General information
product brand nameSITOP
product type designationSEL1600
product designationSITOP Selectivity module
type of current supplyselectivity module, 4 x 10 A, expansion module
input
type of the power supply networkControlled DC voltage
supply voltage at DC rated value24 V
input voltage at DC20.4 ... 30 V
overvoltage overload capability35 V
input current at rated input voltage 24 V rated value40 A
output
voltage curve at outputcontrolled DC voltage
formula for output voltageUe - approx. 0.25 V
relative overall tolerance of the voltage noteIn accordance with the supplying input voltage
number of outputs4
output current up to 60 °C per output rated value10 A; +60 ... +70 °C: Derating 2%/K
adjustable current response value current of the current-dependent overload release0.5 ... 10 A
type of response value settingvia display and IO-Link interface on the basic module
response delay maximum10 s
product feature parallel switching of outputsYes; Two outputs located next to each other within one module
type of outputs connectionswitch-on of all outputs after power-up of the supply voltage > 20 V, for sequential switch-on, delay time of 25 ms, 100 ms, or "load-optimized" configurable via display and IO-Link interface, user-defined times can be configured via IO-Link interface
efficiency
efficiency in percent98 %
power loss [W] at rated output voltage for rated value of the output current typical10 W
switch-off characteristic
of the excess currentswitch-off characteristic selectable: Ia = 1.0 ... 1.25 x set value, shutdown after typ. 10 s; Ia = 1.0 ... 1.5 x set value, shutdown after typ. 5 s; Ia = 1.0 ... 1.7 x set value, shutdown after typ. 1 s
of the current limitationIa = 1.8 x set value, switch-off after typ. 10-100 ms
of the immediate switch-offIout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
design of the reset device/resetting mechanismvia buttons for each output and IO-Link interface on the basic module
remote reset functionvia RESET contact on the basic module
protection and monitoring
fuse protection type at input15 A per output (not accessible)
display version for normal operation3-color LED per output
design of the switching contact for signaling functionvia common signaling contact basic module
safety
galvanic isolation between input and output at switch-offNo
standard for safetyaccording to EN 62368-1
operating resource protection classClass III
protection class IPIP20
for emitted interferenceEN 61000-6-3
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259
UKCA markingYes
CB-certificateYes
MTBF at 40 °C600 000 h
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
standards, specifications, approvals marine classification
shipbuilding approvalYes
Det Norske Veritas (DNV)Yes
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total298.7 kg
during manufacturing24 kg
during operation274 kg
after end of life0.56 kg
ambient conditions
during operation-40 ... +70 °C; with natural convection
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionscrew terminal
at input-1, +1, +2, -2: one screw terminal each for 0.5 ... 16 mm²
at output+, -: each output 1 common screw plug-in terminal for 0.5 ... 2.5 mm²
removable terminal at inputNo
removable terminal at outputYes
mechanical data
width × height × depth of the enclosure45 × 145 × 125 mm
installation width × mounting height45 mm × 225 mm
top40 mm
bottom40 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingYes
S7 rail mountingNo
wall mountingNo
housing can be lined upYes
net weight0.4 kg
accessories
accessories included6EP4990-8KK00-0XU0: SITOP SEL1600 Connection Set for SEL1600 system, contents: COM connecting cable and input wiring bracket
electrical accessories6EP4990-8KK00-0XU0: SITOP SEL1600 Connection Set for SEL1600 system, contents: COM connecting cable and input wiring bracket (only as a spare part, already included with the expansion module)
further information internet links
identification linkYes; acc. to IEC 61406-1:2022
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)