product brand nameSIMATIC
product designatione-Starter
design of the productreversing starter
product type designationET 200SP
of supplied fan unit3RD1000-1FS00-0BP0
of the optionally available fan unit3RD1000-1FD00-0BP0
of the optionally available basic 4DI (LC) submodule3RD1000-1MB00-0BP0
of the optionally available standard 4DI (LC) submodule3RD1000-1MS00-0BP0
General technical data
product function external resetYes
design of the overcurrent releaseETU
equipment version according to IEC 60947-4-22
on-site operationYes
intrinsic device protectionYes
adjustable current limitationYes
remote firmware updateYes
bus communicationYes
for power supply reverse polarity protectionYes
at AC in hot operating state8.1 W
at AC in hot operating state per pole2.7 W
without load current share typical5.5 W
type of calculation of power loss current-dependentquadratic
insulation voltage rated value500 V
degree of pollution3
overvoltage categoryIII
surge voltage resistance rated value6 kV
maximum permissible voltage for protective separation between main and auxiliary circuit500 V
degree of protection NEMA rating1
shock resistance6 g / 11 ms (3 Schocks), 9 g / 6 ms (1000 Schocks)
vibration resistancef = 5 ... 8.5 Hz, dmax = 3.5 mm; 8.5 ... 26.9 Hz, amax = 10 m/s²/ f = 26.9 ... 60.1 Hz, dmax = 0.35 mm / f = 60.1 ... 500 Hz, amax = 50 m/s² / 10 cycles
operating frequency maximum0.19 1/s
type of coordination2
utilization categoryAC-3a
according to IEC 60947-4-2AC-3a
according to IEC 60947-4-3AC-1
reference code according to IEC 81346-2Q
reference code according to IEC 81346-2:2019Q
reference code according to IEC 81346-2:2024Q
continuous current at AC-1 rated value9 A
continuous current at AC-3 rated value7 A
Substance Prohibitance (day/month/year)10/01/2024
SVHC substance nameLead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight0.655 kg
Motor control functions
direct startYes
reverse startingYes
product component motor brake outputNo
Short-circuit protection
product function short circuit protectionYes; resettable
design of short-circuit protectionfully electronic
at 230 V rated value100 000 A
at 400 V rated value100 000 A
at 240 V rated value100 kA
at 415 V rated value100 kA
at 440 V rated value100 kA
Protective and monitoring functions
type of protection function of the overcurrent releaseLI
manual RESETYes
temperature-compensated overload protectionYes
trip classCLASS 10A / 10E / 20E
at 400 V rated value100 kA
at 480 V rated value100 kA
maximum short-circuit current breaking capacity (Icu) in the IT network at 400 V rated value100 kA
response value current of instantaneous short-circuit trip unit115.1 A
Safety related data
safe stateLoad circuit open
MTBF33 a; at 40 °C
Electrical Safety
protection class IP on the front according to IEC 60529IP20
Main circuit
number of poles for main current circuit3
design of the switching contactsolid-state
minimum load [%]10 %; Relative to smallest settable Ie
type of the motor protectionsolid-state
480 V
208 ... 480 V
relative symmetrical tolerance of the operating voltage5 %
operating frequency 1 rated value50 Hz
operating frequency 2 rated value60 Hz
relative symmetrical tolerance of the operating frequency5 %
relative positive tolerance of the operating frequency5 %
relative negative tolerance of the operating frequency5 %
at AC at 400 V rated value7 A
at AC-1 at 400 V at ambient temperature 40 °C rated value9 A
at AC-3 at 400 V rated value7 A
at AC-53a at 400 V at ambient temperature 40 °C rated value7 A
ampacity when starting maximum50.4 A
at AC-3 at 400 V rated value3 kW
at AC-3 at 230 V 3 phase rated value1.73 kW
at AC-53a at 400 V rated value3 kW
operating power for 3-phase motors at 400 V at 50 Hz0.18 ... 3 kW
derating temperature40 °C
Inputs/ Outputs
number of digital inputs4
note4 via 4DI(LC) submodule
of the inputs16 byte
of the outputs4 byte
Supply voltage
type of voltage of the supply voltageDC
in standby mode of operation125 mA
during operation190 mA
at switching on of motor190 mA
control supply voltage at DC rated value20.4 ... 28.8 V
inrush current peak at 24 V50 A
duration of inrush current peak at 24 V0.2 ms
ON-delay time80 ms
OFF-delay time40 ms
Power Electronics
at 230 V rated value1.4 hp
at 200/208 V rated value2.1 hp
at 220/230 V rated value2.3 hp
at 460/480 V rated value4.9 hp
Installation/ mounting/ dimensions
fastening methodpluggable in BaseUnit
height151 mm
width30 mm
depth167 mm
Ambient conditions
during operation-25 ... +60 °C; For derating see manual
during transport-40 ... +70 °C
with upper limit without restrictions40 °C
Communication/ Protocol
supports PROFIenergy measured valuesNo
supports PROFIenergy shutdownNo
Connections/ Terminals
for main current circuitplug-in contact to base unit
for auxiliary and control circuitplug-in contact to base unit
1 for digital input signalsplug-in contact to 4DI (LC) submodule
2 for digital input signalsplug-in contact to 4DI (LC) submodule
for main energy infeedPlug contact to Base Unit
for load-side outgoing feederPlug contact to Base Unit
for supply voltage line-sidePlug contact to Base Unit
wire length for motor unshielded maximum200 m
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor at 480 V rated value7 A
conditional short-circuit current (Iq) with type of coordination 1 at 480 AC Y/277 V rated value100 000 A