product brand nameSIMOCODE
product designationCurrent/voltage measuring module
product type designationM-CP
General technical data
measuring procedureRMS value measurement
size of the circuit-breakerS00, S0
current measurementVar
voltage measurementVar
active power measurementVar
energy measurementVar
frequency measurementVar
active power monitoring for pump dry-run according to Ignition protection type Ex bYok
measuring procedure for current measurementTRMS
current measuring range extension with external current transformersVar
measuring procedure for voltage measurementTRMS
measurable supply voltage between the line conductors at AC maximum rated value690 V
input for thermistor connectionYok
with degree of pollution 3 at AC rated value690 V
for wires of main circuit according to IEC 60947-1 rated value6 kV
surge voltage resistance rated value6.000 V
shock resistance according to IEC 60068-2-2715 g / 11 ms
vibration resistance1 … 6 Hz / 15 mm; 6 … 500 Hz / 2 g
reference code according to IEC 81346-2F
Substance Prohibitance (day/month/year)01/01/2024
SVHC substance nameLead CAS-Yok. 7439-92-1 Lead monoxide (lead oxide) CAS-Yok. 1317-36-8
Net Weight199,58 g
Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1class A
EMC immunity according to IEC 60947-1corresponds to degree of severity 3
due to burst according to IEC 61000-4-42 kV
due to conductor-earth surge according to IEC 61000-4-52 kV
due to conductor-conductor surge according to IEC 61000-4-51 kV
field-based interference according to IEC 61000-4-310 V/m
Inputs/ Outputs
number of outputs as contact-affected switching element0
Protective and monitoring functions
power factor monitoringVar
ground-fault monitoringVar
voltage detectionVar
trip classCLASS 5E, 7E, 10E, 15E, 20E, 25E, 30E, 35E ve 40E adjustable
current detectionVar
overload protectionVar
Precision
of frequency measurement+/- 1,5 %, 0,25... 80 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos phi (0.5...1), 50/60 Hz, 25 °C
for current measurement 1+/- 1,5%, in range 0,25 A... 80 A, in range 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), 50/60 Hz, 25 °C
for current measurement 2+/- 3%, in range 80 A... 320 A, in range 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), 50/60 Hz, 25 °C
for voltage measurement 1+/- 1,5 %, in range 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), 50/60 Hz, 25 °C
at cos phi-measurement 1+/- 3%, 0,4 A... 80 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
at cos phi-measurement 2+/- 5%, 80 A... 320 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for active power measurement 1+/- 5%, 0,25 A... 80 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for active power measurement 2+/- 10%, 80 A... 320 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for energy measurement 1+/- 5%, 0,25 A... 80 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for energy measurement 2+/- 10%, 80 A... 320 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for apparent power measurement 1+/- 3%, 0,25 A... 80 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
for apparent power measurement 2+/- 5%, 80 A... 320 A, 0,85 x 110 V... 1,1 x 690 V (line-to-line voltages), cos-phi (0.4...1), 50/60 Hz, 25 °C
accuracy of ground-fault monitoringIn the range 30 %.. 120 %/Is: +/- 10 % (Class CI-A), in range 15 %.. 30 % Ie: +/- 25 % (Class CI-B), both values acc. to IEC 60947-1 Annex T
temperature drift per °CReference temperature: 25°C
measured variable frequency45... 65 Hz
Installation/ mounting/ dimensions
mounting positionany
fastening methodscrew ve snap-on mounting
height55,2 mm
width98,8 mm
depth40,8 mm
top30 mm
bottom30 mm
left0 mm
right0 mm
diameter of inlet opening7,3 mm
diameter of inlet opening for current measurement7,3 mm
Connections/ Terminals
for main current circuitstraight-through transformers
type of electrical connection at the measurement inputs for voltagescrew-type terminals
finely stranded with core end processing1x (0,25... 2,5 mm²), 2x (0,25... 1,0 mm²)
solid1x (0,25... 2,5 mm²), 2x (0,25... 1,0 mm²)
for AWG cables solid1x (24... 14), 2x (24... 18)
for AWG cables stranded1x (20... 14), 2x (20... 16)
tightening torque at the measurement inputs for voltage0,5... 0,6 N·m
tightening torque [lbf·in] at the measurement inputs for voltage4,4... 5,3 lbf·in
Ambient conditions
1 maximum2.000 m
2 maximum3.000 m; maks. +50 °C (no protective separation)
3 maximum4.000 m; maks. +40 °C (no protective separation)
during operation-25... +70 °C
during storage-40... +80 °C
during transport-40... +80 °C
during operation according to IEC 607213K24 (condensation occasionally, no precipitation, no water, no ice formation, relative humidity 10... 95%), 3C3 (no salt mist), 3B2, 3S5 (sand must not enter the device), 3M6
during storage according to IEC 607211K22 (condensation occasionally, no precipitation, no water, no ice formation, relative humidity 10... 95%), 1C2 (no salt mist), 1B2, 1S10 (sand must not enter the device), 1M4
during transport according to IEC 607212K12 (no condensation, no thermal shock), 2C1 (no salt mist), 2B2, 2S1, 2M2
relative humidity during operation5... 95 %
Short-circuit protection
product function short circuit protectionYok
IEC 61508
Safety Integrity Level (SIL) according to IEC 615081
ATEX
IECExVar; IECEx BVS 25,0051 X
according to ATEX directive 2014/34/EUBVS 25 ATEX F001 X
explosion device group and category according to ATEX directive 2014/34/EUII (2) G, II (2 ) D, I (M2) / I (M2), II (1/2) G, II (1G/2D)
Galvanic isolation
(electrically) protective separation according to IEC 60947-1all circuits with protective separation (double clearances ve creepage distances)
Main circuit
number of poles for main current circuit3
adjustable current response value current of the current-dependent overload release4... 40 A
— at 50 Hz rated value110... 690 V
— at 60 Hz rated value110... 690 V
operating frequency rated value50... 60 Hz
Control circuit/ Control
type of voltageAC
inrush current maximum400 A; 10 x Io
Ürün bilgileri
EAN4047621102498
Ürün ailesiSIMOCODE M 3UF8 motor management and control devices
Yaşam döngüsü durumuAktif
Gümrük tarife kodu85371098
Teslimat ve lojistik
Menşe ülkeCzech Republic
Teslim süresi5 gün
İade edilebilirEvet
Net ağırlık0,19958 Kg
Paket ölçüleri (U x G x Y)115 x 48 x 63 MM
Standart paket adedi1 adet
Minimum sipariş adedi1
Tehlikeli maddeHayır
İhracat kontrolüAL : N / ECCN : 9N9999
Çevre ve uyumluluk
RoHS uyumuSince: 01-01-24
WEEE kategorisi5
REACH bilgisiLead CAS-No. 7439-92-1 > 0,1 % (w / w)
Siemens kataloğu
Ürün grubuX0ME
Katalog kimliğiCC-IC10
Grup koduR711
Ürün sınıfıStraightforward, can be reused over the short term