Genel bilgiler
product brand nameSITOP
product type designationBAT1600
product designationBattery module 7 Ah Pb
type of batterybakım gerektirmez lead-acid batteries
product versionExtension module/battery module
electrical data
at -10 °C recommended28 V
at 0 °C recommended28 V
at 10 °C recommended27,8 V
at 20 °C recommended27,3 V
at 30 °C recommended26,8 V
at 40 °C recommended26,6 V
at 50 °C recommended26,3 V
output
battery capacity7 A·h
output current rated value40 A
output current in buffering mode maximum40 A
peak current120 A; 1x 120 A for 30 ms/1x 60 A for 5 s per minute
charging current maximum1,75 A
output voltage at DC rated value24 V
number of parallel-switched equipment resources for increasing the power6
interfaces
communication functionVar
protection and monitoring
design of short-circuit protection50A / 32V Maxi flat fuse
design of the overload protectionValve control
display version for normal operationThree-color: green = Buffer ready; yellow = Buffer endangered; red = Buffer not possible
safety
operating resource protection classClass III
protection class IPIP20
standards, specifications, approvals
CE markingVar
UL onayıVar; cULus (UL 61010-1 3rd Ed., UL 61010-2-201 2nd Ed.), File E143289
UKCA markingVar
Regulatory Compliance Mark (RCM)Var
type of certification CB-certificateVar
standards, specifications, approvals hazardous environments
IECExYok
ATEXYok
CCC for hazardous zone according to GB standardYok
standards, specifications, approvals marine classification
shipbuilding approvalVar
American Bureau of Shipping Europe Ltd. (ABS)in preparation
Det Norske Veritas (DNV)in preparation
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationVar
total25,62 kg
during manufacturing14,8 kg
during operation8,167 kg
after end of life0,78 kg
ambient conditions
ambient conditionFor storage, mounting ve operation of lead-acid batteries, the relevant DIN/VDE regulations veya country-specific regulations (e.g. VDE 0510 Part 2/EN 50272-2) must be observed. You must ensure that the battery site is sufficiently ventilated. Possible sources of ignition must be least 50 cm away.
during operation-15... +50 °C
during transport-20... +50 °C
during storage-20... +40 °C
relative temporary capacity loss at 20 °C in a month typical3 %
installation altitude at height above sea level maximum4.000 m
service life
typicalReduction of capacity to 80% of the original capacity (according to EUROBAT) - Attention: 80% capacity does not mean 80% of the buffer time; the buffer time is even shorter due to the increase in internal resistance the end of life
at 10 °C typical4 a
at 20 °C typical4 a
at 30 °C typical2 a
at 40 °C typical1 a
at 50 °C typical0,5 a
noteAlong with the storage ve operating temperature, other factors such as the duration of the storage period ve the charge status during storage have a decisive influence on the possible useful life. Batteries should therefore be stored as briefly as possible, always fully charged, ve within the temperature range 0 to +20 °C.
connection method
type of electrical connectionscrew terminal
for UPS module1 screw terminal her biri for 0,5... 16 mm² for + BAT ve - BAT
for control circuit and status message1 screw terminal her biri for 0,2... 2,5 mm²
mechanical data
width × height × depth of the enclosure157 × 156 × 138 mm
installation width × mounting height157 mm × 256 mm
top50 mm
bottom50 mm
left0 mm
right0 mm
fastening methodcan be screwed onto flat surface (keyhole mounting for hooking in to M4 screws)
DIN-rail mountingYok
S7 rail mountingYok
wall mountingVar
net weight6 kg
number of batteries2
number of cells2
accessories
product component includedaccessory kit with 2x FKS fuse 50 A, fire protection cap, power connector, signal connector
mechanical accessoriesBAT1600 wall mounting kit 6EP4990-0MK00-0XU0
additional information
other informationSpecifications rated input voltage ve ambient temperature +25 °C (unless otherwise specified)