General technical data
equipment version according to IEC 60947-4-23
product functionDirect-on-line starter
on-site operationYes
intrinsic device protectionYes
remote firmware updateYes
for power supply reverse polarity protectionYes
at AC in hot operating state per pole1.5 W
insulation voltage rated value500 V
degree of pollution2
overvoltage categoryIII
surge voltage resistance rated value6 kV
between main and auxiliary circuit500 V
consumed current maximum180 mA
shock resistance6 g / 11 ms
vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
operating frequency maximum1 1/s
mechanical service life (operating cycles) of the main contacts typical30 000 000
type of coordination1
according to IEC 60947-4-2AC-53a: 9 A: (8-0,7: 70-32)
according to IEC 60947-4-3AC-51: 9 A: (1,2-10: 50-360); AC-55a: 4 A: (3-240: 40-6)
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)04/15/2016
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.412 kg
direct startYes
reverse startingNo
product component motor brake outputNo
product function short circuit protectionYes
design of short-circuit protectionfuse
at 400 V rated value55 kA
at 500 V rated value55 kA
at 500 V according to UL 60947 rated value100 kA
at 400 V rated value55 kA
at 500 V rated value55 kA
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1class A
EMC immunity according to IEC 60947-1Class A
due to burst according to IEC 61000-4-42 kV
due to conductor-earth surge according to IEC 61000-4-52 kV
due to conductor-conductor surge according to IEC 61000-4-51 kV
due to high-frequency radiation according to IEC 61000-4-6Class A
field-based interference according to IEC 61000-4-310 V/m
electrostatic discharge according to IEC 61000-4-28 kV air discharge
conducted HF interference emissions according to CISPR11Class A for industrial environment
field-bound HF interference emission according to CISPR11Class A for industrial environment
Safety related data
MTBF46 a
Electrical Safety
touch protection against electrical shockfinger-safe
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe
Main circuit
number of poles for main current circuit3
design of the switching contactHybrid
adjustable current response value current of the current-dependent overload release2.8 ... 9 A
minimum load [%]50 %; from smallest adjustable rated current
type of the motor protectionsolid-state
operating voltage rated value48 ... 500 V
relative symmetrical tolerance of the operating voltage10 %
operating frequency 1 rated value50 Hz
operating frequency 2 rated value60 Hz
relative symmetrical tolerance of the operating frequency5 %
relative positive tolerance of the operating frequency5 %
relative negative tolerance of the operating frequency5 %
operational current at AC at 400 V rated value9 A
ampacity when starting maximum90 A
operating power for 3-phase motors at 400 V at 50 Hz1.5 ... 4 kW
Inputs/ Outputs
number of digital inputs4
note4 via 3DI/LC module
of the inputs4 byte
of the outputs2 byte
Supply voltage
type of voltage of the supply voltageDC
minimum permissible20.4 V
maximum permissible28.8 V
supply voltage at DC rated value24 V
in standby mode of operation85 mA
during operation90 mA
at switching on of motor180 mA
in switching state OFF with bypass circuit2.2 W
in switching state ON with bypass circuit4.32 W
inrush current peak at 24 V25 A; Observe the manual for group configuration
duration of inrush current peak at 24 V0.14 ms
Response times
ON-delay time20 ms
OFF-delay time35 ... 50 ms
Power Electronics
at 40 °C rated value9 A
at 50 °C rated value9 A
at 55 °C rated value9 A
at 60 °C rated value9 A
Installation/ mounting/ dimensions
mounting positionVertical, horizontal (observe derating)
fastening methodpluggable in BaseUnit
height142 mm
width30 mm
depth150 mm
upwards50 mm
downwards50 mm
Ambient conditions
installation altitude at height above sea level maximum4 000 m
during operation-25 ... +60 °C; For derating see manual
during storage-40 ... +70 °C
during transport-40 ... +70 °C
environmental category during operation according to IEC 607213K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices)
relative humidity during operation10 ... 95 %
air pressure according to SN 31205900 ... 1 060 hPa
Communication/ Protocol
PROFIBUS DP protocolYes
PROFINET protocolYes
product function bus communicationYes
protocol is supported AS-Interface protocolNo
supports PROFIenergy measured valuesYes
supports PROFIenergy shutdownYes
type of electrical connection of the communication interfacePlug contact to Base Unit
Connections/ Terminals
1 for digital input signalsPluggable module - accessory
for main energy infeedPlug contact to Base Unit
for load-side outgoing feederPlug contact to Base Unit
for supply voltage line-sidePlug contact to Base Unit
wire length for motor unshielded maximum200 m
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor at 480 V rated value9 A
current with locked rotor (LRA) for 3-phase AC motor at 480 V rated value72 A
— at 110/120 V rated value0.33 hp
— at 230 V rated value1 hp
— at 200/208 V rated value2 hp
— at 220/230 V rated value2 hp
— at 460/480 V rated value5 hp
operating voltage at AC at 60 Hz according to CSA and UL rated value480 V