General information
Product type designationAQ 4xU
HW functional statusfrom FS01
Firmware versionV1.0.0
FW update possibleYes
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Output range scalableNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionSTEP 7 V18 or higher; MicroWin V3.0 or higher; Configuration in ES via GSDML;
PROFINET from GSD version/GSD revisionGSDML V2.45
Operating mode
OversamplingNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
external protection for power supply linesYes; 24 V DC/10 A miniature circuit breaker with type B or C tripping characteristic
Input current
Current consumption (rated value)60 mA
Current consumption, max.100 mA
Current carrying capacity
For P1 and P2 bus, max.10 A
Power loss
Power loss, typ.1.25 W
Address space per module
Address space per module, max.8 byte
Hardware configuration
Automatic encodingNo
Mechanical coding elementNo
Formation of potential groups
support of potential groupsYes
Analog outputs
Number of analog outputs4
Cycle time (all channels), min.1 ms
Analog output with oversamplingNo
Output ranges, voltage
0 to 10 VYes; 15 bit
-10 V to +10 VYes; 16 bit incl. sign
Connection of actuators
for voltage output two-wire connectionYes
for voltage output four-wire connectionNo
Load impedance (in rated range of output)
with voltage outputs, min.2 kΩ
with voltage outputs, capacitive load, max.1 µF
Cable length
shielded, max.200 m
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Settling time
for resistive load0.2 ms
for capacitive load1.2 ms
Errors/accuracies
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.005 %/K
Crosstalk between the outputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Operational error limit in overall temperature range
Voltage, relative to output range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)0.3 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakNo
Short-circuitNo
Group errorNo
Overflow/UnderflowYes; module-wise
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsNo
for module diagnosticsYes; green/red DIAG LED
Potential separation
between backplane bus and supply voltageYes
Potential separation analog outputs
between the channelsNo
between the channels and backplane busYes
between the channels and the power supply of the electronicsNo
Isolation
Isolation tested with500 V AC/707 V DC, type test
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]28.8 kg
— global warming potential, (during production) [CO2 eq]4.52 kg
— global warming potential, (during operation) [CO2 eq]24.6 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.373 kg
Use in hazardous areas
EAC ExNo
Ambient temperature during operation
horizontal installation, min.-30 °C
horizontal installation, max.60 °C
vertical installation, min.-30 °C
vertical installation, max.50 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200BL system manual
Terminals
Conductor cross-section, min.0.14 mm²; follow detailed information in System manual of ET 200BL
Conductor cross-section, max.2.5 mm²; follow detailed information in System manual of ET 200BL
Number of process terminals to I/O module16
Number of terminals with connection to P1 and P2 bus2
Dimensions
Width15 mm
Height117 mm
Depth74 mm
Weights
Weight, approx.82 g