General information
Product type designationVibration protection module 4 channels
HW functional statusFS04
Firmware versionV1.2
FW update possibleYes
Usable terminal blocktype H1, N0, H0 (see system manual for details)
Color code for module-specific color-coded labelCC00
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Engineering with
STEP 7 configurable/integrated from versionV5.6 with HSP 298 or higher
PCS 7 configurable/integrated from versionV9.1 SP1
SPPA-T3000 can be configured/integrated from versionV8.2 SP2
Operating mode
DIYes
DQYes
CiR - Configuration in RUN
Reparameterization possible in RUNYes
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)150 mA; without load
Current consumption, max.2 A; At 24 V DC
from backplane bus 24 V DC, max.21 mA
Encoder supply
Number of outputs6; max. depending on parameterization
Output voltage (DC)24 V
Output voltage, min.18.2 V
Short-circuit protectionYes; per channel, electronic
24 V encoder supply
24 VYes
Short-circuit protectionYes; per channel, electronic
Output current per channel, max.0.5 A
Output current per module, max.2 A
Power loss
Power loss, typ.4 W
Address space per module
Address space per module, max.162 byte; Quick inputs and outputs (without AI) and 4 vibration protection function chains: 88 bytes. Of which 71 bytes for inputs, 17 bytes for outputs. Quick inputs and outputs (without AI) and 8 vibration protection function chains: 154 bytes. Of which 137 bytes for inputs, 17 bytes for outputs. Quick inputs and outputs (with AI) and 4 vibration protection function chains 96 bytes. Of which 79 bytes for inputs, 17 bytes for outputs. Quick inputs and outputs (with AI) and 8 vibration protection function chains: 162 bytes. Of which 145 bytes for inputs, 17 bytes for outputs.
Hardware configuration
Mechanical coding elementYes; A, B coding; mounting position B8
Digital inputs
Number of digital inputs10; Of these, 6 combined DI/DQ
Digital inputs, parameterizableYes
Sourcing/sinking inputYes; DI0 ... DI3 (param.); sinking DIDQ4 ... DIDQ9
Input characteristic curve in accordance with IEC 61131, type 1Yes
Pulse extensionYes
Length2 s; off, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s
Input voltage
Rated value (DC)24 V
for signal "0"0 ... 5 V
for signal "1"+11 to +30V
Input current
for signal "1", typ.2.6 mA; 2.6 mA DI, 3.5 mA DIDQ
for standard inputs
— parameterizableYes; 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms (in each case + delay of 30 to 500 µs, depending on line length)
Cable length
shielded, max.1 000 m
Digital outputs
Number of digital outputs6; max. depending on parameterization
Current-sinkingNo
Current-sourcingYes
Digital outputs, parameterizableYes
Short-circuit protectionYes
Response threshold, typ.0.95 A
Open-circuit detectionYes
Response threshold, typ.45 mA
Overload protectionYes
Response threshold, typ.950 mA
Limitation of inductive shutdown voltage toL+ -(37 to 41V)
Controlling a digital inputYes
Digital output functions, parameterizable
Freely usable digital outputYes
Switching capacity of the outputs
with resistive load, max.0.5 A
Load resistance range
lower limit48 Ω
Output voltage
for signal "1", min.18.1 V
Output current
for signal "1" rated value0.5 A
Output delay with resistive load
"0" to "1", typ.1 ms
"1" to "0", typ.100 µs
Switching frequency
with resistive load, max.800 Hz
Total current of the outputs
Current per channel, max.0.5 A
Current per module, max.2 A
Cable length
shielded, max.1 000 m
Analog inputs
Number of analog inputs4
permissible input voltage for voltage input (destruction limit), max.30 V
permissible input current for current input (destruction limit), max.50 mA; Protection available against destruction
Cycle time (all channels), min.1.25 ms; For up to 128 samples per channel
Input ranges (rated values), voltages
0 to +10 VYes
— Input resistance (0 to 10 V)100 kΩ
-10 V to +10 VYes
— Input resistance (-10 V to +10 V)100 kΩ
Input ranges (rated values), currents
0 to 20 mAYes; 0 mA or 4 mA to 20 mA
— Input resistance (0 to 20 mA)70 Ω
-20 mA to +20 mAYes
— Input resistance (-20 mA to +20 mA)70 Ω
4 mA to 20 mAYes; and 0 to 20 mA
— Input resistance (4 mA to 20 mA)70 Ω
Cable length
shielded, max.600 m
Analog outputs
Number of analog outputs8; 4 AQ-I, 4 AQ-U
Voltage output, short-circuit protectionYes; per channel, electronic to chassis
Voltage output, short-circuit current, max.10 mA
Current output, no-load voltage, max.24 V
Cycle time (all channels), min.625 µs
Output ranges, voltage
-10 V to +10 VYes
Output ranges, current
0 to 20 mAYes
-20 mA to +20 mAYes; ±30 mA, ±50 mA
4 mA to 20 mAYes
Connection of actuators
for voltage output two-wire connectionYes
Load impedance (in rated range of output)
with current outputs, max.330 Ω; 150 ohms at ±50 mA
Analog value generation for the inputs
Measurement principleintegrating (Sigma-Delta)
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.24 bit
Smoothing of measured values
ParameterizableYes
Step: NoneYes
Step: lowYes
Step: MediumYes
Step: HighYes
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max.16 bit
Connection of signal encoders
for voltage measurementYes
for current measurement as 2-wire transducerYes
for current measurement as 4-wire transducerYes
Connectable encoders
Single contact / changeover contact unconnectedYes
2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Errors/accuracies
Linearity error (relative to input range), (+/-)0.05 %
Temperature error (relative to input range), (+/-)0.0025 %/K
Crosstalk between the inputs, min.60 dB
Operational error limit in overall temperature range
Voltage, relative to input range, (+/-)0.3 %
Current, relative to input range, (+/-)0.3 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Substitute values connectableYes
Alarms
Diagnostic alarmYes
Diagnoses
Monitoring the supply voltageYes
Wire breakYes; AI 4 ... 20 mA, AQ, DQ, DI 0 ... 3
Short-circuit to groundYes; Encoder supply to M, channel by channel
Short-circuit to L+Yes; Analog inputs
Group errorYes
Overflow/UnderflowYes
Diagnostics indication LED
RUN LEDYes; green LED
MAINT LEDYes; Yellow LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
for module diagnosticsYes; green/red DIAG LED
Potential separation channels
between the channels and backplane busYes
Permissible potential difference
between different circuits75 V DC/60 V AC between L+ and backplane bus
Isolation
Isolation tested with1 500 V DC/1 min, type test
Ambient temperature during operation
horizontal installation, min.-40 °C
horizontal installation, max.70 °C; Observe derating
vertical installation, min.-40 °C
vertical installation, max.60 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.3 500 m
Dimensions
Width22.5 mm
Height115 mm
Depth138 mm
Weights
Weight, approx.200 g