General information
product brand nameSITOP
product type designationBAT1600
product designation3.2 Ah Pb
type of batterymaintenance-free lead-acid batteries
product versionExtension module/battery module
electrical data
at -10 °C recommended28 V
at 0 °C recommended28 V
at 10 °C recommended27.8 V
at 20 °C recommended27.3 V
at 30 °C recommended26.8 V
at 40 °C recommended26.6 V
at 50 °C recommended26.3 V
output
battery capacity3.2 A·h
output current rated value20 A
output current in buffering mode maximum20 A
peak current60 A; for 30 ms
charging current maximum0.8 A
output voltage at DC rated value24 V
interfaces
communication functionYes
protection and monitoring
design of short-circuit protection25A / 32V Maxi flat fuse
design of the overload protectionValve control
display version for normal operationThree-color: green = Buffer ready; yellow = Buffer endangered; red = Buffer not possible
safety
operating resource protection classClass III
protection class IPIP20
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 61010-1, UL61010-2-201 , CSA C22.2 No. 61010-1, CSA C22.2 NO 61010-2-201), File E143289
UKCA markingYes
type of certification CB-certificateYes
standards, specifications, approvals hazardous environments
IECExYes; IECEx Ex ec IIC T4 Gc
ATEXYes; ATEX (EX) II 3G ex ec IIC T4 Gc
ULhazloc approvalYes
CCC for hazardous zone according to GB standardYes
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
Det Norske Veritas (DNV)in preparation
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total14.787 kg
during manufacturing9.373 kg
during operation3.733 kg
after end of life0.494 kg
ambient conditions
ambient conditionFor storage, mounting and operation of lead-acid batteries, the relevant DIN/VDE regulations or country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be at least 50 cm away.
during operation-15 ... +50 °C
during transport-20 ... +50 °C
during storage-20 ... +40 °C
relative temporary capacity loss at 20 °C in a month typical3 %
service life
typicalcapacity falls to 80 % of original capacity (according to EUROBAT)
at 20 °C typical4 a
at 30 °C typical2 a
at 40 °C typical1 a
at 50 °C typical0.5 a
noteAlong with the storage and operating temperature, other factors such as the duration of the storage period and the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, and within the temperature range 0 to +20 °C.
connection method
type of electrical connectionscrew terminal
for UPS module1 screw terminal each for 0.5 ... 10 mm² for + BAT and - BAT
for control circuit and status message1 screw terminal each for 0.2 ... 2.5 mm²
mechanical data
width × height × depth of the enclosure89 × 156 × 169 mm
installation width × mounting height89 mm × 256 mm
top50 mm
bottom50 mm
left0 mm
right0 mm
fastening methodsnaps onto DIN rail EN 60715 35x15 or wall mounting with accessories wall mounting set 6EP4990-0MK00-0XU0
DIN-rail mountingYes
S7 rail mountingYes
wall mountingNo
net weight3.8 kg
number of cells2
accessories
product component included2x Maxi Fuse 25 A/32 V
mechanical accessoriesBAT1600 wall mounting kit 6EP4990-0MK00-0XU0
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)