product brand nameSIMATIC
product designation4DI (LC) submodule
design of the productStandard
product type designationET 200SP
Product Function
ramp-up (soft starting)Yok
soft stoppingYok
Soft TorqueYok
Safe Torque Off (STO) via F-DIVar
Safe Torque Off (STO) via PROFIsafeYok
current limitationYok
creep speed in both directions of rotationYok
pump stopYok
min/max pointerVar
trace functionYok
stationary state detectionYok
switching of capacitive loadsVar
Smart StartVar
torque controlYok
reversing brakesYok
detection of direction of rotationVar
General technical data
on-site operationVar
for power supply reverse polarity protectionVar
for sensor supply short-circuit protectionVar
with 24 V sensor supply short-circuit protectionVar
diagnostics function short-circuit detectionVar
display version for diagnostic function: Status display transmission channel channel status LEDVar
noteGreen LED
shock resistance6 g / 11 ms (3 Schocks), 9 g / 6 ms (1000 Schocks)
vibration resistancef = 5... 8,5 Hz, dmax = 3,5 mm; 8,5... 26,9 Hz, amax = 10 m/s²/ f = 26,9... 60,1 Hz, dmax = 0,35 mm / f = 60,1... 500 Hz, amax = 50 m/s² / 10 cycles
Substance Prohibitance (day/month/year)10/01/2024
SVHC substance nameLead CAS-Yok. 7439-92-1
Net Weight0,05 kg
Short-circuit protection
product function short circuit protectionVar
Protective and monitoring functions
product function active power monitoringVar
Safety related data
product function suitable for safety functionVar
safety-related switching onYok
safety-related switching OFFVar
safe stateLoad circuit open
test wear-related service life necessaryYok
diagnostics test interval by internal test function maximum24 h
stop category according to IEC 60204-10
B10d value2.500.000
average diagnostic coverage level (DCavg)99 %
IEC 62061
Safety Integrity Level (SIL) according to IEC 62061SIL 3
PFHD with high demand rate according to IEC 620614E-9 1/h
ISO 13849
performance level (PL) according to ISO 13849-1PL e
category according to ISO 13849-14
IEC 61508
Safety Integrity Level (SIL) according to IEC 61508SIL 3
systematic capability according to IEC 61508SC 3
PFHD with high demand rate according to IEC 615084E-9 1/h
PFDavg with low demand rate according to IEC 615080,0002
Safe failure fraction (SFF)99 %
hardware fault tolerance according to IEC 615081
T1 value of service life according to IEC 6150820 a
Electrical Safety
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe
touch protection rear side according to IEC 60529finger-safe
ATEX
Safety Integrity Level (SIL) according to IEC 61508 relating to ATEXSIL 1
PFHD with high demand rate according to IEC 61508 relating to ATEX2E-6 1/h
PFDavg with low demand rate according to IEC 61508 relating to ATEX0,0003
hardware fault tolerance according to IEC 61508 relating to ATEX0
T1 value for proof test interval or service life according to IEC 61508 relating to ATEX3 a
MTTFd relating to ATEX46 a
ATEXVar
IECExVar
Inputs/ Outputs
digital inputs parameterizableVar
digital outputs parameterizableYok
at the standard inputs at rated input voltage parameterizable input delay timeYok
for signal <0> to <1> at rated input voltage6... 10 ms
for signal <1> to <0> at rated input voltage6... 10 ms
number of digital inputs4
digital input version type 1 acc. to IEC 61131Var
operating voltage as input voltage minimum permissible0 V
operating voltage as input voltage maximum permissible30 V
value range of the input voltage at digital input for signal <0> detection-30... +5 V
value range of the input voltage at digital input for signal <1> detection+15... +30 V
input voltage at digital input at DC rated value24 V
input current at digital input for signal <1> typical9 mA
output voltage19,4... 28,8 V
type of output voltage for sensor supplyDC
output voltage for sensor supply minimum19,2 V
output current for sensor supply maximum0,1 A
output current for sensor supply at 60 °C maximum0,1 A
wire length of sensor maximum30 m
Installation/ mounting/ dimensions
mounting positiondikey, yatay
fastening methodcan be plugged onto e-starters
height54,5 mm
width30 mm
depth42,3 mm
Ambient conditions
installation altitude at height above sea level maximum4.000 m
during operation-25... +40 °C
during storage-40... +70 °C
during transport-40... +70 °C
relative humidity during operation10... 95 %
air pressure according to SN 31205900... 1.060 hPa
Communication/ Protocol
protocol is supported PROFIsafe protocolYok
Connections/ Terminals
type of electrical connection for auxiliary and control circuitspring-loaded terminals (push-in)
type of connecting terminalpush-in terminal
solid or stranded0,2... 1,5 mm²
finely stranded with core end processing0,25... 1,5 mm²
finely stranded without core end processing0,2... 1,5 mm²
AWG number as coded connectable conductor cross section for auxiliary contacts24... 16
shape of the screwdriver tipSlot
size of the screwdriver tipStandard screwdriver 0,6 mm x 3,5 mm