Genel bilgiler
Ürün tipi tanımıAI 4xI 2-wire HART
FW update possibleVar
based on6ES7134-6TD00-0CA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC03
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Measuring range scalableYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYok
MSIYok
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNYok
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Akım tüketimi, maks.25 mA; without sensor supply
24 V enkoder beslemesi
24 VVar
Short-circuit protectionVar
Output current, max.20 mA; maks. 50 mA per channel for a duration < 10 s
Güç kaybı
Güç kaybı, tipik0,65 W; without sensor supply
Address space per module
Address space per module, max.8 bayt; + 1 bayt for QI information
Address space per module with HART, max.28 bayt; + 1 bayt for QI information
Donanım yapılandırması
Automatic encodingVar
Mechanical coding elementVar
Type of mechanical coding elementType A
Analog girişler
Analog giriş sayısı4; Differential inputs
For current measurement4
permissible input current for current input (destruction limit), max.50 mA
Input ranges (rated values), currents
0 … 20 mAYok
-20 mA to +20 mAYok
4 mA to 20 mAVar; 15 bit + sign
— Input resistance (4 mA to 20 mA)280 Ω; + yaklaşık 0,35 V diode forward voltage
Kablo uzunluğu
Ekranlı, maks.800 m
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Entegrasyon süresi, parametrelenebilirVar; channel by channel
Interference voltage suppression for interference frequency f1 in Hz10 / 50 / 60 Hz
Smoothing of measured values
Number of smoothing levels4; Yok; 4/8/16 times
ParameterizableVar
Connection of signal encoders
for voltage measurementYok
for current measurement as 2-wire transducerVar
Errors/accuracies
Linearity error (relative to input range), (+/-)0,01 %
Temperature error (relative to input range), (+/-)0,005 %/K
Crosstalk between the inputs, min.60 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,05 %
Operational error limit in overall temperature range
Current, relative to input range, (+/-)1 %
Basic error limit (operational limit at 25 °C)
Current, relative to input range, (+/-)0,3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionVar
Alarms
Diagnostic alarmVar
Limit value alarmVar
Diagnoses
Monitoring the supply voltageVar
Wire breakVar; channel by channel
short-circuitVar; Channel-by-channel, short-circuit of the encoder supply to ground veya of an input to the encoder supply
Group errorVar
Overflow/UnderflowVar; channel by channel
Tanılama gösterge LED’i
Monitoring of the supply voltage (PWR-LED)Var; green PWR LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; green/red DIAG LED
Potential separation channels
Kanallar arasıYok
between the channels and backplane busVar
between the channels and the power supply of the electronicsYok
Isolation
Isolation tested with707 V DC (type test)
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C
Yatay montaj, maks.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) veya configured slots to the left ve right of the module
Dikey montaj, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -30 °C
Dikey montaj, maks.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Var; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik15 mm
Yükseklik73 mm
Derinlik58 mm
Ağırlık
Ağırlık, yaklaşık31 g