Genel bilgiler
Ürün tipi tanımıSM 1232 AQ 4x 14 bit
based on6ES7232-4HD32-0XB0
Besleme gerilimi
Nominal değer (DC)24 V
Giriş akımı
Current consumption, typ.45 mA
from backplane bus 5 V DC, typ.80 mA
Güç kaybı
Güç kaybı, tipik1,5 W
Analog çıkışlar
Analog çıkış sayısı4; Current veya voltage
Output ranges, voltage
-10 V to +10 VVar
Çıkış aralıkları, akım
0 … 20 mAVar
Load impedance (in rated range of output)
with voltage outputs, min.1.000 Ω
with current outputs, max.600 Ω
Kablo uzunluğu
Ekranlı, maks.100 m; shielded, twisted pair
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.14 bit; Voltage: 14 bit; Current : 13 bit
Errors/accuracies
Temperature error (relative to output range), (+/-)25 °C ±0,3%, to 55 °C ±0,6% toplam measurement range
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0,3 %
Current, relative to output range, (+/-)0,3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Common mode voltage, max.12 V
Interrupts/diagnostics/status information
AlarmsVar
Diagnostics functionVar
Alarms
Diagnostic alarmVar
Diagnoses
Monitoring the supply voltageVar
Wire breakVar
short-circuitVar
Tanılama gösterge LED’i
for status of the outputsVar
for maintenanceVar
Isolation
Isolation tested with750 V DC (type test) ve according to EN 50155 (routine test)
Koruma derecesi ve sınıfı
IP koruma sınıfıIP20
Standartlar, onaylar, sertifikalar
CE işaretiVar
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]36,4 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]7,46 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]29,1 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.18 kg
Railway application
EN 50121-3-2Var; EMC for rail vehicles
EN 50121-4Var; EMC for signal ve telecommunications systems
EN 50124-1Var; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0,5 kV; UNm = 24 V DC
EN 50125-1Var; Rail vehicles - see ambient conditions
EN 50125-2Var; Stationary electrical equipment - see ambient conditions
EN 50125-3Var; Signal ve telecommunications systems - see ambient conditions; vibrations ve shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Var; Rail vehicles - temperature class OT1, ST1/ST2, yatay mounting position
EN 61373Var; Rail vehicles - vibrations ve shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Var; For proof of conformity, see Service & Support
Serbest düşme
Düşme yüksekliği, maks.0,3 m; five times, in product package
Çalışma ortam sıcaklığı
Yatay montaj, min.-25 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.60 °C; = Tmax; +70 °C for 10 min (OT1, ST1/ST2 acc. to EN 50155)
Dikey montaj, min.-25 °C; = Tmin
Dikey montaj, maks.50 °C; = Tmax
Depolama/taşıma ortam sıcaklığı
min.-40 °C
maks.70 °C
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.2.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Var; Class 5B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 5B3 talep üzerine
— to chemically active substances according to EN 60721-3-5Var; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Var; Class 5S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Var; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Connection method
required front connectorVar
Mechanics/material
plasticVar
Ölçüler
Genişlik45 mm
Yükseklik100 mm
Derinlik75 mm
Ağırlık
Ağırlık, yaklaşık180 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776