Load voltage L+
Rated value (DC)24 V; Only required for supplying 2-wire transmitters
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.200 mA; for 8 connected, fully controlled 2-wire transmitters
from backplane bus 5 V DC, max.600 mA
Power loss
Power loss, typ.3.5 W
Analog inputs
Number of analog inputs8
For voltage/current measurement8
For resistance measurement4
permissible input voltage for voltage input (destruction limit), max.18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20)
permissible input current for current input (destruction limit), max.40 mA; Permanent
Constant measurement current for resistance-type transmitter, typ.1.67 mA
Input ranges
VoltageYes
CurrentYes
ThermocoupleYes
Resistance thermometerYes
ResistanceYes
Input ranges (rated values), voltages
1 V to 5 VYes
— Input resistance (1 V to 5 V)1 MΩ
-1 V to +1 VYes
— Input resistance (-1 V to +1 V)1 MΩ
-10 V to +10 VYes
— Input resistance (-10 V to +10 V)1 MΩ
-2.5 V to +2.5 VYes
— Input resistance (-2.5 V to +2.5 V)1 MΩ
-250 mV to +250 mVYes
— Input resistance (-250 mV to +250 mV)1 MΩ
-5 V to +5 VYes
— Input resistance (-5 V to +5 V)1 MΩ
-500 mV to +500 mVYes
— Input resistance (-500 mV to +500 mV)1 MΩ
-80 mV to +80 mVYes
— Input resistance (-80 mV to +80 mV)1 MΩ
Input ranges (rated values), currents
0 to 20 mAYes
— Input resistance (0 to 20 mA)50 Ω
4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)50 Ω
Input ranges (rated values), thermocouples
Type BYes
— Input resistance (Type B)1 MΩ
Type EYes
— Input resistance (Type E)1 MΩ
Type JYes
— Input resistance (type J)1 MΩ
Type KYes
— Input resistance (Type K)1 MΩ
Type LYes
— Input resistance (Type L)1 MΩ
Type NYes
— Input resistance (Type N)1 MΩ
Type RYes
— Input resistance (Type R)1 MΩ
Type SYes
— Input resistance (Type S)1 MΩ
Type TYes
— Input resistance (Type T)1 MΩ
Type UYes
— Input resistance (Type U)1 MΩ
Input ranges (rated values), resistance thermometer
Ni 100Yes
— Input resistance (Ni 100)1 MΩ
Ni 1000Yes
— Input resistance (Ni 1000)1 MΩ
Pt 100Yes
— Input resistance (Pt 100)1 MΩ
Pt 1000Yes
Pt 10000Yes
Pt 200Yes
— Input resistance (Pt 200)1 MΩ
Pt 500Yes
— Input resistance (Pt 500)1 MΩ
Input ranges (rated values), resistors
0 to 48 ohmsYes
— Input resistance (0 to 48 ohms)1 MΩ
0 to 150 ohmsYes
— Input resistance (0 to 150 ohms)1 MΩ
0 to 300 ohmsYes
— Input resistance (0 to 300 ohms)1 MΩ
0 to 600 ohmsYes
— Input resistance (0 to 600 ohms)1 MΩ
0 to 6000 ohmsYes; Usable up to 5000 Ohm
— Input resistance (0 to 6000 ohms)1 MΩ
Temperature compensation
— ParameterizableYes
— internal temperature compensationNo
— external temperature compensation with Pt100Yes
— external temperature compensation with compensations socketYes
— dynamic reference temperature valueYes
Characteristic linearization
ParameterizableYes
— for thermocouplesType B, E, J, K, L, N, R, S, T, U
— for resistance thermometerPt100, Pt200, Pt500, Pt1000, Ni100, Ni1000
Cable length
shielded, max.200 m; 50 m with thermocouples and input ranges ≤ 80 mV
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.14 bit; with activated filtering: 16 bit
Integration time, parameterizableYes
Basic conversion time (ms)20.1 / 23.5 ms
Integration time (ms)16,7 / 20 ms
Interference voltage suppression for interference frequency f1 in Hz50 / 60 Hz
Basic execution time of the module (all channels released)161 ms; 161 / 188 ms
Connection of signal encoders
for voltage measurementYes; possible
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
for resistance measurement with two-wire connectionYes; Line resistances are also measured
for resistance measurement with three-wire connectionYes
for resistance measurement with four-wire connectionYes
Errors/accuracies
Temperature error (relative to input range), (+/-)0.004 %/K
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.38 %; ±0.38 % at ±80 mV; ±0.35 % at ±250 mV, ±500 mV, ±1 V, ±2,5 V, ±5 V, 1 to 5 V, ±10 V
Current, relative to input range, (+/-)0.35 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.5 %
Resistance thermometer, relative to input range, (+/-)0.5 %
Thermocouple, relative to input range, (+/-)TC Type B (±14.8 K), TC Type R (±9.4 K), TC Type S (±10.6 K), TC Type T (±2.2 K), TC Type E (±4.0 K), TC Type J (±5.2 K), TC Type K (±7.6 K), TC Type U (±3.5 K), TC Type L (±5.1 K), TC Type N (±5.5 K)
Basic error limit (operational limit at 25 °C)
Voltage, relative to input range, (+/-)0.15 %; ±0.15 % (±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 to 5 V, ±10 V); ±0.17% (±80 mV)
Current, relative to input range, (+/-)0.15 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
Resistance, relative to input range, (+/-)0.15 %; ±0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); ±0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms)
Resistance thermometer, relative to input range, (+/-)0.3 %
Thermocouple, relative to input range, (+/-)TC Type B (±8.2 K), TC Type R (±5.2 K), TC Type S (±5.9 K), TC Type T (±1.2 K), TC Type E (±1.8 K), TC Type J (±2.3 K), TC Type K (±3.4 K), TC Type U (±1.8 K), TC Type L (±2.3 K), TC Type N (±2.9 K)
Interrupts/diagnostics/status information
Diagnostics functionNo
Potential separation analog inputs
Potential separation analog inputsYes; internal/external
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+Yes
Isolation
Isolation tested with2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground
Dimensions
Width25 mm
Height290 mm
Depth210 mm
Weights
Weight, approx.500 g