Load voltage L+
Rated value (DC)24 V; Only required for supplying 2-wire transmitters
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.400 mA; for 16 connected, fully controlled 2-wire transmitters
from backplane bus 5 V DC, max.700 mA
Power loss
Power loss, typ.4.5 W
Analog inputs
Number of analog inputs16
For voltage/current measurement16
For resistance measurement8
permissible input voltage for voltage input (destruction limit), max.18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max.40 mA
Constant measurement current for resistance-type transmitter, typ.1.67 mA
Input ranges
VoltageYes
CurrentYes
ThermocoupleYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
1 V to 5 VYes
— Input resistance (1 V to 5 V)1 MΩ
-1 V to +1 VYes
— Input resistance (-1 V to +1 V)1 MΩ
-10 V to +10 VYes
— Input resistance (-10 V to +10 V)1 MΩ
-2.5 V to +2.5 VYes
— Input resistance (-2.5 V to +2.5 V)1 MΩ
-25 mV to +25 mVYes
— Input resistance (-25 mV to +25 mV)1 MΩ
-250 mV to +250 mVYes
— Input resistance (-250 mV to +250 mV)1 MΩ
-5 V to +5 VYes
— Input resistance (-5 V to +5 V)1 MΩ
-50 mV to +50 mVYes
— Input resistance (-50 mV to +50 mV)1 MΩ
-500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)1 MΩ
-80 mV to +80 mVYes
— Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), currents
0 to 20 mAYes
— Input resistance (0 to 20 mA)50 Ω
-10 mA to +10 mAYes
— Input resistance (-10 mA to +10 mA)50 Ω
-20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)50 Ω
4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)50 Ω
-5 mA to +5 mAYes
— Input resistance (-5 mA to +5 mA)50 Ω
Input ranges (rated values), thermocouples
Type BYes
— Input resistance (Type B)1 MΩ
Type EYes
— Input resistance (Type E)1 MΩ
Type JYes
— Input resistance (type J)1 MΩ
Type KYes
— Input resistance (Type K)1 MΩ
Type LYes
— Input resistance (Type L)1 MΩ
Type NYes
— Input resistance (Type N)1 MΩ
Type RYes
— Input resistance (Type R)1 MΩ
Type SYes
— Input resistance (Type S)1 MΩ
Type TYes
— Input resistance (Type T)1 MΩ
Type UYes
— Input resistance (Type U)1 MΩ
Input ranges (rated values), resistance thermometer
Ni 100Yes
— Input resistance (Ni 100)1 MΩ
Ni 1000Yes
— Input resistance (Ni 1000)1 MΩ
Pt 100Yes
— Input resistance (Pt 100)1 MΩ
Pt 1000Yes
— Input resistance (Pt 1000)1 MΩ
Pt 200Yes
— Input resistance (Pt 200)1 MΩ
Pt 500Yes
— Input resistance (Pt 500)1 MΩ
Input ranges (rated values), resistors
0 to 48 ohmsYes
— Input resistance (0 to 48 ohms)1 MΩ
0 to 150 ohmsYes
— Input resistance (0 to 150 ohms)1 MΩ
0 to 300 ohmsYes
— Input resistance (0 to 300 ohms)1 MΩ
0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)1 MΩ
0 to 6000 ohmsYes; Usable up to 5000 Ohm
— Input resistance (0 to 6000 ohms)1 MΩ
Temperature compensation
— ParameterizableYes
— external temperature compensation with Pt100Yes
— external temperature compensation with compensations socketYes
— dynamic reference temperature valueYes
Characteristic linearization
ParameterizableYes
— for thermocouplesType B, E, J, K, L, N, R, S, T, U
— for resistance thermometerPt100, Pt200, Pt500, Pt1000, Ni100, Ni1000
Cable length
shielded, max.200 m; 50 m with thermocouples and input ranges ≤ 80 mV
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit; 16 / 16 / 16
Integration time, parameterizableYes
Basic conversion time (ms)6 / 20,1 / 23,5 ms
Integration time (ms)2,5 / 16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 Hz
Connection of signal encoders
for voltage measurementYes; possible
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
for resistance measurement with two-wire connectionYes; Line resistances are also measured
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Temperature error (relative to input range), (+/-)0.004 %/K
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.3 %; ±0.3 % at ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 to 5 V, ±10 V; ±0.31 % at ±80 mV; ±0.32 % at ±50 mV; ±0.35 % at ±25 mV
Current, relative to input range, (+/-)0.3 %; at 0 to 20 mA, ±5 mA, ±10 mA, ±20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.3 %; ±0.3% at 0 to 48 Ohm (4-conductor measurement), 0 to 150 Ohm (4-conductor measurement), 0 to 300 Ohm (4-conductor measurement), 0 to 600 Ohm (4-conductor measurement), 0 to 5000 Ohm (4-conductor measurement, in range of 6000 Ohm); ±0.4% at 0 to 300 Ohm (3-conductor measurement), 0 to 600 Ohm (3-conductor measurement), 0 to 5000 Ohm (3-conductor measurement, in range of 6000 Ohm);
Resistance thermometer, relative to input range, (+/-)0.4 %
Thermocouple, relative to input range, (+/-)TC Type B (±11.5 K), TC Type R (±7.3 K), TC Type S (±8.3 K), TC Type T (±1.7 K), TC Type E (±3.2 K), TC Type J (±4.3 K), TC Type K (±6.2 K), TC Type U (±2.8 K), TC Type L (±4.2 K), TC Type N (±4.4 K)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.15 %; ±0.15% at ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 V to 5 V, ±10 V; ±0.17% at ±80 mV; ±0.19% at ±50 mV; ±0.23% at ±25 mV
Current, relative to input range, (+/-)0.15 %; at 0 to 20 mA, ±5 mA, ±10 mA, ±20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.15 %; ±0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); ±0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms)
Resistance thermometer, relative to input range, (+/-)0.3 %
Thermocouple, relative to input range, (+/-)TC Type B (±7.6 K), TC Type R (±4.8 K) TC Type S (±5.4 K), TC Type T (±1.1 K), TC Type E (±1.8 K), TC Type J (±2.3 K), TC Type K (±3.4 K), TC Type U (±1.7 K), TC Type L (±2.3 K), TC Type N (±2.6 K)
Interrupts/diagnostics/status information
Diagnostics functionYes; Parameterizable
Alarms
Diagnostic alarmYes; Parameterizable
Limit value alarmYes; Parameterizable
Hardware interruptYes; Parameterizable
Diagnoses
Diagnostic information readableYes
Diagnostics indication LED
internal fault INTF (red)Yes
external fault EXTF (red)Yes
Potential separation analog inputs
Potential separation analog inputsYes; internal/external
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Isolation
Isolation tested with2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground
Dimensions
Width25 mm
Height290 mm
Depth210 mm
Weights
Weight, approx.500 g