General information
product brand nameSITOP
product type designationPSU6200
product designationPower supply SITOP PSU6200
type of current supply12 V/7 A
input
type of the power supply network1-phase AC or DC
phase number1
voltage curve at inputAC/DC
minimum rated value120 V
maximum rated value240 V
initial value85 V
full-scale value264 V
supply voltage at DC120 ... 240 V
input voltage at DC99 ... 275 V
at 50 Hz240 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47 ... 63 Hz
wide range inputYes
overvoltage overload capability300 V AC for 30 s
buffering time for rated value of the output current in the event of power failure minimum90 ms
operating condition of the mains bufferingat Vin = 240 V
at rated input voltage 120 V1.4 A
at rated input voltage 240 V0.8 A
current limitation of inrush current at 25 °C maximum29 A
fuse protection type5 A
fuse protection type in the feederCircuit breaker 4 A characteristic C or 6 A characteristic B/C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledYes
product function output voltage stabilizedYes
number of outputs1
output voltage at DC rated value12 V
at output 1 at DC rated value12 V
at output 1 at DC12 V
output voltage adjustableYes; via potentiometer
adjustable output voltage12 ... 15.5 V; max. 84 W (100 W up to 45°C)
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0.1 %
on slow fluctuation of ohm loading0.2 %
maximum30 mV
typical20 mV
maximum100 mV
typical60 mV
display version for normal operationGreen LED for 24 V OK
type of signal at outputElectronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K.
behavior of the output voltage when switching onOvershoot of Vout < 2 %
response delay maximum0.5 s
typical100 ms
rated value7 A
rated range0 ... 7 A; 8.4 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical84 W
on short-circuiting during the start-up typical8.4 A
at short-circuit during operation typical8.4 A
bridging of equipmentNo
efficiency
efficiency in percent87.1 %
at rated output voltage for rated value of the output current typical13 W
during no-load operation maximum1.8 W
closed-loop control
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical3 %
load step 10 to 90% typical1 ms
load step 90 to 10% typical1 ms
maximum2 ms
protection and monitoring
design of the overvoltage protection< 20 V
property of the output short-circuit proofYes
design of short-circuit protectionShutdown and periodic restart attempts
typical8.4 A
in normal operationoverload capability 150 % Iout rated up to 5 s/min
safety
galvanic isolation between input and outputYes
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3.5 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingYes
UL approvalYes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
UKCA markingYes
EAC approvalYes
Regulatory Compliance Mark (RCM)Yes
NEC Class 2No
SEMI F47Yes
BISYes; R-41188271
CB-certificateYes
standards, specifications, approvals hazardous environments
IECExNo
ATEXNo
ULhazloc approvalNo
FM registrationNo
standards, specifications, approvals marine classification
shipbuilding approvalYes
American Bureau of Shipping Europe Ltd. (ABS)Yes
French marine classification society (BV)No
Det Norske Veritas (DNV)Yes
Lloyds Register of Shipping (LRS)No
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationYes
total347.3 kg
during manufacturing18 kg
during operation328.8 kg
after end of life0.3 kg
ambient conditions
during operation-30 ... +70 °C; with natural convection a monotonically increasing start-up from -25 °C, safe start-up from -40 °C
during transport-40 ... +85 °C
during storage-40 ... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connectionpush-in terminals
at inputL1/+, L2/N/-, PE: push-in for 0.5 ... 4 mm² single-core/finely stranded
at output+1, +2, -1, -2, -3: push-in for 0.5 ... 2.5 mm²
for auxiliary contacts13, 14 (alarm signal): 1 push-in terminal each for 0.2 ... 1.5 mm²
mechanical data
width × height × depth of the enclosure35 × 135 × 125 mm
installation width × mounting height35 mm × 225 mm
top45 mm
bottom45 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingYes
S7 rail mountingNo
wall mountingNo
housing can be lined upYes
net weight0.7 kg
accessories
electrical accessoriesRedundancy module
mechanical accessoriesIdentification labels SIMATIC ET 200SP 6ES7193-6LF30-0AW0
further information internet links
identification linkYes; acc. to IEC 61406-1:2022
additional information
other informationSpecifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing18 kg
global warming potential [CO2 eq] / during operation328.8 kg
global warming potential [CO2 eq] / after end of life0.3 kg
global warming potential [CO2 eq] / total347.3 kg