Genel bilgiler
Ürün tipi tanımıAI 2xU/I 2-/4-wire HS
FW update possibleVar
based on6ES7134-6HB00-0DA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeVar; 125 µs
Measuring range scalableYok
Scalable measured valuesYok
Adjustment of measuring rangeYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingVar; 2 channels per module
MSIYok
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNYok
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Akım tüketimi (nominal değer)39 mA; without sensor supply
24 V enkoder beslemesi
24 VVar; For current measurement
Short-circuit protectionVar
Output current, max.20 mA; maks. 50 mA per channel for a duration < 10 s
Güç kaybı
Güç kaybı, tipik0,95 W; without sensor supply
Address space per module
Address space per module, max.4 bayt; + 1 bayt for QI information (32 bytes in the oversampling operating mode)
Donanım yapılandırması
Automatic encodingVar
Mechanical coding elementVar
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
4-wire connectionBU type A0, A1
Analog girişler
Analog giriş sayısı2; Differential inputs
For current measurement2
For voltage measurement2
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels), min.125 µs
Analog input with oversamplingVar
Values per cycle, max.16
Resolution, min.50 µs
Giriş aralıkları (nominal değerler), gerilim
0 … +10 VVar; 15 bit
— Giriş direnci (0 … 10 V)75 kΩ
1 V to 5 VVar; 13 bit
— Input resistance (1 V to 5 V)75 kΩ
-10 V to +10 VVar; 16 bit incl. sign
— Input resistance (-10 V to +10 V)75 kΩ
-5 V to +5 VVar; 15 bit incl. sign
— Input resistance (-5 V to +5 V)75 kΩ
Input ranges (rated values), currents
0 … 20 mAVar; 15 bit
— Input resistance (0 to 20 mA)130 Ω
-20 mA to +20 mAVar; 16 bit incl. sign
— Input resistance (-20 mA to +20 mA)130 Ω
4 mA to 20 mAVar; 14 bit
— Input resistance (4 mA to 20 mA)130 Ω
Kablo uzunluğu
Ekranlı, maks.1.000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principleActual value encryption (successive approximation)
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Interference voltage suppression for interference frequency f1 in HzYok
Dönüşüm süresi (kanal başına)10 µs
Smoothing of measured values
Number of smoothing levels7; yok; 2-/4-/8-/16-/32-/64-fold
parameterizableVar
Connection of signal encoders
for voltage measurementVar
for current measurement as 2-wire transducerVar
— Burden of 2-wire transmitter, max.650 Ω
for current measurement as 4-wire transducerVar
Errors/accuracies
Linearity error (relative to input range), (+/-)0,03 %
Temperature error (relative to input range), (+/-)0,01 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,1 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0,5 %
Current, relative to input range, (+/-)0,5 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,2 %
Current, relative to input range, (+/-)0,2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode voltage, max.35 V
Common mode interference, min.90 dB
Isochronous mode
Filtering and processing time (TCI), min.80 µs
Bus cycle time (TDP), min.125 µs; Starting from firmware Version V2.0.1
Alarms
Diagnostic alarmVar
Limit value alarmVar; two upper ve two lower limit values in her biri case
Diagnoses
Wire breakVar; channel-by-channel, 4 to 20 mA only
Short-circuitVar; channel-by-channel, 1 to 5 V veya for current measuring ranges short-circuit in encoder supply
Group errorVar
Overflow/UnderflowVar; channel by channel
Tanılama gösterge LED’i
Monitoring of the supply voltage (PWR-LED)Var; green PWR LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; green/red DIAG LED
Potential separation channels
Kanallar arasıVar
between the channels and backplane busVar
between the channels and the power supply of the electronicsVar
Isolation
Isolation tested with707 V DC (type test)
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) veya configured slots to the left ve right of the module
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Var; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik15 mm
Yükseklik73 mm
Derinlik58 mm
Ağırlık
Ağırlık, yaklaşık32 g