Genel bilgiler
Ürün tipi tanımıCM 1x CAN ST
FW update possibleVar
based on6ES7137-6EA00-0BA0
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC00
Product function
I&M dataVar; I&M0 to I&M3
Module swapping during operation (hot swapping)Var
Isochronous modeYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Current consumption, typ.20 mA
Akım tüketimi, maks.25 mA
Güç kaybı
Güç kaybı, tipik0,5 W
Address space per module
Address space per module, max.256 bayt
1. Arayüz
Arayüz tipiCAN according to CiA 303-1
İzoleliVar; 500 V AC veya 707 V DC
Arayüz tipleri
Port sayısı1
Design of the connectionPush-in terminal
CAN
CAN operating modesCAN Standard CAN 2.0A/B; CANopen Manager / Slave acc. to CiA
Specification acc. to CiACiA 301 & CiA 302
Transmission rate, min.10 kbit/s
İletim hızı, maks.1.000 kbit/s
max. number of devices60
Number of SDOs in parallel16; Parallel
Number of PDOs128; Send / receive
Servisler
— Node/life-guardingVar
— HeartbeatVar
— SYNCVar
Interrupts/diagnostics/status information
AlarmsVar
Diagnostics functionVar
Tanılama gösterge LED’i
RUN LEDVar
ERROR LED’iVar
MAINT LED’iYok
Monitoring of the supply voltage (PWR-LED)Var; green PWR LED
Potential separation
between backplane bus and interfaceVar
Isolation
Isolation tested with707 V DC (type test)
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]25,2 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]6,15 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]19,4 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.289 kg
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) veya configured slots to the left ve right of the module
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.50 °C; = Tmax
ceiling installation, min.-40 °C; = Tmin
ceiling installation, max.50 °C; = Tmax
floor installation, min.-40 °C; = Tmin
floor installation, max.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold, fungal ve dry rot spores (excluding fauna)
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Var; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Decentralized operation
to SIMATIC S7-300Yok
to SIMATIC S7-400Yok
to SIMATIC S7-1200Var
to SIMATIC S7-1500Var
Ölçüler
Genişlik15 mm
Yükseklik73 mm
Derinlik58 mm
Ağırlık
Ağırlık, yaklaşık32 g