product brand nameSIRIUS
product categoryHybrid switching devices
product designationSoft starter
product type designation3RW50
of standard HMI module usable3RW5980-0HS00
of high feature HMI module usable3RW5980-0HF00
of communication module PROFINET standard usable3RW5980-0CS00
of communication module PROFIBUS usable3RW5980-0CP00
of communication module Modbus TCP usable3RW5980-0CT00
of communication module Modbus RTU usable3RW5980-0CR00
of communication module Ethernet/IP3RW5980-0CE00
of circuit breaker usable at 400 V3VA2220-7MN32-0AA0; Type of assignment 1, Iq = 20 kA
of circuit breaker usable at 500 V3VA2220-7MN32-0AA0; Type of assignment 1, Iq = 20 kA
of the gG fuse usable up to 690 V3NA3244-6; Type of coordination 1, Iq = 65 kA
of full range R fuse link for semiconductor protection usable up to 690 V3NE1 230-0; Type of coordination 2, Iq = 65 kA
of back-up R fuse link for semiconductor protection usable up to 690 V3NE3 335; Type of coordination 2, Iq = 65 kA
of line contactor usable up to 480 V3RT1056
of line contactor usable up to 690 V3RT1064
General technical data
starting voltage [%]30... 100 %
stopping voltage [%]50 %; non-adjustable
start-up ramp time of soft starter0... 20 s
ramp-down time of soft starter0... 20 s
current limiting value [%] adjustable130... 700 %
CE markingVar
UL onayıVar
CSA approvalVar
HMI-High FeatureYok
is supported HMI-StandardVar
is supported HMI-High FeatureVar
product feature integrated bypass contact systemVar
number of controlled phases2
for main current circuit100 ms
for control circuit100 ms
insulation voltage rated value600 V
degree of pollution3, acc. to IEC 60947-4-2
impulse voltage rated value6 kV
blocking voltage of the thyristor maximum1.400 V
service factor1
surge voltage resistance rated value6 kV
between main and auxiliary circuit600 V
shock resistance15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
vibration resistance15 mm to 6 Hz; 2 g to 500 Hz
utilization category according to IEC 60947-4-2AC-53a
reference code according to IEC 81346-2Q
Substance Prohibitance (day/month/year)09/23/2019
SVHC substance nameLead CAS-Yok. 7439-92-1 Lead monoxide (lead oxide) CAS-Yok. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-Yok. 71868-10-5 Melamine CAS-Yok. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-Yok. 119-47-1 Perfluorobutane sulfonic acid (PFBS) ve its salts CAS-Yok. -
Net Weight5,253 kg
ramp-up (soft starting)Var
soft stoppingVar
Soft TorqueVar
adjustable current limitationVar
pump stopVar
intrinsic device protectionVar
motor overload protectionVar; Full motor protection (thermistor motor protection ve electronic motor overload protection)
evaluation of thermistor motor protectionVar; Type A PTC veya Klixon / Thermoclick
auto-RESETVar
manual RESETVar
remote resetVar; By turning off the control supply voltage
communication functionVar
operating measured value displayVar; Only in conjunction with special accessories
error logbookVar; Only in conjunction with special accessories
via software parameterizableYok
via software configurableVar
PROFIenergyVar; in connection with the PROFINET Standard communication module
voltage rampVar
torque controlYok
analog outputYok
Power Electronics
at 40 °C rated value171 A
at 50 °C rated value153 A
at 60 °C rated value141 A
rated value200... 480 V
relative negative tolerance of the operating voltage-15 %
relative positive tolerance of the operating voltage10 %
at 230 V at 40 °C rated value45 kW
at 400 V at 40 °C rated value90 kW
Operating frequency 1 rated value50 Hz
Operating frequency 2 rated value60 Hz
relative negative tolerance of the operating frequency-10 %
relative positive tolerance of the operating frequency10 %
at rotary coding switch on switch position 181 A
at rotary coding switch on switch position 287 A
at rotary coding switch on switch position 393 A
at rotary coding switch on switch position 499 A
at rotary coding switch on switch position 5105 A
at rotary coding switch on switch position 6111 A
at rotary coding switch on switch position 7117 A
at rotary coding switch on switch position 8123 A
at rotary coding switch on switch position 9129 A
at rotary coding switch on switch position 10135 A
at rotary coding switch on switch position 11141 A
at rotary coding switch on switch position 12147 A
at rotary coding switch on switch position 13153 A
at rotary coding switch on switch position 14159 A
at rotary coding switch on switch position 15165 A
at rotary coding switch on switch position 16171 A
minimum81 A
minimum load [%]15 %; Relative to smallest settable Ie
at 40 °C after startup29 W
at 50 °C after startup23 W
at 60 °C after startup20 W
at 40 °C during startup1.751 W
at 50 °C during startup1.478 W
at 60 °C during startup1.308 W
type of the motor protectionElectronic, tripping in the event of thermal overload of the motor
Control circuit/ Control
type of voltage of the control supply voltageAC/DC
at 50 Hz rated value24 V
at 60 Hz rated value24 V
relative negative tolerance of the control supply voltage at AC at 50 Hz-20 %
relative positive tolerance of the control supply voltage at AC at 50 Hz20 %
relative negative tolerance of the control supply voltage at AC at 60 Hz-20 %
relative positive tolerance of the control supply voltage at AC at 60 Hz20 %
control supply voltage frequency50... 60 Hz
relative negative tolerance of the control supply voltage frequency-10 %
relative positive tolerance of the control supply voltage frequency10 %
control supply voltage at DC rated value24 V
relative negative tolerance of the control supply voltage at DC-20 %
relative positive tolerance of the control supply voltage at DC20 %
control supply current in standby mode rated value160 mA
holding current in bypass operation rated value360 mA
inrush current by closing the bypass contacts maximum7,6 A
inrush current peak at application of control supply voltage maximum3,3 A
duration of inrush current peak at application of control supply voltage12,1 ms
design of the overvoltage protectionVaristor
design of short-circuit protection for control circuit4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply
Inputs/ Outputs
number of digital inputs1
number of digital outputs3
not parameterizable2
digital output version2 normally-open contacts (NO) / 1 changeover contact (CO)
number of analog outputs0
at AC-15 at 250 V rated value3 A
at DC-13 at 24 V rated value1 A
Installation/ mounting/ dimensions
mounting positionwith dikey mounting surface +/-90° rotatable, with dikey mounting surface +/- 22,5° tiltable to the front ve back
fastening methodscrew fixing
height198 mm
width120 mm
depth249 mm
forwards10 mm
backwards0 mm
upwards100 mm
downwards75 mm
at the side5 mm
weight without packaging5,2 kg
Connections/ Terminals
for main current circuitbusbar connection
for control circuitspring-loaded terminals
width of connection bar maximum25 mm
with conductor cross-section = 0.5 mm² maximum50 m
with conductor cross-section = 1.5 mm² maximum150 m
with conductor cross-section = 2.5 mm² maximum250 m
using the front clamping point solid16... 120 mm²
using the front clamping point finely stranded with core end processing16... 120 mm²
using the front clamping point finely stranded without core end processing10... 120 mm²
using the front clamping point stranded16... 70 mm²
using the back clamping point solid16... 120 mm²
r box terminal using the back clamping point6... 250 kcmil
using both clamping points solidmaks. 1x 95 mm², 1x 120 mm²
using both clamping points finely stranded with core end processingmaks. 1x 95 mm², 1x 120 mm²
using both clamping points finely stranded without core end processingmaks. 1x 95 mm², 1x 120 mm²
using both clamping points strandedmaks. 2x 120 mm²
using the back clamping point finely stranded with core end processing16... 120 mm²
using the back clamping point finely stranded without core end processing10... 120 mm²
using the back clamping point stranded16... 120 mm²
for AWG cables for main current circuit solid4... 250 kcmil
for DIN cable lug for main contacts stranded16... 95 mm²
for DIN cable lug for main contacts finely stranded25... 120 mm²
for control circuit solid2x (0,25... 1,5 mm²)
for control circuit finely stranded with core end processing2x (0,25... 1,5 mm²)
for AWG cables for control circuit solid2x (24... 16)
for AWG cables for control circuit finely stranded with core end processing2x (24... 16)
between soft starter and motor maximum800 m
at the digital inputs at AC maximum1.000 m
for main contacts with screw-type terminals10... 14 N·m
for auxiliary and control contacts with screw-type terminals0,8... 1,2 N·m
for main contacts with screw-type terminals89... 124 lbf·in
for auxiliary and control contacts with screw-type terminals7... 10,3 lbf·in
Ambient conditions
installation altitude at height above sea level maximum5.000 m
during operation-25... +60 °C; Please observe derating temperatures of 40 °C veya above
during storage and transport-40... +80 °C
during operation according to IEC 607213K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
during storage according to IEC 607211K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
during transport according to IEC 607212K2, 2C1, 2S1, 2M2 (maks. fall height 0,3 m)
Electromagnetic compatibility
EMC emitted interferenceacc. to IEC 60947-4-2: Class A
Communication/ Protocol
PROFINET standardVar
EtherNet/IPVar
Modbus RTUVar
Modbus TCPVar
PROFIBUSVar
UL/CSA ratings
— usable for Standard Faults at 460/480 V according to ULSiemens type: 3VA5225, maks. 250 A; Iq = 10 kA
— usable for High Faults at 460/480 V according to ULSiemens type: 3VA52, maks. 250 A; Iq max = 65 kA
— usable for Standard Faults up to 575/600 V according to ULType: Class RK5 / K5, maks. 400 A; Iq = 10 kA
— usable for High Faults up to 575/600 V according to ULType: Class J, maks. 350 A; Iq = 100 kA
at 200/208 V at 50 °C rated value50 hp
at 220/230 V at 50 °C rated value50 hp
at 460/480 V at 50 °C rated value100 hp
Electrical Safety
protection class IP on the front according to IEC 60529IP00; IP20 with cover
touch protection on the front according to IEC 60529finger-safe, for dikey contact from the front with cover
ATEX
Safety Integrity Level (SIL) according to IEC 61508 relating to ATEXSIL 1
PFHD with high demand rate according to IEC 61508 relating to ATEX9E-6 1/h
PFDavg with low demand rate according to IEC 61508 relating to ATEX0,09
hardware fault tolerance according to IEC 61508 relating to ATEX0
T1 value for proof test interval or service life according to IEC 61508 relating to ATEX3 a
ATEXVar
IECExVar
UKEXVar
Approvals Certificates
global warming potential [CO2 eq] / during manufacturing31,2 kg
global warming potential [CO2 eq] / during sales0,945 kg
global warming potential [CO2 eq] / during operation316 kg
global warming potential [CO2 eq] / after end of life-2.75 kg
global warming potential [CO2 eq] / total345 kg