Genel bilgiler
Ürün tipi tanımıIM 155-5 DP ST
FW update possibleVar
Vendor identification (VendorID)81AAh
based on6ES7155-5BA00-0AB0
Product function
I&M dataVar; I&M0 to I&M3
Module swapping during operation (hot swapping)Yok
Isochronous modeYok
IRTYok
Tool changerYok
Local coupling, IO dataYok
Mühendislik aracı
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
Configuration control
via datasetYok
Besleme gerilimi
Nominal değer (DC)24 V
İzin verilen aralık, alt sınır (DC)19,2 V
İzin verilen aralık, üst sınır (DC)28,8 V
Ters polarite korumasıVar
Short-circuit protectionVar
Mains buffering
Mains/voltage failure stored energy time5 ms
Giriş akımı
Akım tüketimi (nominal değer)0,2 A; 24 V DC ve without load
Akım tüketimi, maks.1,2 A; 20,4 V DC ve maks. load
Ani çekiş akımı, maks.4 A
I²t0,09 A²·s
from interface 5 V DC, max.80 mA
Power
Infeed power to the backplane bus14 W
Güç kaybı
Güç kaybı, tipik4 W
Address space per module
Address space per module, max.64 bayt; For input ve output data respectively
Address space per station
Address space per station, max.244 bayt; For input ve output data respectively
Donanım yapılandırması
Integrated power supplyVar; 14 W
System power supply can be plugged in to left of IMYok
Number of permissible power segments1; incl. interface module
Rack
Modules per rack, max.12; I/O modules
Arayüzler
Number of PROFIBUS interfaces1; 1 port
Arayüz tipleri
RS 485Var
Port sayısı1
Dahili switchYok
BusAdapter (PROFINET)Yok
Protokoller
PROFIBUS DP deviceVar
Servisler
— IRTYok
RS 485
İletim hızı, maks.12 Mbit/s
Protokoller
PROFINET IO protokolünü desteklerYok
PROFIsafeVar
PROFIBUSVar
EtherNet/IPYok
Modbus TCPYok
Servisler
— SYNC capabilityVar
— FREEZE capabilityVar
— DPV1Var
Interrupts/diagnostics/status information
Status indicatorVar
AlarmsVar
Diagnostics functionVar
Tanılama gösterge LED’i
RUN LEDVar; green LED
ERROR LED’iVar; red LED
MAINT LED’iVar; Yellow LED
Connection display DPVar; green LED
Potential separation
between backplane bus and electronicsYok
between PROFIBUS DP and all other circuit componentsVar
between supply and all other circuitsYok
Permissible potential difference
between different circuitsSafety extra low voltage SELV
Isolation
Isolation tested with707 V DC (type test)
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]64,1 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]11,1 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]53,6 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.669 kg
Çalışma ortam sıcaklığı
Yatay montaj, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
Yatay montaj, maks.60 °C; = Tmax
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
ET-Connection
via BU/BA SendYok
Ölçüler
Genişlik35 mm
Yükseklik147 mm
Derinlik129 mm
Ağırlık
Ağırlık, yaklaşık360 g