Genel bilgiler
Ürün tipi tanımıAI 4xTC HS
FW update possibleVar
based on6ES7134-6JD00-0DA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Measuring range scalableVar
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYok
MSIVar
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNVar
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Akım tüketimi (nominal değer)37 mA
Akım tüketimi, maks.50 mA
Güç kaybı
Güç kaybı, tipik0,9 W
Address space per module
Address space per module, max.16 bayt; + 1 bayt for QI information
Donanım yapılandırması
Automatic encodingVar
Mechanical coding elementVar
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
Analog girişler
Analog giriş sayısı4
permissible input voltage for voltage input (destruction limit), max.30 V
Cycle time (all channels), min.5 ms; Sum of the basic conversion times ve additional processing times (depending on the parameterization of the active channels)
Technical unit for temperature measurement adjustableVar; °C/°F/K
Giriş aralıkları (nominal değerler), gerilim
-1 V to +1 VVar; 16 bit incl. sign
— Input resistance (-1 V to +1 V)1 MΩ
-250 mV to +250 mVVar; 16 bit incl. sign
— Input resistance (-250 mV to +250 mV)1 MΩ
-50 mV to +50 mVVar; 16 bit incl. sign
— Input resistance (-50 mV to +50 mV)1 MΩ
-80 mV to +80 mVVar; 16 bit incl. sign
— Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermocouples
Type BVar; 16 bit incl. sign
— Input resistance (Type B)1 MΩ
Type CVar; 16 bit incl. sign
— Input resistance (Type C)1 MΩ
Type EVar; 16 bit incl. sign
— Input resistance (Type E)1 MΩ
Type JVar; 16 bit incl. sign
— Input resistance (type J)1 MΩ
Type KVar; 16 bit incl. sign
— Input resistance (Type K)1 MΩ
Type LVar; 16 bit incl. sign
— Input resistance (Type L)1 MΩ
Type NVar; 16 bit incl. sign
— Input resistance (Type N)1 MΩ
Type RVar; 16 bit incl. sign
— Input resistance (Type R)1 MΩ
Type SVar; 16 bit incl. sign
— Input resistance (Type S)1 MΩ
Type TVar; 16 bit incl. sign
— Input resistance (Type T)1 MΩ
Type UVar; 16 bit incl. sign
— Input resistance (Type U)1 MΩ
Type TXK/TXK(L) to GOSTVar; 16 bit incl. sign
— Input resistance (Type TXK/TXK(L) to GOST)1 MΩ
Temperature compensation
— ParametrelenebilirVar
— Reference channel of the moduleYok
— internal comparison pointVar; with BaseUnit type A1
— Reference channel of the groupVar
— Number of reference channel groups4; Group 0 to 3
— fixed reference temperatureVar
Kablo uzunluğu
Ekranlı, maks.200 m; 100 m for thermocouples
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Entegrasyon süresi, parametrelenebilirVar
— additional processing time for wire-break check1 ms
Interference voltage suppression for interference frequency f1 in Hz16,6 / 50 / 60 Hz / off
Dönüşüm süresi (kanal başına)180/60/50/1,25 ms
Smoothing of measured values
Number of smoothing levels4; Yok; 4/8/16 times
parameterizableVar
Step: NoneVar
Step: lowVar
Step: MediumVar
Step: HighVar
Connection of signal encoders
for voltage measurementVar
Errors/accuracies
Linearity error (relative to input range), (+/-)0,01 %
Temperature error (relative to input range), (+/-)0,005 %/K
Crosstalk between the inputs, min.-70 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,03 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0,2 %; 0,5 % when voltage frequency converter OFF
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,05 %; 0,2 % when SFU OFF
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.60 V; DC
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Diagnostics functionVar
Alarms
Diagnostic alarmVar
Limit value alarmVar; two upper ve two lower limit values in her biri case
Diagnoses
Monitoring the supply voltageVar
Wire breakVar; channel by channel
Group errorVar
Overflow/UnderflowVar; channel by channel
Tanılama gösterge LED’i
Monitoring of the supply voltage (PWR-LED)Var; green PWR LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; green/red LED
Potential separation channels
Kanallar arasıYok
between the channels and backplane busVar
between the channels and the power supply of the electronicsVar
Permissible potential difference
between the inputs (UCM)60 V DC
Isolation
Isolation tested with707 V DC (type test)
Standartlar, onaylar, sertifikalar
Suitable for applications according to AMS 2750Var; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9Var; Based on AMS 2750 E
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.60 °C; = Tmax; +70 °C with configured empty slots to the left ve right of the module
Dikey montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Dikey montaj, maks.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.080 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax - 20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Var; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik15 mm
Yükseklik73 mm
Derinlik58 mm
Ağırlık
Ağırlık, yaklaşık33 g