General information
product brand nameSIMATIC
product type designationET 200SP
product designationDesign power supply for SIMATIC ET 200SP
type of current supply24 V/5 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85 ... 132 V
input voltage 2 at AC170 ... 264 V
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputNo
overvoltage overload capability2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingat Vin = 93/187 V
at rated input voltage 120 V2.16 A
at rated input voltage 230 V1.22 A
current limitation of inrush current at 25 °C maximum45 A
I2t value maximum3.15 A²·s
fuse protection typeT 3,15 A/250 V (not accessible)
fuse protection type in the feederrecommended LS switch: B/C 6 A/3 A
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableYes; via potentiometer
adjustable output voltage22.8 ... 28 V
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading1 %
maximum150 mV
typical50 mV
maximum240 mV
typical150 mV
display version for normal operationGreen LED for 24 V OK
type of signal at outputRelay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching onOvershoot of Vout < 3 %
response delay maximum0.3 s
typical30 ms
rated value5 A
rated range0 ... 6 A; 5 A up to +60°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical120 W
on short-circuiting during the start-up typical15 A
at short-circuit during operation typical15 A
on short-circuiting during the start-up800 ms
at short-circuit during operation800 ms
bridging of equipmentYes
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent88 %
at rated output voltage for rated value of the output current typical17 W
during no-load operation maximum2.7 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical0.3 %
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical3 %
load step 10 to 90% typical1 ms
load step 90 to 10% typical1 ms
protection and monitoring
design of the overvoltage protectionprotection against overvoltage in case of internal fault Vout < 31.8 V
property of the output short-circuit proofYes
design of short-circuit protectionConstant current characteristic
response value current limitation7 ... 7.5 A
in normal operationoverload capability 150 % Iout rated up to 5 s/min
typical7 A
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
typical1 mA
protection class IPIP20
EMC
for emitted interferenceEN 61000-6-3 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL61010-2-201, CSA C22.2 No.142)
EAC approvalYes
NEC Class 2No
CB-certificateYes
MTBF at 40 °C1 598 441 h
standards, specifications, approvals hazardous environments
IECExYes; IECEx Ex ec nC IIC T3 Gc
ATEXYes; ATEX (EX) II 3G Ex ec nC IIC T3 Gc
ULhazloc approvalYes
UKEXYes
CCC for hazardous zone according to GB standardYes
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)No
French marine classification society (BV)Yes
Det Norske Veritas (DNV)Yes
Lloyds Register of Shipping (LRS)No
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total474.9 kg
during manufacturing9.4 kg
during operation465 kg
after end of life0.35 kg
ambient conditions
during operation-30 ... +70 °C; with natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionpush-in terminals
at inputL, N, PE: 1 push-in terminal each for 0.2 ... 2.5 mm² single-core/finely stranded
at output+, -: 2 push-in terminals each for 0.2 ... 2.5 mm²
for auxiliary contactsSignaling contact: 2 push-in terminals for 0.2 ... 2.5 mm²
for signaling contact2 push-in terminals for 0.2 ... 2.5 mm²
removable terminal at inputYes
removable terminal at outputYes
mechanical data
width × height × depth of the enclosure160 × 117 × 74 mm
installation width × mounting height160 mm × 174 mm
top50 mm
bottom50 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingYes
S7 rail mountingNo
wall mountingNo
housing can be lined upYes
net weight0.5 kg
accessories
electrical accessoriesRedundancy module, buffer module, selectivity module, DC UPS
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing9.4 kg
global warming potential [CO2 eq] / during operation465 kg
global warming potential [CO2 eq] / after end of life0.35 kg
global warming potential [CO2 eq] / total474.9 kg