Genel bilgiler
Ürün tipi tanımıAI 16xU BA
FW update possibleVar
based on6ES7531-7LH00-0AB0
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Prioritized startupYok
Measuring range scalableYok
Scalable measured valuesYok
Adjustment of measuring rangeYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
OversamplingYok
MSIVar
CiR - Configuration in RUN
Reparameterization possible in RUNVar
Calibration possible in RUNYok
Power
Power consumption from the backplane bus0,85 W
Güç kaybı
Güç kaybı, tipik0,75 W
Analog girişler
Analog giriş sayısı16
For voltage measurement16
permissible input voltage for voltage input (destruction limit), max.12 V; 12 V continuous, 30 V for maks. 1 s
Giriş aralıkları (nominal değerler), gerilim
0 to +5 VYok
0 … +10 VYok
1 V to 5 VVar
— Input resistance (1 V to 5 V)10 MΩ
-1 V to +1 VVar
— Input resistance (-1 V to +1 V)10 MΩ
-10 V to +10 VVar
— Input resistance (-10 V to +10 V)10 MΩ
-2.5 V to +2.5 VYok
-25 mV to +25 mVYok
-250 mV to +250 mVYok
-5 V to +5 VVar
— Input resistance (-5 V to +5 V)10 MΩ
-50 mV to +50 mVYok
-500 mV to +500 mVYok
-80 mV to +80 mVYok
Kablo uzunluğu
Ekranlı, maks.200 m
Analog value generation for the inputs
Measurement principleintegrating
Kanal başına entegrasyon/dönüşüm süresi ve çözünürlük
Aşım dahil çözünürlük (işaret biti dahil), maks.16 bit
Entegrasyon süresi, parametrelenebilirVar
Integration time (ms)2,5 / 16,67 / 20 / 100 ms
Basic conversion time, including integration time (ms)10 / 24 / 27 / 107 ms
— additional conversion time for wire-break monitoring4 ms (to be considered for 1 to 5 V measurement)
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10 Hz
Smoothing of measured values
parameterizableVar
Step: NoneVar
Step: lowVar
Step: MediumVar
Step: HighVar
Connection of signal encoders
for voltage measurementVar
Errors/accuracies
Linearity error (relative to input range), (+/-)0,1 %
Temperature error (relative to input range), (+/-)0,006 %/K
Crosstalk between the inputs, max.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0,1 %
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0,6 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0,3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
Series mode interference (peak value of interference < rated value of input range), min.40 dB
Common mode voltage, max.4 V
Common mode interference, min.60 dB
Interrupts/diagnostics/status information
Diagnostics functionVar
Alarms
Diagnostic alarmVar
Limit value alarmVar; two upper ve two lower limit values in her biri case
Diagnoses
Monitoring the supply voltageYok
Wire breakVar; Only for 1... 5 V
Short-circuitYok
Group errorYok
Overflow/UnderflowVar
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
MAINT LED’iYok
Monitoring of the supply voltage (PWR-LED)Yok
Channel status displayVar; green LED
for channel diagnosticsVar; red LED
for module diagnosticsVar; red LED
Potential separation channels
Kanallar arasıYok
Kanallar arası, grup başına16
between the channels and backplane busVar
Permissible potential difference
between the inputs (UCM)8 V DC
Between the inputs and MANA (UCM)4 V DC
Isolation
Isolation tested with707 V DC (type test)
Security
signed firmware updateYok
data integrityYok
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Yatay montaj, maks.70 °C; = Tmax
Dikey montaj, min.-40 °C; = Tmin (incl. condensation/frost)
Dikey montaj, maks.40 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık250 g