Genel bilgiler
Ürün tipi tanımı4AI TC
HW functional status7
Firmware sürümüV1.0.1
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Installation type/mounting
Rack mountingYok
Front mountingVar
Rail mountingVar
Wall mounting/direct mountingYok
Besleme gerilimi
Type of supply voltageDC
İzin verilen aralık, alt sınır (DC)20,4 V
İzin verilen aralık, üst sınır (DC)28,8 V
Giriş akımı
Current consumption, typ.17 mA
from load voltage (power bus), max.30 mA
Güç kaybı
Güç kaybı, tipik0,4 W
Donanım yapılandırması
Fieldbus connection via separate transceiverVar
Analog girişler
Analog giriş sayısı4
Cycle time (all channels) max.320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz
Technical unit for temperature measurement adjustableVar
Giriş aralıkları
GerilimVar
CurrentYok
ThermocoupleVar
Resistance thermometerYok
ResistanceYok
Giriş aralıkları (nominal değerler), gerilim
-80 mV to +80 mVVar
— Input resistance (-80 mV to +80 mV)1.000 kΩ
Input ranges (rated values), thermocouples
type BVar
— Input resistance (Type B)1.000 kΩ
type CVar
— Input resistance (Type C)1.000 kΩ
Type EVar
— Input resistance (Type E)1.000 kΩ
Type JVar
— Input resistance (type J)1.000 kΩ
Type KVar
— Input resistance (Type K)1.000 kΩ
Type LVar
— Input resistance (Type L)1.000 kΩ
Type NVar
— Input resistance (Type N)1.000 kΩ
Type RVar
— Input resistance (Type R)1.000 kΩ
Type SVar
— Input resistance (Type S)1.000 kΩ
Type TVar
— Input resistance (Type T)1.000 kΩ
Type UVar
— Input resistance (Type U)1.000 kΩ
Temperature compensation
— internal temperature compensationVar; via supplied TC sensor module
— external temperature compensation with compensations socketVar; via temperature value, acquired by an analog module of the same ET 200iSP station
Characteristic linearization
ParameterizableVar
— for thermocouplesVar
Kablo uzunluğu
Ekranlı, maks.50 m
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Entegrasyon süresi, parametrelenebilirVar
Basic conversion time, including integration time (ms)80 ms 50 Hz; 66 ms 60 Hz
— additional conversion time for wire-break monitoring5 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Smoothing of measured values
ParameterizableVar; in 4 stages
Step: NoneVar; 1x cycle time
Step: lowVar; 4x cycle time
Step: MediumVar; 32x cycle time
Step: HighVar; 64x cycle time
Errors/accuracies
Linearity error (relative to input range), (+/-)0,015 %
Temperature error (relative to input range), (+/-)0,02 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,01 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0,15 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.70 dB
Common mode interference, min.90 dB
Arayüzler
PROFINET arayüz sayısı0
Protokoller
PROFINET IO protokolünü desteklerYok
PROFIsafeYok
PROFIBUSYok
Diğer protokoller
other bus systemsYok
Alarms
Diagnostic alarmVar; Parameterizable
Limit value alarmVar; Parameterizable
Diagnoses
Diagnostic information readableVar
Wire breakVar; R > 1,7 kOhm
Tanılama gösterge LED’i
Group error SF (red)Var
Ex(i) characteristics
Module for Ex(i) protectionVar; for more Co/Lo combinations, see certificate IECEx KEM 05,0008
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.5,9 V
Io (short-circuit current), max.15 mA
Po (power output), max.23 mW
Co (permissible external capacity), max.43 µF
Lo (permissible external inductivity), max.100 mH
Potential separation
between channels and powerbusVar
Potential separation analog inputs
Kanallar arasıVar; Functional
between the channels and backplane busVar
Koruma derecesi ve sınıfı
IP koruma sınıfıIP30
Standartlar, onaylar, sertifikalar
CE işaretiCE 0344
UKCA markDEKRA 21UKEX0086 Importer UK: Siemens plc Manchester M20 2UR
cULusLISTED E334384
FM onayıCLASSIFIED 3025852
Suitable for safety functionsYok
INMETRO certificateUL-BR 12,0071
reference designation according to IEC 81346-2 (2009)K
Highest safety class achievable in safety mode
acc. to EN 954n.a.
Performance level according to ISO 13849-1yok
SIL acc. to IEC 61508Yok
Use in hazardous areas
ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
ATEX certificateKEMA 04 ATEX 1246
IECExIECEx KEM 05,0008
CCC Ex2020322316002943
EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Explosion protection category for gasATEX gas explosion protection, Zone 1
Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
associated equipment (Ex ia)Var
associated equipment (Ex ib)Var
Marine approval
Germanischer Lloyd (GL)Var
American Bureau of Shipping (ABS)Var
Bureau Veritas (BV)Var
Det Norske Veritas (DNV)Var
Connection method
Design of electrical connectionScrew/spring-type terminal
Ölçüler
Genişlik30 mm
Yükseklik129 mm
Derinlik136,5 mm
Ağırlık