Genel bilgiler
Ürün tipi tanımıAQ 4xU/I ST
FW update possibleVar
based on6ES7532-5HD00-0AB0
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Prioritized startupYok
Output range scalableYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYok
MSOVar
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNVar
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Giriş akımı
Akım tüketimi, maks.190 mA; with 24 V DC supply
Power
Power consumption from the backplane bus0,6 W
Güç kaybı
Güç kaybı, tipik4 W
Analog çıkışlar
Analog çıkış sayısı4; > +60 °C maks. 4x ±10 V permissible
Voltage output, short-circuit protectionVar
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Cycle time (all channels), min.3,2 ms; independent of number of activated channels
Output ranges, voltage
0 to 10 VVar
1 V to 5 VVar
-5 V to +5 VYok
-10 V to +10 VVar
Çıkış aralıkları, akım
0 … 20 mAVar
-20 mA to +20 mAVar
4 mA to 20 mAVar
Connection of actuators
for voltage output two-wire connectionVar
for voltage output four-wire connectionVar
for current output two-wire connectionVar
Load impedance (in rated range of output)
with voltage outputs, min.1 kΩ; 0,5 kOhm 1 to 5 V
with voltage outputs, capacitive load, max.1 µF
with current outputs, max.750 Ω
with current outputs, inductive load, max.10 mH
Kablo uzunluğu
Ekranlı, maks.800 m; for current, 200 m for voltage
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Dönüşüm süresi (kanal başına)0,5 ms
Settling time
for resistive load1,5 ms
for capacitive load2,5 ms
for inductive load2,5 ms
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0,02 %
Linearity error (relative to output range), (+/-)0,15 %
Temperature error (relative to output range), (+/-)0,002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0,05 %
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0,4 %
Current, relative to output range, (+/-)0,4 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0,2 %
Current, relative to output range, (+/-)0,2 %
Interrupts/diagnostics/status information
Diagnostics functionVar
Substitute values connectableVar
Alarms
Diagnostic alarmVar
Diagnoses
Monitoring the supply voltageVar
Wire breakVar; Only for output type "current"
Short-circuitVar; Only for output type "voltage"
Overflow/UnderflowVar
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
Monitoring of the supply voltage (PWR-LED)Var; green LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; red LED
Potential separation channels
Kanallar arasıYok
Kanallar arası, grup başına4
between the channels and backplane busVar
Between the channels and load voltage L+Var
Permissible potential difference
between S- and MANA (UCM)8 V DC
Isolation
Isolation tested with750 V DC (type test) ve according to EN 50155 (routine test)
Standartlar, onaylar, sertifikalar
Suitable for safety-related tripping of standard modulesVar; From FS05
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]37,6 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]11,1 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]26,8 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.364 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
Railway application
EN 50121-3-2Var; EMC for rail vehicles
EN 50121-4Var; EMC for signal ve telecommunications systems
EN 50121-5Var; EMC for fixed installations ve railway power supply equipment
EN 50124-1Var; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0,5 kV; UNm = 24 V DC
EN 50125-1Var; Rail vehicles - see ambient conditions
EN 50125-2Var; Stationary electrical equipment - see ambient conditions
EN 50125-3Var; Signal ve telecommunications systems - see ambient conditions; vibrations ve shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Var; Rail vehicles - temperature class OT4, ST1/ST2, yatay mounting position
EN 61373Var; Rail vehicles - vibrations ve shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Var; For proof of conformity, see Service & Support
Security
signed firmware updateYok
data integrityYok
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.40 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.2.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Var; Class 5B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 5B3 talep üzerine
— to chemically active substances according to EN 60721-3-5Var; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Var; Class 5S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Var; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık310 g
Other