Genel bilgiler
Ürün tipi tanımıDQ 16x24VDC/0.5A HF
FW update possibleVar
based on6ES7522-1BH01-0AB0
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeVar
Prioritized startupVar
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQVar
DQ with energy-saving functionYok
PWMYok
Cam control (switching at comparison values)Yok
OversamplingYok
MSOVar
Integrated operating cycle counterVar
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar; through internal protection with 7 A per group
Giriş akımı
Akım tüketimi, maks.30 mA
Çıkış gerilimi
Nominal değer (DC)24 V
Power
Power consumption from the backplane bus1,1 W
Güç kaybı
Güç kaybı, tipik2 W
Dijital çıkışlar
Type of digital outputTransistor
Dijital çıkış sayısı16
Current-sourcingVar
Digital outputs, parameterizableVar
output type acc. to IEC 61131, type 0.5Var
Short-circuit protectionVar; Clocked electronically
Response threshold, typ.1 A
Endüktif kapatma geriliminin sınırlandırılmasıL+ (-53 V)
Controlling a digital inputVar
Çıkışların anahtarlama kapasitesi
Omik yükte, maks.0,5 A
Lamba yükünde, maks.5 W
Load resistance range
lower limit48 Ω
upper limit12 kΩ
Çıkış gerilimi
“1” sinyali için, min.L+ (-0.8 V)
Çıkış akımı
“1” sinyali için nominal değer0,5 A
for signal "1" permissible range, max.0,5 A
“0” sinyali için artık akım, maks.0,5 mA
Omik yükte çıkış gecikmesi
“0”dan “1”e, maks.100 µs
“1”den “0”a, maks.500 µs
Parallel switching of two outputs
for logic linksVar
for upratingYok
for redundant control of a loadVar
Anahtarlama frekansı
Omik yükte, maks.100 Hz
with inductive load, max.0,5 Hz; According to IEC 60947-5-1, DC-13
Lamba yükünde, maks.10 Hz
Total current of the outputs
Current per channel, max.0,5 A; see additional description in the manual
Current per group, max.4 A; see additional description in the manual
Current per module, max.8 A; see additional description in the manual
Kablo uzunluğu
Ekranlı, maks.1.000 m
Ekransız, maks.600 m
Isochronous mode
Execution and activation time (TCO), min.70 µs
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Diagnostics functionVar
Substitute values connectableVar
Alarms
Diagnostic alarmVar
Maintenance interruptVar
Diagnoses
Monitoring the supply voltageVar
Wire breakVar
Short-circuitVar
Group errorVar
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
MAINT LED’iVar; Yellow LED
Monitoring of the supply voltage (PWR-LED)Var; green LED
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; red LED
Potential separation channels
Kanallar arasıYok
Kanallar arası, grup başına8
between the channels and backplane busVar
Isolation
Isolation tested with750 V DC (type test) ve according to EN 50155 (routine test)
Standartlar, onaylar, sertifikalar
Suitable for safety functionsYok
Suitable for safety-related tripping of standard modulesVar; From FS02
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]43,8 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]9,5 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]34,5 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.231 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
Railway application
EN 50121-3-2Var; EMC for rail vehicles
EN 50121-4Var; EMC for signal ve telecommunications systems
EN 50121-5Var; EMC for fixed installations ve railway power supply equipment (shielded cables required)
EN 50124-1Var; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0,5 kV; UNm = 24 V DC
EN 50125-1Var; Rail vehicles - see ambient conditions
EN 50125-2Var; Stationary electrical equipment - see ambient conditions
EN 50125-3Var; Signal ve telecommunications systems - see ambient conditions; vibrations ve shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Var; Rail vehicles - temperature class OT4, ST1/ST2, yatay mounting position
EN 61373Var; Rail vehicles - vibrations ve shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Var; For proof of conformity, see Service & Support
Security
signed firmware updateYok
data integrityYok
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs maks. 8x 0,5 A, maks. toplam current per group 2 A; +85 °C for 10 minutes (OT4, ST1/ST2 acc. to EN 50155)
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.40 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.2.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Var; Class 5B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 5B3 talep üzerine
— to chemically active substances according to EN 60721-3-5Var; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Var; Class 5S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Var; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık230 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776