General information
Product type designationAI 4xRTD/TC 2-/3-/4-wire HF
FW update possibleYes
based on6ES7134-6JD00-0CA1
usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingNo
MSINo
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Input current
Current consumption (rated value)30 mA
Current consumption, max.32 mA
Power loss
Power loss, typ.0.75 W
Address space per module
Address space per module, max.8 byte; + 1 byte for QI information
Hardware configuration
Mechanical coding elementYes
Type of mechanical coding elementType A
Analog inputs
Number of analog inputs4
permissible input voltage for voltage input (destruction limit), max.30 V
Constant measurement current for resistance-type transmitter, typ.2 mA
Cycle time (all channels), min.Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels); for line compensation in case of a three-wire connection, an additional cycle is necessary
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input ranges (rated values), voltages
-1 V to +1 VYes; 16 bit incl. sign
— Input resistance (-1 V to +1 V)1 MΩ
-250 mV to +250 mVYes; 16 bit incl. sign
— Input resistance (-250 mV to +250 mV)1 MΩ
-50 mV to +50 mVYes; 16 bit incl. sign
— Input resistance (-50 mV to +50 mV)1 MΩ
-80 mV to +80 mVYes; 16 bit incl. sign
— Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), thermocouples
Type BYes; 16 bit incl. sign
— Input resistance (Type B)1 MΩ
Type CYes; 16 bit incl. sign
— Input resistance (Type C)1 MΩ
Type EYes; 16 bit incl. sign
— Input resistance (Type E)1 MΩ
Type JYes; 16 bit incl. sign
— Input resistance (type J)1 MΩ
Type KYes; 16 bit incl. sign
— Input resistance (Type K)1 MΩ
Type LYes; 16 bit incl. sign
— Input resistance (Type L)1 MΩ
Type NYes; 16 bit incl. sign
— Input resistance (Type N)1 MΩ
Type RYes; 16 bit incl. sign
— Input resistance (Type R)1 MΩ
Type SYes; 16 bit incl. sign
— Input resistance (Type S)1 MΩ
Type TYes; 16 bit incl. sign
— Input resistance (Type T)1 MΩ
Type UYes; 16 bit incl. sign
— Input resistance (Type U)1 MΩ
Type TXK/TXK(L) to GOSTYes; 16 bit incl. sign
— Input resistance (Type TXK/TXK(L) to GOST)1 MΩ
Input ranges (rated values), resistance thermometer
Cu 10Yes; 16 bit incl. sign
— Input resistance (Cu 10)1 MΩ
Ni 100Yes; 16 bit incl. sign
— Input resistance (Ni 100)1 MΩ
Ni 1000Yes; 16 bit incl. sign
— Input resistance (Ni 1000)1 MΩ
LG-Ni 1000Yes; 16 bit incl. sign
— Input resistance (LG-Ni 1000)1 MΩ
Ni 120Yes; 16 bit incl. sign
— Input resistance (Ni 120)1 MΩ
Ni 200Yes; 16 bit incl. sign
— Input resistance (Ni 200)1 MΩ
Ni 500Yes; 16 bit incl. sign
— Input resistance (Ni 500)1 MΩ
Pt 100Yes; 16 bit incl. sign
— Input resistance (Pt 100)1 MΩ
Pt 1000Yes; 16 bit incl. sign
— Input resistance (Pt 1000)1 MΩ
Pt 200Yes; 16 bit incl. sign
— Input resistance (Pt 200)1 MΩ
Pt 500Yes; 16 bit incl. sign
— Input resistance (Pt 500)1 MΩ
Input ranges (rated values), resistors
0 to 150 ohmsYes; 15 bit
— Input resistance (0 to 150 ohms)1 MΩ
0 to 300 ohmsYes; 15 bit
— Input resistance (0 to 300 ohms)1 MΩ
0 to 600 ohmsYes; 15 bit
— Input resistance (0 to 600 ohms)1 MΩ
0 to 3000 ohmsYes; 15 bit
— Input resistance (0 to 3000 ohms)1 MΩ
0 to 6000 ohmsYes; 15 bit
— Input resistance (0 to 6000 ohms)1 MΩ
PTCYes; 15 bit
— Input resistance (PTC)1 MΩ
Temperature compensation
— ParameterizableYes
— Reference channel of the moduleYes
— internal comparison pointYes; with BaseUnit type A1
— Reference channel of the groupYes
— Number of reference channel groups4; Group 0 to 3
— fixed reference temperatureYes
Cable length
shielded, max.200 m; 50 m with thermocouples
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Integration time, parameterizableYes
— additional processing time for wire-break check2 ms; In the ranges resistance thermometers, resistors and thermocouples
— additional power line wire-break check2 ms; for 3/4 wire transducer (resistance thermometer and resistor)
Interference voltage suppression for interference frequency f1 in Hz16.6 / 50 / 60 Hz
Conversion time (per channel)180 / 60 / 50 / (67.5 / 22.5 / 18.75) ms
Smoothing of measured values
Number of smoothing levels4; None; 4/8/16 times
parameterizableYes
Connection of signal encoders
for voltage measurementYes
for resistance measurement with two-wire connectionYes
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.0009 %/K; ±0.005 % / K at thermocouple
Crosstalk between the inputs, min.50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.2 %
Resistance, relative to input range, (+/-)0.2 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.05 %
Resistance, relative to input range, (+/-)0.05 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode voltage, max.10 V
Common mode interference, min.90 dB
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Limit value alarmYes; two upper and two lower limit values in each case
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; channel by channel
Group errorYes
Overflow/UnderflowYes; channel by channel
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsYes
Permissible potential difference
between the inputs (UCM)10 V DC
Isolation
Isolation tested with707 V DC (type test)
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.60 °C; = Tmax; +70 °C with spacing modules (6AG1193-6BN00-7BA0) or configured slots to the left and right of the module
vertical installation, min.-40 °C; = Tmin (incl. condensation/frost)
vertical installation, max.50 °C; = Tmax
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights