Genel bilgiler
Ürün tipi tanımıAI 2xSG 4-/6-wire HS
FW update possibleVar
based on7MH4134-6LB00-0DA0
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC00
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeVar
Measuring range scalableVar
Scalable measured valuesYok
Adjustment of measuring rangeVar; ±0,5... 320 mV/V
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingVar; 2 channels per module
MSIYok
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNYok
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Akım tüketimi (nominal değer)70 mA
Encoder supply
Output voltage (DC)4,85 V
Short-circuit protectionVar
Çıkış akımı
Rated value60 mA; Per channel
Power
Power consumption from the backplane bus65 mW
Güç kaybı
Güç kaybı, tipik1,5 W
Address space per module
Address space per module, max.32 bayt
Inputs32 bayt
Outputs8 bayt
Donanım yapılandırması
Automatic encodingVar
Mechanical coding elementVar
Type of mechanical coding elementType A
Analog girişler
Analog giriş sayısı2; Differential inputs
Cycle time (all channels), min.100 µs
Analog input with oversamplingVar
Values per cycle, max.14
Resolution, min.100 µs
Giriş aralıkları
Strain gauges (full bridges)Var
Kablo uzunluğu
Ekranlı, maks.500 m
Analog value generation for the inputs
Measurement principleSigma Delta
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.28 bit; 16 bits with oversampling
Entegrasyon süresi, parametrelenebilirVar
Interference voltage suppression for interference frequency f1 in Hz60 / 50 Hz / no
Dönüşüm süresi (kanal başına)100 µs
Smoothing of measured values
IIR low-pass filter frequency0,01... 600 Hz
IIR low-pass filter ordinal number1... 4
Notch filter frequency0,1... 1.000 Hz
Notch filter quality5,00... 250,00
Average value filter0,1... 655,3 ms
Connection of signal encoders
For strain gauges (full bridges) with 4-conductor connectionVar
For strain gauges (full bridges) with 6-conductor connectionVar
Resistance of full bridge, min.80 Ω
Resistance of full bridge, max.5.000 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0,025 %
Temperature error (relative to input range), (+/-)0,0005 %/°C; Strain gauge full bridge, 6-conductor connection
Temperature coefficient, zero point≤ ±0,25 μV/K
Temperature coefficient, span, 4-wire connection (in relation to end value)≤ ±5 ppm/K
Temperature coefficient, span, 6-wire connection (in relation to end value)≤ ±10 ppm/K
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,05 %; See manual for details
Isochronous mode
Filtering and processing time (TCI), min.87 µs
Bus cycle time (TDP), min.125 µs
Interrupts/diagnostics/status information
Diagnostics functionVar; Diagnostic alarm
Alarms
Diagnostic alarmVar; Parameterizable
Limit value alarmVar; two upper ve two lower limit values in her biri case
Diagnoses
Monitoring the supply voltageVar
Wire breakVar
Short-circuitVar
Group errorVar
Overflow/UnderflowVar
Tanılama gösterge LED’i
Monitoring of the supply voltage (PWR-LED)Var; green PWR LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; green/red DIAG LED
Potential separation channels
Kanallar arasıYok
between the channels and backplane busVar
between the channels and the power supply of the electronicsVar
Isolation
Isolation tested with707 V DC (type test)
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) veya configured slots to the left ve right of the module
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity degree 3)
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0//6AG1193-6AB00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold, fungal ve dry rot spores (excluding fauna)
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75%) incl. salt spray acc. to EN 60068-2-52 (severity degree 3).
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust
— Against mechanical environmental conditions acc. to EN 60721-3-6Var; class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0/6AG1193-6AB00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik15 mm
Yükseklik73 mm
Derinlik58 mm
Ağırlık
Ağırlık, yaklaşık30 g