product brand nameSIRIUS
product categoryHybrid switching devices
product designationSoft starter
product type designation3RW52
of standard HMI module usable3RW5980-0HS00
of high feature HMI module usable3RW5980-0HF00
of communication module PROFINET standard usable3RW5980-0CS00
of communication module PROFIBUS usable3RW5980-0CP00
of communication module Modbus TCP usable3RW5980-0CT00
of communication module Modbus RTU usable3RW5980-0CR00
of communication module Ethernet/IP3RW5980-0CE00
of circuit breaker usable at 400 V3VA2450-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
of circuit breaker usable at 500 V3VA2450-7MN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
of circuit breaker usable at 400 V at inside-delta circuit3VA2510-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
of circuit breaker usable at 500 V at inside-delta circuit3VA2510-6HN32-0AA0; Type of coordination 1, Iq = 65 kA, CLASS 10
of the gG fuse usable up to 690 V2x3NA3365-6; Type of coordination 1, Iq = 65 kA
of the gG fuse usable at inside-delta circuit up to 500 V2x3NA3365-6; Type of coordination 1, Iq = 65 kA
of full range R fuse link for semiconductor protection usable up to 690 V3NE1436-2; Type of coordination 2, Iq = 65 kA
of back-up R fuse link for semiconductor protection usable up to 690 V3NE3340-8; Type of coordination 2, Iq = 65 kA
General technical data
starting voltage [%]30... 100 %
stopping voltage [%]50 %; non-adjustable
start-up ramp time of soft starter0... 20 s
current limiting value [%] adjustable130... 700 %
CE markingVar
UL onayıVar
CSA approvalVar
HMI-High FeatureYok
is supported HMI-StandardVar
is supported HMI-High FeatureVar
product feature integrated bypass contact systemVar
number of controlled phases3
for main current circuit100 ms
for control circuit100 ms
insulation voltage rated value600 V
degree of pollution3, acc. to IEC 60947-4-2
impulse voltage rated value6 kV
blocking voltage of the thyristor maximum1.600 V
service factor1
surge voltage resistance rated value6 kV
between main and auxiliary circuit600 V
shock resistance15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
utilization category according to IEC 60947-4-2AC 53a
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)02/15/2018
SVHC substance nameLead CAS-Yok. 7439-92-1 Lead monoxide (lead oxide) CAS-Yok. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-Yok. 71868-10-5 Melamine CAS-Yok. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-Yok. 119-47-1 Dibutylbis(pentane-2,4-dionato-O,O')tin CAS-Yok. 22673-19-4
Net Weight9,713 kg
ramp-up (soft starting)Var
soft stoppingVar
Soft TorqueVar
adjustable current limitationVar
pump stopVar
intrinsic device protectionVar
motor overload protectionVar; Full motor protection (thermistor motor protection ve electronic motor overload protection)
evaluation of thermistor motor protectionVar; Type A PTC veya Klixon / Thermoclick
inside-delta circuitVar
auto-RESETVar
manual RESETVar
remote resetVar; By turning off the control supply voltage
communication functionVar
operating measured value displayVar; Only in conjunction with special accessories
error logbookVar; Only in conjunction with special accessories
via software parameterizableYok
via software configurableVar
PROFIenergyVar; in connection with the PROFINET Standard communication module
firmware updateVar
removable terminal for control circuitVar
torque controlYok
analog outputYok
Power Electronics
at 40 °C rated value470 A
at 50 °C rated value416 A
at 60 °C rated value380 A
at 40 °C rated value814 A
at 50 °C rated value721 A
at 60 °C rated value658 A
rated value200... 480 V
at inside-delta circuit rated value200... 480 V
relative negative tolerance of the operating voltage-15 %
relative positive tolerance of the operating voltage10 %
relative negative tolerance of the operating voltage at inside-delta circuit-15 %
relative positive tolerance of the operating voltage at inside-delta circuit10 %
at 230 V at 40 °C rated value132 kW
at 230 V at inside-delta circuit at 40 °C rated value250 kW
at 400 V at 40 °C rated value250 kW
at 400 V at inside-delta circuit at 40 °C rated value400 kW
Operating frequency 1 rated value50 Hz
Operating frequency 2 rated value60 Hz
relative negative tolerance of the operating frequency-10 %
relative positive tolerance of the operating frequency10 %
at rotary coding switch on switch position 1200 A
at rotary coding switch on switch position 2218 A
at rotary coding switch on switch position 3236 A
at rotary coding switch on switch position 4254 A
at rotary coding switch on switch position 5272 A
at rotary coding switch on switch position 6290 A
at rotary coding switch on switch position 7308 A
at rotary coding switch on switch position 8326 A
at rotary coding switch on switch position 9344 A
at rotary coding switch on switch position 10362 A
at rotary coding switch on switch position 11380 A
at rotary coding switch on switch position 12398 A
at rotary coding switch on switch position 13416 A
at rotary coding switch on switch position 14434 A
at rotary coding switch on switch position 15452 A
at rotary coding switch on switch position 16470 A
minimum200 A
for inside-delta circuit at rotary coding switch on switch position 1346 A
for inside-delta circuit at rotary coding switch on switch position 2378 A
for inside-delta circuit at rotary coding switch on switch position 3409 A
for inside-delta circuit at rotary coding switch on switch position 4440 A
for inside-delta circuit at rotary coding switch on switch position 5471 A
for inside-delta circuit at rotary coding switch on switch position 6502 A
for inside-delta circuit at rotary coding switch on switch position 7533 A
for inside-delta circuit at rotary coding switch on switch position 8565 A
for inside-delta circuit at rotary coding switch on switch position 9596 A
for inside-delta circuit at rotary coding switch on switch position 10627 A
for inside-delta circuit at rotary coding switch on switch position 11658 A
for inside-delta circuit at rotary coding switch on switch position 12689 A
for inside-delta circuit at rotary coding switch on switch position 13721 A
for inside-delta circuit at rotary coding switch on switch position 14752 A
for inside-delta circuit at rotary coding switch on switch position 15783 A
for inside-delta circuit at rotary coding switch on switch position 16814 A
at inside-delta circuit minimum346 A
minimum load [%]15 %; Relative to smallest settable Ie
at 40 °C after startup153 W
at 50 °C after startup137 W
at 60 °C after startup126 W
at 40 °C during startup7.903 W
at 50 °C during startup6.604 W
at 60 °C during startup5.794 W
Control circuit/ Control
type of voltage of the control supply voltageAC
at 50 Hz110... 250 V
at 60 Hz110... 250 V
relative negative tolerance of the control supply voltage at AC at 50 Hz-15 %
relative positive tolerance of the control supply voltage at AC at 50 Hz10 %
relative negative tolerance of the control supply voltage at AC at 60 Hz-15 %
relative positive tolerance of the control supply voltage at AC at 60 Hz10 %
control supply voltage frequency50... 60 Hz
relative negative tolerance of the control supply voltage frequency-10 %
relative positive tolerance of the control supply voltage frequency10 %
control supply current in standby mode rated value30 mA
holding current in bypass operation rated value100 mA
inrush current by closing the bypass contacts maximum2,2 A
inrush current peak at application of control supply voltage maximum12,2 A
duration of inrush current peak at application of control supply voltage2,2 ms
design of the overvoltage protectionVaristor
design of short-circuit protection for control circuit4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply
Inputs/ Outputs
number of digital inputs1
number of digital outputs3
not parameterizable2
digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)
number of analog outputs0
at AC-15 at 250 V rated value3 A
at DC-13 at 24 V rated value1 A
Installation/ mounting/ dimensions
mounting positionwith dikey mounting surface +/-90° rotatable, with dikey mounting surface +/- 22,5° tiltable to the front ve back
fastening methodscrew fixing
height393 mm
width210 mm
depth203 mm
forwards10 mm
backwards0 mm
upwards100 mm
downwards75 mm
at the side5 mm
weight without packaging9,9 kg
Connections/ Terminals
for main current circuitbusbar connection
for control circuitspring-loaded terminals
width of connection bar maximum45 mm
with conductor cross-section = 0.5 mm² maximum50 m
with conductor cross-section = 1.5 mm² maximum150 m
with conductor cross-section = 2.5 mm² maximum250 m
for DIN cable lug for main contacts stranded2x (50... 240 mm²)
for DIN cable lug for main contacts finely stranded2x (70... 240 mm²)
for control circuit solid2x (0,25... 1,5 mm²)
for control circuit finely stranded with core end processing2x (0,25... 1,5 mm²)
for AWG cables for control circuit solid2x (24... 16)
for AWG cables for control circuit finely stranded with core end processing2x (24... 16)
between soft starter and motor maximum800 m
at the digital inputs at AC maximum100 m
for main contacts with screw-type terminals14... 24 N·m
for auxiliary and control contacts with screw-type terminals0,8... 1,2 N·m
for main contacts with screw-type terminals124... 210 lbf·in
for auxiliary and control contacts with screw-type terminals7... 10,3 lbf·in
Ambient conditions
installation altitude at height above sea level maximum5.000 m
during operation-25... +60 °C; Please observe derating temperatures of 40 °C veya above
during storage and transport-40... +80 °C
during operation according to IEC 607213K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
during storage according to IEC 607211K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
during transport according to IEC 607212K2, 2C1, 2S1, 2M2 (maks. fall height 0,3 m)
Electromagnetic compatibility
EMC emitted interferenceacc. to IEC 60947-4-2: Class A
Communication/ Protocol
PROFINET standardVar
EtherNet/IPVar
Modbus RTUVar
Modbus TCPVar
PROFIBUSVar
UL/CSA ratings
— usable for Standard Faults up to 575/600 V according to ULType: Class J / L, maks. 1600 A; Iq = 30 kA
— usable for High Faults up to 575/600 V according to ULType: Class J / L, maks. 1200 A; Iq = 100 kA
— usable for Standard Faults at inside-delta circuit up to 575/600 V according to ULType: Class J / L, maks. 1600 A; Iq = 30 kA
— usable for High Faults at inside-delta circuit up to 575/600 V according to ULType: Class J / L, maks. 1200 A; Iq = 100 kA
at 200/208 V at 50 °C rated value150 hp
at 220/230 V at 50 °C rated value150 hp
at 460/480 V at 50 °C rated value350 hp
at 200/208 V at inside-delta circuit at 50 °C rated value250 hp
at 220/230 V at inside-delta circuit at 50 °C rated value250 hp
at 460/480 V at inside-delta circuit at 50 °C rated value600 hp
contact rating of auxiliary contacts according to ULR300-B300
Electrical Safety
protection class IP on the front according to IEC 60529IP00; IP20 with cover
touch protection on the front according to IEC 60529finger-safe, for dikey contact from the front with cover
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing84,2 kg
global warming potential [CO2 eq] / during sales2,81 kg
global warming potential [CO2 eq] / during operation721 kg
global warming potential [CO2 eq] / after end of life-21.8 kg
global warming potential [CO2 eq] / total786 kg
Ürün bilgileri
EAN4047621038087
Ürün ailesi3RW52 soft starters
Yaşam döngüsü durumuAktif
Gümrük tarife kodu85371098
Teslimat ve lojistik
Menşe ülkeCzech Republic
Teslim süresi5 gün
İade edilebilirEvet
Net ağırlık9,713 Kg
Paket ölçüleri (U x G x Y)501 x 328 x 338 MM
Standart paket adedi1 adet
Minimum sipariş adedi1
Tehlikeli maddeHayır
İhracat kontrolüAL : N / ECCN : N
Çevre ve uyumluluk
RoHS uyumuSince: 15-02-18
WEEE kategorisi4
REACH bilgisiLead CAS-No. 7439-92-1 > 0,1 % (w / w)
SCIP numarası18cf6ae5-2e6e-4b20-acd9-edc161f17652
Siemens kataloğu
Ürün grubu4981
Katalog kimliğiCC-IC10
Grup koduR711
Ürün sınıfıStraightforward, can be reused over the short term