product brand nameSITOP
product designationPower supply SITOP smart
type of current supply12 V/10 A
input
type of the power supply network1-phase AC
phase number1
voltage curve at inputAC
supply voltage at ACAutomatic range selection
supply voltage120 V/230 V
input voltage 1 at AC85... 132 V
input voltage 2 at AC170... 264 V
at 50 Hz230 V
at 60 Hz120 V
line frequency50/60 Hz
line frequency47... 63 Hz
wide range inputYok
overvoltage overload capability2,3 × Vin rated, 1,3 ms
buffering time for rated value of the output current in the event of power failure minimum20 ms
operating condition of the mains bufferingVin = 93/187 V
at rated input voltage 120 V2,42 A
at rated input voltage 230 V1,03 A
current limitation of inrush current at 25 °C maximum60 A
fuse protection typeT 6,3 A/250 V (not accessible)
fuse protection type in the feederRecommended miniature circuit breaker: 6 A/10 A characteristic C
output
voltage curve at outputControlled, isolated DC voltage
product function output voltage controlledVar
product function output voltage stabilizedVar
output voltage at DC rated value12 V
at output 1 at DC rated value12 V
at output 1 at DC12 V
output voltage adjustableVar; via potentiometer
adjustable output voltage11,5... 15,5 V
relative overall tolerance of the voltage3 %
on slow fluctuation of input voltage0,1 %
on slow fluctuation of ohm loading1 %
maximum150 mV
typical20 mV
maximum240 mV
typical100 mV
display version for normal operationGreen LED for 12 V OK
type of signal at outputRelay contact (NO contact, rating 60 V DC/ 0,3 A) for 12 V OK
behavior of the output voltage when switching onOvershoot of Vout < 3 %
response delay maximum0,3 s
typical10 ms
rated value10 A
rated range0... 10 A; +55... +60 °C: Derating 5%/K
supplied active power typical168 W
on short-circuiting during the start-up typical40 A
at short-circuit during operation typical40 A
on short-circuiting during the start-up800 ms
at short-circuit during operation800 ms
bridging of equipmentYok
number of parallel-switched equipment resources for increasing the power0
efficiency
efficiency in percent87 %
at rated output voltage for rated value of the output current typical24 W
closed-loop control
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical5 %
load step 10 to 90% typical1 ms
load step 90 to 10% typical1 ms
protection and monitoring
design of the overvoltage protection< 20 V
property of the output short-circuit proofVar
design of short-circuit protectionConstant current characteristic
response value current limitation10... 12 A
typical12 A
safety
galvanic isolation between input and outputVar
galvanic isolationOutput voltage: SELV, ES1 (IEC 62368-1), DVC As (IEC 61204-7)
operating resource protection classClass I
maximum3,5 mA
typical0,8 mA
protection class IPIP20
EMC
for emitted interferenceEN 55022 Class B
for mains harmonics limitationEN 61000-3-2
for interference immunityEN 61000-6-2
standards, specifications, approvals
CE markingVar
UL onayıYok
EAC approvalVar
NEC Class 2Yok
CB-certificateYok
standards, specifications, approvals hazardous environments
IECExYok
ATEXYok
ULhazloc approvalYok
FM registrationYok
standards, specifications, approvals marine classification
shipbuilding approvalVar
American Bureau of Shipping Europe Ltd. (ABS)Yok
French marine classification society (BV)Yok
Det Norske Veritas (DNV)Var
Lloyds Register of Shipping (LRS)Yok
ambient conditions
during operation-10... +60 °C; with natural convection
during transport-40... +85 °C
during storage-40... +85 °C
environmental category according to IEC 60721Climate class 3K3, 5... 95% no condensation
connection method
type of electrical connectionscrew terminal
at inputL, N, PE: 1 screw terminal her biri for 0,5... 2,5 mm² single-core/finely stranded
at output+, -: 2 screw terminals her biri for 0,5... 2,5 mm²
for auxiliary contactsAlarm signals: 2 screw terminals for 0,5... 2,5 mm²
for signaling contact3 screw terminals for 0,5... 2,5 mm²
mechanical data
width × height × depth of the enclosure70 × 125 × 120 mm
installation width × mounting height70 mm × 225 mm
fastening methodSnaps onto DIN rail EN 60715 35x7.5/15
DIN-rail mountingVar
S7 rail mountingYok
wall mountingYok
housing can be lined upVar
net weight0,7 kg
additional information
other informationSpecifications rated input voltage ve ambient temperature +25 °C (unless otherwise specified)