts13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm²
mechanical data
width × height × depth of the enclosure70 × 135 × 155 mm
installation width × mounting height70 mm × 225 mm
top45 mm
bottom45 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingYes
S7 rail mountingNo
wall mountingNo
housing can be lined upYes
net weight1.5 kg
accessories
electrical accessoriesBuffer module, redundancy module
mechanical accessoriesIdentification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0
further information internet links
identification linkYes; acc. to IEC 61406-1:2022
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing33.9 kg
global warming potential [CO2 eq] / during operation623.6 kg
global warming potential [CO2 eq] / after end of life0.56 kg
global warming potential [CO2 eq] / total614.4 kg