General information
Product type designationDQ 4x24 ... 230 V AC/2 A HF
FW update possibleYes
based on6ES7132-6FD00-0CU0
usable BaseUnitsBU type U0
Color code for module-specific color-coded labelCC20
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQYes
DQ with energy-saving functionYes
PWMNo
OversamplingNo
MSONo
Phase controlYes; Control area: 8.5 ... 100% of the phase angle
Trailing-edge phaseNo
Half-waveYes
Full-waveYes
Supply voltage
Rated value (AC)230 V; 47 ... 63 Hz, max. rate of change of frequency 1 mHz/s
permissible range, lower limit (AC)20.4 V
permissible range, upper limit (AC)264 V
Input current
Current consumption (rated value)8 mA; without load
Output voltage
Rated value (AC)230 V; 24V AC to 230V AC
Power loss
Power loss, typ.9 W; Active power, load voltage 230 V, all outputs loaded with 2 A, 50 Hz
Address space per module
Inputs+ 1 byte for QI information
Outputs8 byte
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Selection of BaseUnit for connection variants
1-wire connectionBU type U0
2-wire connectionBU type U0
3-wire connectionBU type U0 + Potential distributor module
Digital outputs
Type of digital outputTriac
Number of digital outputs4
Current-sinkingNo
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionNo; external fusing necessary
Open-circuit detectionYes; channel by channel
Response threshold, typ.1 mA; 40 V AC or more
Overload protectionNo; A miniature fuse with 10 tripping current and tripping characteristic "quick response" must be provided in the module supply
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.2 A; Max. 4 A, see additional description in manual
with inductive load, max.2 A
on lamp load, max.100 W; Tungsten rating in accordance with UL; for thermistors with higher power ratings, see the notes in the manual
Output voltage
for signal "1", min.20.4 V
Output current
for signal "1" rated value2 A
for signal "1" permissible range, min.10 mA
for signal "1" permissible range, max.4 A; note derating data in the manual
for signal "0" residual current, max.3 mA
Output delay with resistive load
"0" to "1", max.40 ms; 2 AC cycles
"1" to "0", max.20 ms; 1 AC cycle
Parallel switching of two outputs
for logic linksNo
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.10 Hz; Applies to DQ mode; limited by line frequency in PC mode
with inductive load (acc. to IEC 60947-5-1, AC15), max.10 Hz; Applies to DQ mode; limited by line frequency in PC mode
on lamp load, max.1 Hz; Applies to DQ mode; limited by line frequency in PC mode
Total current of the outputs
Current per channel, max.2 A; Max. 4 A, see additional description in manual
Current per module, max.8 A
horizontal installation
— up to 40 °C, max.8 A; Applicable for current channels up to 2 A. For current channels between 2 A and 4 A, note derating data in the manual
— up to 50 °C, max.6 A; Applicable for current channels up to 2 A. For current channels between 2 A and 4 A, note derating data in the manual
— up to 60 °C, max.4 A; Applicable for current channels up to 2 A. For current channels between 2 A and 4 A, note derating data in the manual
— up to 70 °C, max.2 A; Applicable for current channels up to 2 A
vertical installation
— up to 30 °C, max.8 A
— up to 40 °C, max.6 A
— up to 50 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Diagnostic information readableYes
Monitoring the supply voltageYes
Wire breakYes; channel by channel
Short-circuitNo
Group errorYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red Fn LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with2 545 V DC (type test) and according to EN 50155 (routine test)
Standards, approvals, certificates
Suitable for safety functionsNo
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50121-5Yes; EMC for fixed installations and railway power supply equipment (shielded cables required)
EN 50124-1Yes; Railway applications - overvoltage category OV3; pollution degree PD2; UNm = 230 V AC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
vertical installation, min.-40 °C; = Tmin
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Yes; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Yes; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width20 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.50 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776