General information
Product type designationAI 4xTC HS
HW functional statusFS22 or higher
Firmware versionV2.0.0
FW update possibleYes
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Measuring range scalableYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV21.1 or higher
STEP 7 configurable/integrated from versionconfigurable as of V5.7.3.3 with HSP0348 V3.0 / integrated as of V5.7.5.0
PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
PROFINET from GSD version/GSD revisionGSDML V2.50
Operating mode
OversamplingNo
MSIYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)37 mA
Current consumption, max.50 mA
Power loss
Power loss, typ.0.9 W
Address space per module
Address space per module, max.16 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
Analog inputs
Number of analog inputs4
For voltage measurement4
For thermocouple measurement4
permissible input voltage for voltage input (destruction limit), max.30 V
Cycle time (all channels), min.5 ms; Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input ranges (rated values), voltages
-1 V to +1 VYes; 16 bit incl. sign
— Input resistance (-1 V to +1 V)1 MΩ
-250 mV to +250 mVYes; 16 bit incl. sign
— Input resistance (-250 mV to +250 mV)1 MΩ
-50 mV to +50 mVYes; 16 bit incl. sign
— Input resistance (-50 mV to +50 mV)1 MΩ
-80 mV to +80 mVYes; 16 bit incl. sign
— Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermocouples
Type BYes; 16 bit incl. sign
— Input resistance (Type B)1 MΩ
Type CYes; 16 bit incl. sign
— Input resistance (Type C)1 MΩ
Type EYes; 16 bit incl. sign
— Input resistance (Type E)1 MΩ
Type JYes; 16 bit incl. sign
— Input resistance (type J)1 MΩ
Type KYes; 16 bit incl. sign
— Input resistance (Type K)1 MΩ
Type LYes; 16 bit incl. sign
— Input resistance (Type L)1 MΩ
Type NYes; 16 bit incl. sign
— Input resistance (Type N)1 MΩ
Type RYes; 16 bit incl. sign
— Input resistance (Type R)1 MΩ
Type SYes; 16 bit incl. sign
— Input resistance (Type S)1 MΩ
Type TYes; 16 bit incl. sign
— Input resistance (Type T)1 MΩ
Type UYes; 16 bit incl. sign
— Input resistance (Type U)1 MΩ
Type TXK/TXK(L) to GOSTYes; 16 bit incl. sign
— Input resistance (Type TXK/TXK(L) to GOST)1 MΩ
Temperature compensation
— ParameterizableYes
— Reference channel of the moduleNo
— internal comparison pointYes; with BaseUnit type A1
— Reference channel of the groupYes
— Number of reference channel groups4; Group 0 to 3
— fixed reference temperatureYes
Cable length
shielded, max.200 m; 100 m for thermocouples
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
— additional processing time for wire-break check1 ms
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 Hz / off
Conversion time (per channel)180/60/50/1.25 ms
Smoothing of measured values
Number of smoothing levels4
parameterizableYes
Step: NoneYes; 1x conversion time
Step: lowYes; 4x conversion time
Step: MediumYes; 8x conversion time
Step: HighYes; 16x conversion time
Connection of signal encoders
for voltage measurementYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-70 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.03 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.1 %; 0.3 % when SFU OFF
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %; 0.2 % when SFU OFF
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.60 V; DC
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; channel by channel
Overflow/UnderflowYes; channel by channel
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Permissible potential difference
between the inputs (UCM)60 Vpp
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for applications according to AMS 2750Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9Yes; Based on AMS 2750 E
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]9.32 kg
— global warming potential, (during production) [CO2 eq]4.97 kg
— global warming potential, (during operation) [CO2 eq]4.79 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.449 kg
Security
signed firmware updateYes; firmware V2.0.0 or higher
Ambient temperature during operation
horizontal installation, min.-30 °C; < 0 °C as of FS02
horizontal installation, max.60 °C
vertical installation, min.-30 °C; < 0 °C as of FS02
vertical installation, max.50 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.33 g