General information
Product type designationDQ 8x24VDC/0,5A HF
HW functional status01
Firmware versionV1.0
FW update possibleYes
usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC02
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeYes; 250 µs
Engineering with
STEP 7 TIA Portal configurable/integrated from versionas of TIA Portal V19 with HSP0428 / integrated as of TIA Portal V20
STEP 7 configurable/integrated from versionas of STEP 7 V5.5 SP3 with HSP0230 V11.0 / integrated as of STEP 7 V5.7 SP3
PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
PROFINET from GSD version/GSD revisionGSDML V2.43
Operating mode
DQYes
DQ with energy-saving functionNo
PWMNo
OversamplingNo
MSOYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption, max.20 mA; without load
Output voltage
Rated value (DC)24 V
Power loss
Power loss, typ.1 W
Address space per module
Address space per module, max.8 byte; 2 channels per submodule + QI information
Hardware configuration
Automatic encodingYes
Mechanical coding elementYes
Type of mechanical coding elementType A
Submodules
Number of configurable submodules, max.4
Selection of BaseUnit for connection variants
1-wire connectionBU type A0
2-wire connectionBU type A0
3-wire connectionBU type A0 with AUX terminals or potential distributor module
Digital outputs
Type of digital outputSource output (PNP, current-sourcing)
Number of digital outputs8
Current-sinkingNo
Current-sourcingYes
Digital outputs, parameterizableYes
output type acc. to IEC 61131, type 0.5Yes
Short-circuit protectionYes; Electronic
Response threshold, typ.0.7 to 1.3 A
Limitation of inductive shutdown voltage toTyp. L+ (-50 V)
Controlling a digital inputYes
Switching capacity of the outputs
with resistive load, max.0.5 A
with inductive load, max.0.5 A
on lamp load, max.5 W
Load resistance range
lower limit48 Ω
upper limit12 kΩ
Output current
for signal "1" rated value0.5 A
for signal "1" permissible range, max.0.5 A
for signal "0" residual current, max.0.1 mA
Output delay with resistive load
"0" to "1", typ.50 µs
"1" to "0", typ.100 µs
Parallel switching of two outputs
for upratingNo
for redundant control of a loadYes
Switching frequency
with resistive load, max.100 Hz
with inductive load, max.0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads"
on lamp load, max.10 Hz
Total current of the outputs
Current per channel, max.0.5 A
Current per module, max.4 A
horizontal installation
— up to 60 °C, max.4 A
vertical installation
— up to 50 °C, max.4 A
Cable length
shielded, max.1 000 m
unshielded, max.600 m
Isochronous mode
Execution and activation time (TCO), min.48 µs
Bus cycle time (TDP), min.500 µs
Jitter, max.8 µs
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
— parameterizableYes
Wire breakYes; channel by channel
Short-circuit to groundYes; channel by channel
Short-circuit to L+Yes; channel by channel
Group errorYes
Diagnostics indication LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Channel status displayYes; green LED
for channel diagnosticsYes; red LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channelsNo
between the channels and backplane busYes
Between the channels and load voltage L+No
Isolation
Isolation tested with707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functionsNo
Suitable for safety-related tripping of standard modulesYes; see FAQ Entry ID: 39198632
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]20.4 kg
— global warming potential, (during production) [CO2 eq]3.16 kg
— global warming potential, (during operation) [CO2 eq]17.5 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.221 kg
Highest safety class achievable for safety-related tripping of standard modules
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SIL acc. to IEC 62061SIL 2
Ambient temperature during operation
horizontal installation, min.-30 °C
horizontal installation, max.60 °C
vertical installation, min.-30 °C
vertical installation, max.50 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.30 g