Model
product brand nameSENTRON
product designationMolded-case circuit breaker
product designation / according to UL fileHFAS
design of the productSystem protection
design of the load switch / according to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type)Yes
design of the load switch / according to UL 489 / High-Intensity-Discharge circuit breaker (HID Type)No
design of the load switch / according to UL 489 / Switching Duty circuit breaker (SWD Type)No
design of the overcurrent releaseTM230
protection function of the overcurrent releaseLI
number of poles3
design of the auxiliary releaseundervoltage release (UVR)
design of the auxiliary switch1 auxiliary switch + 1 trip alarm switch HQ
General technical data
insulation voltage / rated value800 V
operating voltage / at DC / rated value750 V
operating voltage / at AC / rated value690 V
power loss [W] / maximum58 W
power loss [W] / for rated value of the current / at AC / in hot operating state / per pole19.33 W
mechanical service life (operating cycles) / typical20 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V8 000
electrical endurance (operating cycles) / at AC-1 / at 690 V4 000
electrical endurance (operating cycles) / at 480 V8 000
electrical endurance (operating cycles) / at 600 V4 000
product feature / for neutral conductors / upgradable/retrofittable / short-circuit and overload proofNo
communication functionNo
other measurement functionNo
Net Weight2.04 kg
Current
marking / according to UL 489 / 100%-rated breakerNo
at 40 °C250 A
at 45 °C244 A
at 50 °C239 A
at 55 °C233 A
at 60 °C227 A
at 65 °C222 A
at 70 °C216 A
Switching capacity according to IEC 60947
switching capacity class of the circuit breakerH
at 240 V100 kA
at 415 V70 kA
at 690 V10 kA
at 240 V100 kA
at 415 V70 kA
at 690 V10 kA
at 240 V220 kA
at 415 V154 kA
at 690 V17 kA
design of short-circuit protectionFor switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter
Switching capacity according to UL 489
at 240 V100 kA
at 480 V65 kA
at 600 V25 kA
Adjustable parameters
minimum250 A
maximum250 A
minimum1 s
maximum1 s
minimum1 250 A
maximum2 500 A
minimum0 A
maximum0 A
product function / grounding protectionNo
Mechanical Design
undervoltage releaseYes
voltage triggerNo
trip indicatorYes
height [in]7.28 in
height185 mm
width [in]4.13 in
width105 mm
depth [in]3.27 in
depth83 mm
Connections
arrangement of electrical connectors / for main current circuitWithout connection
type of electrical connection / for main current circuitWithout
Auxiliary circuit
number of CO contacts / for auxiliary contacts2
Accessories
product extension / optional / motor driveYes
of the supplied basic switch3VA52256EC310AA0
of the integrated auxiliary switch/alarm switch3VA9988-0AA12
of the integrated auxiliary switch/alarm switch3VA9988-0AB12
of the integrated auxiliary trip unit3VA9608-0BB11
Environmental conditions
protection class IP / on the frontIP40
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C
reference code / according to IEC 81346-2Q
Product information
EAN4042949324232
Life cycle statusActive
Commodity code85362090
Delivery and logistics
Country of originCzech Republic
Standard delivery time10 Day/Days
ReturnableYes
Net weight2.04 Kg
Packaging dimensions (L x W x H)245 x 150 x 160 MM
Standard package quantity1 Piece
Minimum order quantity1
Dangerous goodsNo
Export control regulationsECCN : EAR99 / AL : N
Environment and compliance
RoHS conformitySince: 22-11-16
WEEE category5
REACH information2-(2H-benzotriazol-2-yl)-4-(1,1,3,3-tetramethylbutyl)phenol (UV-329) CAS-No. 3147-75-9 > 0,1 % (w / w)
Siemens catalog
Product group5385
Catalog IDLV10.1
Group codeP360
Product classProducts that have been produced/purchased for specific orders, and which generally cannot
be reused in any form; a credit will not be issued when these products are returned. This product class includes, e.g. configurable versions