General information
Product type designationTM FCT070
Firmware versionV1.0
FW update possibleYes
usable BaseUnitsBU type B1
Color code for module-specific color-coded labelCC40
Product function
I&M dataYes; I&M 0
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV16
STEP 7 configurable/integrated from versionV5.5 SP4 and higher
PROFINET from GSD version/GSD revisionGSDML V2.34
Supply voltage
Rated value (DC)24 V
Load voltage L+
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Short-circuit protectionYes
Reverse polarity protectionYes; against destruction
Input current
Current consumption, max.500 mA
Power
Active power input1.2 W
Address space per module
Inputs83 byte
Outputs7 byte
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementtype D
Digital inputs
Number of digital inputs2
Digital inputs, parameterizableYes
Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital input functions, parameterizable
product function, parameterizablestart dosing, stop dosing, pause dosing, continue dosing, force output, freeze output, zero adjust, reset totalizer 1, reset totalizer 2, reset totalizer 3
Freely usable digital inputYes
Input voltage
Type of input voltageDC
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+11 to +30V
permissible voltage at input, min.-30 V
permissible voltage at input, max.30 V
Input current
for signal "1", typ.2.5 mA
Cable length
shielded, max.50 m; depending on load and cable quality
unshielded, max.25 m; depending on load and cable quality
Digital outputs
Number of digital outputs2
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionYes; electronic/thermal
Digital output functions, parameterizable
Freely usable digital outputYes
Switching capacity of the outputs
with resistive load, max.300 mA
on lamp load, max.8 W
Load resistance range
lower limit80 Ω
upper limit10 kΩ
Output voltage
Type of output voltageDC
for signal "0", max.1 V
for signal "1", min.23.2 V; L+ (-0.8 V)
Output current
for signal "1" rated value300 mA
Switching frequency
switching frequency, min.0 Hz
switching frequency, max.12 Hz
Pulse output (passive)
Output voltage, max.23.2 V
ampacity of the external power supply300 mA
Frequency output
number of frequency outputs1
percentage pulse/pause ratio50 %
Cable length
shielded, max.50 m; depending on load and cable quality
unshielded, max.25 m; depending on load and cable quality
Errors/accuracies
relative suppression of the residual flow / min.0 %
relative suppression of the residual flow / max.9.9 %
Interfaces
Design of the interface for communicationDigital Sensor Link (DSL), ET 200SP backplane bus
Protocols
Bus protocol/transmission protocolPROFINET
Interrupts/diagnostics/status information
Substitute values connectableYes; Parameterizable
Alarms
Diagnostic alarmYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
for module diagnosticsYes; green/red DIAG LED
Measuring functions
Measured variablemass flow, volume flow, density, temperature, fraction
Potential separation
Potential separationto all inputs, to all supplies, to all communications interfaces
Design of electrical isolationgalvanic isolation
Potential separation channels
between the channelsNo
between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC (base isolation)
Isolation
Isolation tested with707 V DC (type test)
Ambient temperature during operation
horizontal installation, min.-25 °C
horizontal installation, max.60 °C; Observe derating
vertical installation, min.-25 °C
vertical installation, max.50 °C; Observe derating
Ambient temperature during storage/transportation
Storage, min.-40 °C
Storage, max.70 °C
Altitude during operation relating to sea level
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
Operation, min.5 %
Operation, max.95 %
Mechanics/material
of the transmitterplastic
Decentralized operation
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
to standard PROFINET controllerYes
Dimensions
Width20 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.32 g