Genel bilgiler
product brand nameSITOP
product type designationmodular
product designationPower supply SITOP modular
type of current supply24 V/40 A
input
type of the power supply network3-phase AC
phase number3
voltage curve at inputAC
minimum rated value400 V
maximum rated value500 V
initial value320 V
full-scale value550 V
supply voltage at ACStarting from Vin > 340 V
at 50 Hz400 V
at 60 Hz500 V
line frequency50/60 Hz
line frequency47... 63 Hz
wide range inputVar
overvoltage overload capability2,3 × Vin rated, 1,3 ms
buffering time for rated value of the output current in the event of power failure minimum6 ms
operating condition of the mains bufferingVin = 400 V
at rated input voltage 400 V2,2 A
current limitation of inrush current at 25 °C maximum70 A
I2t value maximum2,8 A²·s
fuse protection typeyok
fuse protection type in the feederRequired: 3-pole connected miniature circuit breaker 10... 16 A characteristic C veya circuit breaker 3RV2011-1DA10 (setting 3 A) veya 3RV2711-1DD10 (UL 489)
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledVar
product function output voltage stabilizedVar
output voltage at DC rated value24 V
at output 1 at DC rated value24 V
at output 1 at DC24 V
output voltage adjustableVar; via potentiometer
adjustable output voltage24... 28,8 V; maks. 960 W
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0,1 %
on slow fluctuation of ohm loading0,2 %
maximum100 mV
maximum200 mV
display version for normal operationGreen LED for 24 V OK
type of signal at outputvia signaling module (6EP1961-3BA10)
behavior of the output voltage when switching onYok overshoot of Vout (soft start)
response delay maximum2,5 s
maximum500 ms
rated value40 A
rated range0... 40 A; +60... +70 °C: Derating 2%/K
supplied active power typical960 W
at short-circuit during operation typical120 A
at short-circuit during operation25 ms
on short-circuiting during the start-up typical46 A
bridging of equipmentVar; switchable characteristic
number of parallel-switched equipment resources for increasing the power2
efficiency
efficiency in percent90 %
at rated output voltage for rated value of the output current typical106 W
closed-loop control
relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical1 %
relative control precision of the output voltage load step of resistive load 50/100/50 % typical2 %
load step 50 to 100% typical4 ms
load step 100 to 50% typical4 ms
maximum10 ms
protection and monitoring
design of the overvoltage protection< 35 V
property of the output short-circuit proofVar
design of short-circuit protectionAlternatively, constant current characteristic yaklaşık 46 A veya latching shutdown
typical46 A
typical46 A
display version for overload and short circuitLED yellow for "overload", LED red for "latching shutdown"
safety
galvanic isolation between input and outputVar
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3,5 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingVar
UL onayıVar; UL-Listed (UL 508), File E197259
UKCA markingVar
EAC approvalVar
Regulatory Compliance Mark (RCM)Var
NEC Class 2Yok
CB-certificateYok
MTBF at 40 °C485.437 h
standards, specifications, approvals hazardous environments
IECExYok
ATEXYok
ULhazloc approvalYok
FM registrationYok
standards, specifications, approvals marine classification
shipbuilding approvalYok
American Bureau of Shipping Europe Ltd. (ABS)Yok
French marine classification society (BV)Yok
Det Norske Veritas (DNV)Yok
Lloyds Register of Shipping (LRS)Yok
standards, specifications, approvals Environmental Product Declaration
Environmental Product DeclarationVar
total2.762,3 kg
during manufacturing76,5 kg
during operation2.684,2 kg
after end of life0,64 kg
ambient conditions
during operation0... 70 °C; with natural convection
during transport-40... +85 °C
during storage-40... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5... 95% no condensation
connection method
type of electrical connectionscrew terminal
at inputL1, L2, L3, PE: 1 screw terminal her biri for 0,2... 4 mm² single-core/finely stranded
at output+, -: 2 screw terminals her biri for 0,33... 10 mm²
for auxiliary contacts-
mechanical data
width × height × depth of the enclosure240 × 125 × 125 mm
installation width × mounting height240 mm × 225 mm
top50 mm
bottom50 mm
left0 mm
right0 mm
fastening methodSnaps onto DIN rail EN 60715 35x15
DIN-rail mountingVar
S7 rail mountingYok
wall mountingYok
housing can be lined upVar
net weight3,2 kg
accessories
electrical accessoriesBuffer module, signaling module
additional information
other informationSpecifications rated input voltage ve ambient temperature +25 °C (unless otherwise specified)
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing76,5 kg
global warming potential [CO2 eq] / during operation2684,2 kg
global warming potential [CO2 eq] / after end of life0,64 kg
global warming potential [CO2 eq] / total2762,3 kg