General information
Product type designationCFU PA
HW functional statusFS02
Firmware versionV2.0.1
FW update possibleYes
Vendor identification (VendorID)002AH
Device identifier (DeviceID)060DH
Number of channels16
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
The user can configure digital channels as input/output as requiredYes
Digital channels can be parameterizedYes
Engineering with
STEP 7 TIA Portal configurable/integrated from versionV19 Update 2
STEP 7 configurable/integrated from versionSTEP 7 V5.7.1.4
PCS 7 configurable/integrated from versionV9.1 SP2 UC7
PROFIBUS from GSD version/GSD revision- / -
PROFINET from GSD version/GSD revisionGSDML V2.43 2024.03.08
Operating mode
DIYes
CounterYes
DQYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Installation type/mounting
Mountingon 35 mm DIN rail, 2 spacing units wide
Mounting positionHorizontal, vertical
Supply voltage
Type of supply voltage24 V DC
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
redundant power supplyYes
Mains buffering
Mains/voltage failure stored energy time5 ms; Bridging for field devices and communication
Input current
Current consumption (rated value)2.5 A
Current consumption, max.2.55 A
Inrush current, max.8 A
I²t0.3 A²·s
Encoder supply
Number of outputs8
Output voltage, min.18.2 V
Short-circuit protectionYes; Electronic
Output current
up to 60 °C, max.2 A
up to 70 °C, max.1 A
Power loss
Power loss, typ.8.2 W; Depending on the type of BusAdapter used (typ. RJ45)
Address space per station
Address space per station, max.1 440 byte; Dependent on configuration
Digital inputs
Number of digital inputs8
Digital inputs, parameterizableYes
Sourcing/sinking inputYes; P-reading
Input characteristic curve in accordance with IEC 61131, type 1Yes
Input characteristic curve in accordance with IEC 61131, type 2No
Input characteristic curve in accordance with IEC 61131, type 3Yes
Pulse extensionNo
horizontal installation
— up to 60 °C, max.8; Total current must be observed, see DQ
— up to 70 °C, max.8; Total current must be observed, see DQ
vertical installation
— up to 60 °C, max.8; Total current must be observed, see DQ
Digital input functions, parameterizable
CounterYes
— Number, max.1
— Counting frequency, max.1 kHz
— Counting width32 bit
— Counting direction up/downYes; Up
Input voltage
Rated value (DC)24 V
for signal "0"-30 to +5 V
for signal "1"+11 to +30V
Input current
for signal "1", typ.2.5 mA; Typical
for standard inputs
— parameterizableNo
— at "0" to "1", max.3.2 ms; for counter function 0,1 ms
— at "1" to "0", max.3.2 ms; for counter function 0,1 ms
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Digital outputs
Type of digital outputTransistor
Number of digital outputs8
Current-sinkingNo
Current-sourcingYes
Short-circuit protectionYes
Response threshold, typ.0.7 to 1.3 A
Open-circuit detectionYes
Limitation of inductive shutdown voltage toTyp. L+ (-50 V)
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.0.5 A
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit12 kΩ
Output voltage
Type of output voltageDC
for signal "1", min.Ue minus 1 V
Output current
for signal "1" rated value0.5 A
for signal "0" residual current, max.0.1 mA
Output delay with resistive load
"0" to "1", max.50 µs
"1" to "0", max.100 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadNo
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.2 Hz
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.0.5 A
horizontal installation
— up to 60 °C, max.2 A
— up to 70 °C, max.1 A
vertical installation
— up to 60 °C, max.2 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Connectable encoders
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Interfaces
Number of PROFINET interfaces1
Number of PROFIBUS interfaces0
PROFIBUS PA
Transmission rate, max.31.25 kbit/s
Automatic addressingYes
System-supported integration of field devices via PA profilesYes
Extended fieldbus diagnosticsYes
1. Interface
Interface typePROFINET
IsolatedYes
Interface types
Number of ports2; via BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes
Protocols
PROFINET IO deviceYes
PROFIBUS DP deviceNo
Media redundancyYes; as MRP client
RJ 45 (Ethernet)
100 MbpsYes
AutonegotiationYes
AutocrossingYes
Protocols
Supports protocol for PROFINET IOYes
Redundancy mode
PROFINET system redundancy (S2)Yes; Type S2
Media redundancy
— MRPYes
Open IE communication
LLDPYes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Alarms
Diagnostic alarmYes
Maintenance interruptYes
Limit value alarmYes
Hardware interruptYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes
Short-circuitYes
Diagnostics indication LED
RUN LEDYes; green LED
ERROR LEDYes; red LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green/red LED
Channel status displayYes; green/red LED
Status indicator digital input (green)Yes
Status indicator digital output (green)Yes
Connection display LINK TX/RXYes; 2x green LEDs on BusAdapter
Spur line status/faultYes
Potential separation
between the channels and PROFINETYes
Potential separation digital inputs
between the channelsNo
between the channels and the power supply of the electronicsNo
Potential separation digital outputs
between the channelsNo
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with1 500 V AC between PROFINET and other electronics
Degree and class of protection
IP degree of protectionIP20
Ambient temperature during operation
min.-40 °C
max.70 °C
horizontal installation, min.-40 °C
horizontal installation, max.70 °C; Observe derating
vertical installation, min.-40 °C
vertical installation, max.60 °C; Observe derating
Ambient temperature during storage/transportation
min.-40 °C
max.70 °C
Relative humidity
Operation, max.95 %
Connection method
Design of electrical connectionConnection plug
Spur line
Number of spur lines8
Type of cableType A
Cable diameter, min.6 mm
Cable diameter, max.12 mm
Conductor cross-section, min.0.2 mm²
Conductor cross-section, max.2.5 mm²
Cable length, max.120 m
Number of connectable field devices8
total current output to field devices, max.320 mA
Current limitation per field device, max.40 mA
No-load voltage, max.15.3 V
short-circuit proofYes
Short-circuit current (test current); max.8 mA
intrinsically safe according to FISCO modelYes
Debounce logicYes
Dimensions
Width329 mm
Height123 mm
Depth74 mm
Weights
Weight, approx.650 g