Genel bilgiler
Ürün tipi tanımıAI 8xU/I/R/RTD BA
HW functional statusFS01
Firmware sürümüV1.0.0
FW update possibleVar
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Prioritized startupYok
Measuring range scalableYok
Scalable measured valuesYok
Adjustment of measuring rangeYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionV15.1 / V16
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
Operating mode
OversamplingYok
MSIVar
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNYok
Giriş akımı
Akım tüketimi, maks.0 mA; no supply required
Power
Power consumption from the backplane bus0,85 W
Güç kaybı
Güç kaybı, tipik0,9 W
Address space per module
Inputs16 bayt; typical, maximum 68 bytes, see manual for details
Outputs0 bayt
Analog girişler
Analog giriş sayısı8
For current measurement8
For voltage measurement8
For resistance/resistance thermometer measurement8
permissible input voltage for voltage input (destruction limit), max.12 V; 12 V continuous, 30 V for maks. 1 s
permissible input current for current input (destruction limit), max.40 mA
Constant measurement current for resistance-type transmitter, typ.230... 370 µA
Technical unit for temperature measurement adjustableVar; °C/°F/K
Analog input with oversamplingYok
Standardization of measured valuesYok
Giriş aralıkları (nominal değerler), gerilim
0 to +5 VYok
0 … +10 VYok
1 V to 5 VVar
— Input resistance (1 V to 5 V)10 MΩ
-1 V to +1 VVar
— Input resistance (-1 V to +1 V)10 MΩ
-10 V to +10 VVar
— Input resistance (-10 V to +10 V)10 MΩ
-2.5 V to +2.5 VYok
-25 mV to +25 mVYok
-250 mV to +250 mVYok
-5 V to +5 VVar
— Input resistance (-5 V to +5 V)10 MΩ
-50 mV to +50 mVVar
— Input resistance (-50 mV to +50 mV)10 MΩ
-500 mV to +500 mVVar
— Input resistance (-500 mV to +500 mV)10 MΩ
-80 mV to +80 mVYok
Input ranges (rated values), currents
0 … 20 mAVar
— Input resistance (0 to 20 mA)25 Ω; Plus yaklaşık 42 ohms for overvoltage protection by PTC
-20 mA to +20 mAVar
— Input resistance (-20 mA to +20 mA)25 Ω; Plus yaklaşık 42 ohms for overvoltage protection by PTC
4 mA to 20 mAVar
— Input resistance (4 mA to 20 mA)25 Ω; Plus yaklaşık 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
Type BYok
Type CYok
Type EYok
Type JYok
Type KYok
Type LYok
Type NYok
Type RYok
Type SYok
Type TYok
Type UYok
Type TXK/TXK(L) to GOSTYok
Input ranges (rated values), resistance thermometer
Cu 10Yok
Cu 10 according to GOSTYok
Cu 50Yok
Cu 50 according to GOSTYok
Cu 100Yok
Cu 100 according to GOSTYok
Ni 10Yok
Ni 10 according to GOSTYok
Ni 100Var; Standard/climate
— Input resistance (Ni 100)10 MΩ
Ni 100 according to GOSTYok
Ni 1000Var; Standard/climate
— Input resistance (Ni 1000)10 MΩ
Ni 1000 according to GOSTYok
LG-Ni 1000Var; Standard/climate
— Input resistance (LG-Ni 1000)10 MΩ
Ni 120Yok
Ni 120 according to GOSTYok
Ni 200Yok
Ni 200 according to GOSTYok
Ni 500Yok
Ni 500 according to GOSTYok
Pt 10Yok
Pt 10 according to GOSTYok
Pt 50Yok
Pt 50 according to GOSTYok
Pt 100Var; Standard/climate
— Input resistance (Pt 100)10 MΩ
Pt 100 according to GOSTYok
Pt 1000Var; Standard/climate
— Input resistance (Pt 1000)10 MΩ
Pt 1000 according to GOSTYok
Pt 200Yok
Pt 200 according to GOSTYok
Pt 500Yok
Pt 500 according to GOSTYok
Input ranges (rated values), resistors
0 to 150 ohmsYok
0 to 300 ohmsYok
0 to 600 ohmsVar
— Input resistance (0 to 600 ohms)10 MΩ
0 to 3000 ohmsYok
0 to 6000 ohmsVar
— Input resistance (0 to 6000 ohms)10 MΩ
PTCVar
— Input resistance (PTC)10 MΩ
Kablo uzunluğu
Ekranlı, maks.200 m; 50 m 50 mV
Analog value generation for the inputs
Measurement principleintegrating
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Entegrasyon süresi, parametrelenebilirVar
Integration time (ms)2,5 / 16,67 / 20 / 100 ms
Basic conversion time, including integration time (ms)10 / 24 / 27 / 107 ms
— additional conversion time for wire-break monitoring4 ms (to be considered in R/RTD/U 1 to 5 V measurement)
— additional conversion time for resistance measurement8 ms
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
Smoothing of measured values
Number of smoothing levels4
parameterizableVar
Step: NoneVar
Step: lowVar
Step: MediumVar
Step: HighVar
Connection of signal encoders
for voltage measurementVar
for current measurement as 2-wire transducerVar; with external supply
for current measurement as 4-wire transducerVar
for resistance measurement with two-wire connectionVar; Only for PTC
for resistance measurement with three-wire connectionVar; All measuring ranges except PTC; internal compensation of the cable resistances
for resistance measurement with four-wire connectionYok
Errors/accuracies
Linearity error (relative to input range), (+/-)0,1 %
Temperature error (relative to input range), (+/-)0,006 %/K
Crosstalk between the inputs, max.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,1 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0,5 %
Current, relative to input range, (+/-)0,5 %
Resistance, relative to input range, (+/-)0,5 %
Resistance thermometer, relative to input range, (+/-)Ptxxx Standard: ±1,2 K, Ptxxx Climate: ±0,8 K, Nixxx Standard: ±0,8 K, Nixxx Climate: ±0,8 K
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,3 %
Current, relative to input range, (+/-)0,3 %
Resistance, relative to input range, (+/-)0,3 %
Resistance thermometer, relative to input range, (+/-)Ptxxx Standard: ±1,0 K, Ptxxx Climate: ±0,5 K, Nixxx Standard: ±0,5 K, Nixxx Climate: ±0,5 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode voltage, max.4 V
Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionVar
Alarms
Diagnostic alarmVar
Limit value alarmVar; two upper ve two lower limit values in her biri case
Diagnoses
Monitoring the supply voltageYok
Wire breakVar; Only for 1... 5 V, 4... 20 mA, R, ve RTD
Short-circuitYok
Group errorYok
Overflow/UnderflowVar
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
MAINT LED’iYok
Monitoring of the supply voltage (PWR-LED)Yok
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; red LED
Potential separation channels
Kanallar arasıYok
Kanallar arası, grup başına8
between the channels and backplane busVar
Permissible potential difference
between the inputs (UCM)8 V DC
Between the inputs and MANA (UCM)4 V DC
Isolation
Isolation tested with707 V DC (type test)
Standartlar, onaylar, sertifikalar
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for applications according to AMS 2750Yok
Suitable for applications according to CQI-9Yok
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]38,6 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]14,4 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]24,6 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.44 kg
Security
signed firmware updateYok
securely removing dataYok
data integrityYok
Çalışma ortam sıcaklığı
Yatay montaj, min.-30 °C; From FS05
Yatay montaj, maks.60 °C
Dikey montaj, min.-30 °C; From FS05
Dikey montaj, maks.40 °C
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m; Restrictions for installation altitudes > 2.000 m, see manual
Absolute humidity
dew point, min.-60 °C; suitable for dry room applications
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık250 g
Other
Note:please order front connectors (screw-in/push-in) separately