Genel bilgiler
Ürün tipi tanımıDQ 16x230VAC/1A ST (Triac)
FW update possibleVar
based on6ES7522-5FH00-0AB0
Product function
I&M dataVar; I&M0 to I&M3
Isochronous modeYok
Prioritized startupVar
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Operating mode
DQVar
DQ with energy-saving functionYok
PWMYok
OversamplingYok
MSOVar
Integrated operating cycle counterVar; FW V1.3.0 veya üstü
Çıkış gerilimi
Rated value (AC)230 V; 120/230 V AC, 50/60 Hz
Power
Power consumption from the backplane bus1,2 W
Güç kaybı
Güç kaybı, tipik11,1 W
Dijital çıkışlar
Type of digital outputTriac
Dijital çıkış sayısı16
Current-sinkingVar
Current-sourcingVar
Digital outputs, parameterizableVar
Short-circuit protectionYok
built-in fuse6,3 A melting fuse, slow-blow
Size of motor starters according to NEMA, max.4
Çıkışların anahtarlama kapasitesi
Omik yükte, maks.1 A
Lamba yükünde, maks.50 W
Çıkış gerilimi
“1” sinyali için, min.L1 (-1.5 V) maximum output current; L1 (-8.5 V) minimum output current
Çıkış akımı
“1” sinyali için nominal değer1 A
for signal "1" permissible range, min.10 mA
for signal "1" permissible range, max.15 A; maks. 1 AC cycle
“0” sinyali için artık akım, maks.2 mA
Omik yükte çıkış gecikmesi
“0”dan “1”e, maks.1 AC cycle
“1”den “0”a, maks.1 AC cycle
Parallel switching of two outputs
for logic linksYok
for upratingYok
for redundant control of a loadVar
Anahtarlama frekansı
Omik yükte, maks.10 Hz
with inductive load, max.0,5 Hz
Lamba yükünde, maks.1 Hz
Total current of the outputs
Current per channel, max.1 A; see additional description in the manual
Current per group, max.2 A; see additional description in the manual
Current per module, max.10 A; see additional description in the manual
Kablo uzunluğu
Ekranlı, maks.1.000 m
Ekransız, maks.600 m
Interrupts/diagnostics/status information
Diagnostics functionYok
Substitute values connectableVar
Alarms
Diagnostic alarmYok
Maintenance interruptVar; maintenance alarm for switching cycle counter
Diagnoses
Monitoring the supply voltageYok
Wire breakYok
Short-circuitYok
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
Monitoring of the supply voltage (PWR-LED)Yok
Channel status displayVar; green LED
for channel diagnosticsYok
for module diagnosticsVar; red LED
Potential separation channels
Kanallar arasıYok
Kanallar arası, grup başına2
between the channels and backplane busVar
Permissible potential difference
between different circuits250 V AC between the channels ve the backplane bus; 500 V AC between the channels
Isolation
Isolation tested with3.100 V DC
Standartlar, onaylar, sertifikalar
Suitable for safety functionsYok
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]43,8 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]9,5 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]34,5 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.231 kg
Security
signed firmware updateYok
data integrityYok
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Yatay montaj, maks.70 °C; = Tmax; see Derating BasedOn (e.g. manual), additionally Tmax > 60 °C maks. 4 A aggregate current per module, maks. 0,25 A per output
Dikey montaj, min.-40 °C; = Tmin; Startup @ -25 °C
Dikey montaj, maks.60 °C
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.2.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık310 g