Genel bilgiler
Ürün tipi tanımıBU type U0
based on6ES7193-6BP00-0BU0
Besleme gerilimi
Nominal değer (DC)See manual
For P1 and P2 bus120 V
For AUX bus120 V; Equal potential group to P1/P2 bus veya PE
for process terminals120 V
Rated value (AC)See manual
For P1 and P2 bus277 V
For AUX bus277 V; Equal potential group to P1/P2 bus veya PE
for process terminals277 V; 480 V (L1 - L2 - L3); 277 V (L, N)
Mains filter
DahiliYok
Current carrying capacity
up to 60 °C, max.10 A
For P1 and P2 bus, max.10 A
For AUX bus, max.10 A
For process terminals, max.10 A; Point of contact, derating depends on the module
Donanım yapılandırması
Automatic encodingVar
Formation of potential groups
New potential groupYok
Potential group continued from the leftVar
Slots
Number of slots1
Potential separation
between backplane bus and supply voltageVar
between process terminals and supply voltageVar; Not applicable for process terminals 15 ve 16
between power bus and supply voltageYok
Isolation
Isolation tested with2.545 V DC (type test) ve according to EN 50155 (routine test)
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]0,873 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]0,866 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]0 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.0011 kg
Railway application
EN 50121-3-2Var; EMC for rail vehicles
EN 50121-4Var; EMC for signal ve telecommunications systems
EN 50121-5Var; EMC for fixed installations ve railway power supply equipment
EN 50124-1Var; Railway applications - overvoltage category OV3; pollution degree PD2; UNm = 230 V AC
EN 50125-1Var; Rail vehicles - see ambient conditions
EN 50125-2Var; Stationary electrical equipment - see ambient conditions
EN 50125-3Var; Signal ve telecommunications systems - see ambient conditions; vibrations ve shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Var; Rail vehicles - temperature class OT4, ST1/ST2, yatay mounting position
EN 61373Var; Rail vehicles - vibrations ve shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Var; For proof of conformity, see Service & Support
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
Dikey montaj, min.-40 °C; = Tmin
Dikey montaj, maks.50 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.2.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Var; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Var; Class 5B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 5B3 talep üzerine
— to chemically active substances according to EN 60721-3-5Var; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Var; Class 5S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-5Var; Class 5M2 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
— against mechanical environmental conditions in agriculture acc. to ISO 15003Var; level 1 (Location LE) using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Var; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Terminals
Terminal typePush-in terminal
Conductor cross-section, min.0,14 mm²; 0,2 mm² without wire end ferrule
Conductor cross-section, max.2,5 mm²; 1,5 mm² with wire end ferrule
Number of process terminals to I/O module16
Number of terminals to AUX bus0
Number of add-on terminals0
Number of terminals with connection to P1 and P2 bus2
Ölçüler
Genişlik20 mm
Yükseklik117 mm
Derinlik35 mm
Ağırlık
Ağırlık, yaklaşık50 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776