General information
Product type designationAI 4x U/I 2-wire ST
HW functional statusFS22 or higher
Firmware versionV3.0.0
FW update possibleYes
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC03
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Measuring range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV21.1 or higher
STEP 7 configurable/integrated from versionconfigurable as of V5.7.3.3 with HSP0348 V3.0 / integrated as of V5.7.5.0
PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
PROFINET from GSD version/GSD revisionGSDML V2.50
Operating mode
OversamplingNo
MSINo
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)30 mA
Current consumption, max.117 mA
24 V encoder supply
24 VYes; For current measurement
Short-circuit protectionYes
Output current, max.20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ.0.85 W
Address space per module
Address space per module, max.8 byte; + 1 byte for QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Selection of BaseUnit for connection variants
2-wire connectionBU type A0, A1
Analog inputs
Number of analog inputs4; Differential inputs
For current measurement4
For voltage measurement4
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels), min.Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Input ranges (rated values), voltages
0 to +10 VYes; 15 bit
— Input resistance (0 to 10 V)120 kΩ
1 V to 5 VYes; 15 bit
— Input resistance (1 V to 5 V)120 kΩ
-10 V to +10 VYes; 16 bit incl. sign
— Input resistance (-10 V to +10 V)120 kΩ
-5 V to +5 VYes; 16 bit incl. sign
— Input resistance (-5 V to +5 V)120 kΩ
Input ranges (rated values), currents
0 to 20 mAYes; 15 bit
— Input resistance (0 to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
4 mA to 20 mAYes; 15 bit
— Input resistance (4 mA to 20 mA)100 Ω; + approx. 0.7 V diode forward voltage
Cable length
shielded, max.1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principleSigma Delta
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 Hz
Conversion time (per channel)180 / 60 / 50 ms
Smoothing of measured values
Number of smoothing levels4
parameterizableYes
Step: NoneYes; 1x conversion time
Step: lowYes; 4x conversion time
Step: MediumYes; 8x conversion time
Step: HighYes; 16x conversion time
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes
— Burden of 2-wire transmitter, max.650 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.5 %
Current, relative to input range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.3 %
Current, relative to input range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.10 V
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmNo
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; at 4 to 20 mA
Short-circuitYes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply
Overflow/UnderflowYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red LED
Potential separation channels
between the channelsYes; channel group-specific between 2-wire current input group and voltage input group
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes; only for voltage inputs
Permissible potential difference
between the inputs (UCM)10 Vpp
Isolation
Isolation tested with707 V DC (type test)
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]9.32 kg
— global warming potential, (during production) [CO2 eq]4.97 kg
— global warming potential, (during operation) [CO2 eq]4.79 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.449 kg
Security
signed firmware updateYes; firmware V3.0.0 or higher
Ambient temperature during operation
horizontal installation, min.-30 °C; < 0 °C as of FS02
horizontal installation, max.60 °C
vertical installation, min.-30 °C; < 0 °C as of FS02
vertical installation, max.50 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.31 g