Genel bilgiler
Ürün tipi tanımı8DI NAMUR
HW functional status12
Firmware sürümüV1.1.1
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Installation type/mounting
Rack mountingYok
Front mountingVar
Rail mountingVar
Wall mounting/direct mountingYok
Besleme gerilimi
Type of supply voltageDC
İzin verilen aralık, alt sınır (DC)20,4 V
İzin verilen aralık, üst sınır (DC)28,8 V
Giriş akımı
Current consumption, typ.80 mA
from load voltage (power bus), max.90 mA
Güç kaybı
Güç kaybı, tipik1,1 W
Donanım yapılandırması
Fieldbus connection via separate transceiverVar
Dijital girişler
Dijital giriş sayısı8
Digital input functions, parameterizable
— Number, max.2; normal ve periodic count function
— Counting frequency, max.5 kHz; with a cable length of 20 m: 5 kHz; with a cable length of 100 m: 1 kHz; with a cable length of 200 m: 500 Hz
Giriş gerilimi
Type of input voltageDC
Giriş akımı
for signal "0", max. (permissible quiescent current)1,2 mA
“1” sinyali için, min.2,1 mA
Input delay (for rated value of input voltage)
Delay time for signal change, min.2,8 ms
Delay time for signal change, max.3,5 ms
Standart girişler için
— “0”dan “1”e, min.2,8 ms
— “0”dan “1”e, maks.3,5 ms
— at "1" to "0", min.2,8 ms
— at "1" to "0", max.3,5 ms
Kablo uzunluğu
Ekranlı, maks.500 m
Encoder
Number of connectable encoders, max.8
Bağlanabilir enkoderler
NAMUR encoderVar
Arayüzler
PROFINET arayüz sayısı0
Number of RS 485 interfaces0
Protokoller
PROFINET IOYok
PROFIsafeYok
PROFIBUSYok
Interrupts/diagnostics/status information
Diagnostics functionVar
Alarms
Diagnostic alarmVar; Parameterizable
Hardware interruptYok
Diagnoses
Diagnostic information readableVar
Wire breakVar; I load < 0,2 mA with NAMUR encoders/encoders ve NAMUR changeover contact/encoders to DIN 19234
short-circuitVar; R load < 150 ohms with NAMUR sensor/sensor ve NAMUR changeover contact/sensor to DIN 19234
Tanılama gösterge LED’i
Group error SF (red)Var
Status indicator digital input (green)Var
Entegre fonksiyonlar
Frekans ölçümüVar; (Gate time) 50 ms; 200 ms; 1 s
Number of frequency meters2
Ex(i) characteristics
Module for Ex(i) protectionVar; for more Co/Lo combinations, see certificate IECEx KEM 05,0010
maximum values for connecting terminals for gas group IIC
Uo (no-load voltage), max.9,6 V
Io (short-circuit current), max.16 mA
Po (power output), max.38 mW
Co (permissible external capacity), max.3,6 µF
Lo (permissible external inductivity), max.110 mH
Dijital girişlerde potansiyel ayrımı
Kanallar arasıYok
between the channels and backplane busVar
Permissible potential difference
between different circuits60 V DC/30 V AC
Koruma derecesi ve sınıfı
IP koruma sınıfıIP30
Standartlar, onaylar, sertifikalar
CE işaretiCE 0344
UKCA markDEKRA 21UKEX0084 Importer UK: Siemens plc Manchester M20 2UR
cULusLISTED E334384
FM onayıCLASSIFIED 3025852
Suitable for safety functionsYok
INMETRO certificateUL-BR 12,0068
reference designation according to IEC 81346-2 (2009)K
Use in hazardous areas
ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
ATEX certificateKEMA 04 ATEX 1248
IECExIECEx KEM 05,0010
CCC Ex2020322310002637
EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Explosion protection category for gasATEX gas explosion protection, Zone 1
Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
associated equipment (Ex ia)Var
associated equipment (Ex ib)Var
Marine approval
Germanischer Lloyd (GL)Var
American Bureau of Shipping (ABS)Var
Bureau Veritas (BV)Var
Det Norske Veritas (DNV)Var
Connection method
Design of electrical connectionScrew/spring-type terminal
Ölçüler
Genişlik30 mm
Yükseklik129 mm
Derinlik136,5 mm
Ağırlık
Ağırlık, yaklaşık255 g