Genel bilgiler
based on6ED1055-1MB00-0BA2
Installation type/mounting
Mountingon 35 mm DIN rail, 2 spacing units wide
Besleme gerilimi
12 V DCVar
24 V DCVar
İzin verilen aralık, alt sınır (DC)10,8 V
İzin verilen aralık, üst sınır (DC)28,8 V
Dijital girişler
Dijital giriş sayısı4
Giriş gerilimi
Type of input voltageDC
“0” sinyali için< 5 V DC
“1” sinyali için> 8,5 V
Giriş akımı
for signal "0", max. (permissible quiescent current)0,88 mA
for signal "1", typ.1,5 mA
Standart girişler için
— “0”dan “1”e, maks.1,5 ms
— at "1" to "0", max.1,5 ms
Dijital çıkışlar
Dijital çıkış sayısı4; Relays
Short-circuit protectionYok
Controlling a digital inputVar
Çıkışların anahtarlama kapasitesi
Lamba yükünde, maks.1.000 W
Çıkış akımı
“1” sinyali için nominal değer5 A
for signal "1" minimum load current100 mA
Parallel switching of two outputs
for upratingYok
Anahtarlama frekansı
Omik yükte, maks.2 Hz
with inductive load, max.0,5 Hz
mechanical, max.10 Hz
Switching capacity of contacts
— with inductive load, max.3 A
— with resistive load, max.5 A
EN 55 011’e göre radyo girişimi yayımı
Sınır sınıfı B, yerleşim alanlarında kullanım içinVar
Koruma derecesi ve sınıfı
IP koruma sınıfıIP20
Ekolojik ayak izi
Çevresel ürün beyanıVar
Küresel ısınma potansiyeli
— Küresel ısınma potansiyeli (toplam) [CO₂ eşd.]59,1 kg
— Küresel ısınma potansiyeli (üretim sırasında) [CO₂ eşd.]5,82 kg
— Küresel ısınma potansiyeli (çalışma sırasında) [CO₂ eşd.]53,6 kg
— Küresel ısınma potansiyeli (ömür sonrası) [CO₂ eşd.]-0.373 kg
Çalışma ortam sıcaklığı
min.-40 °C; = Tmin; Startup @ -25 °C
maks.70 °C; = Tmax; Tmax > +55 °C maks. load 3 A per relay veya maks. toplam current 10 A
At cold restart, min.-25 °C; incl. condensation / frost permitted (no commissioning under condensation conditions)
Depolama/taşıma ortam sıcaklığı
min.-40 °C
maks.70 °C
Deniz seviyesine göre çalışma yüksekliği
Installation altitude above sea level, max.5.000 m
Ambient air temperature-barometric pressure-altitudeTmin... Tmax 1.140 hPa... 795 hPa (-1 000 m... +2.000 m) // Tmin... (Tmax - 10 K) 795 hPa... 658 hPa (+2.000 m... +3.500 m) // Tmin... (Tmax -20 K) 658 hPa... 540 hPa (+3.500 m... +5.000 m)
Bağıl nem
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), yatay installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsVar; Incl. diesel ve oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Var; Class 3B2 mold, fungus ve dry rot spores (with the exception of fauna); Class 3B3 talep üzerine
— to chemically active substances according to EN 60721-3-3Var; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Var; Class 3S4 incl. sand, dust, *
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Var; Class 6B2 mold ve fungal spores (excluding fauna); Class 6B3 talep üzerine
— to chemically active substances according to EN 60721-3-6Var; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Var; Class 6S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Var; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Var; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) ve level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Var; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Var; Type 1 protection
Military testing according to MIL-I-46058C, Amendment 7Var; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AVar; Conformal coating, Class A
Ölçüler
Genişlik35,5 mm
Yükseklik90 mm
Derinlik58 mm