General information
Product type designationPN/J1939 LINK
FW update possibleYes
Vendor identification (VendorID)0x002A
based on6BK1623-0AA00-0AA0
Product function
I&M dataYes; I&M0 to I&M3
Isochronous modeNo
Engineering with
STEP 7 TIA Portal configurable/integrated from versionsee entry ID: 109746275
PROFINET from GSD version/GSD revisionGSDML V2.3.x
Installation type/mounting
MountingDIN rail, wall mounting, portrait mounting
Mounting positionany
Recommended mounting positionHorizontal
Rail mountingYes
Control cabinet installationYes
Supply voltage
Type of supply voltageDC
Rated value (DC)24 V
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Overvoltage protectionYes
Short-circuit protectionYes
Mains buffering
Mains/voltage failure stored energy time10 ms; PN side
Input current
Current consumption (rated value)0.09 A
Current consumption, max.0.11 A
Power loss
Power loss, typ.2.2 W
Interfaces
Interfaces/bus type2x Ethernet (RJ45), 1x Sub-D (9-pin)
Supports protocol for PROFINET IO
automatic detection of transmission rateNo
Transmission rate, max.100 Mbit/s
Number of RJ45 ports2
Number of FC (FastConnect) connections2
PROFINET functions
Assignment of the IP address, supportedYes
Assignment of the device name, supportedYes
1. Interface
Interface typeJ1939 according to the standard "SAE J1939"
IsolatedYes; 500 V AC or 707 V DC
Interface types
Number of ports1
Design of the connection9-pin sub D socket
CAN
CAN operating modesJ1939 according to the standard "SAE J1939"
Transmission rate, min.100 kbit/s
Transmission rate, max.500 kbit/s
max. number of devices30
J1939
Addressable ECUs, max.30
Logical nodes, max.253
PDU 1Yes
PDU 2Yes
DM dataYes
BAMYes
CMDTYes
2. Interface
Interface typePROFINET
IsolatedYes; 1 500 V AC or 2 250 V DC
Interface types
RJ 45 (Ethernet)Yes
Number of ports2
integrated switchYes
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Diagnostics indication LED
RUN LEDYes
ERROR LEDYes
MAINT LEDYes
LINK LEDYes
RX/TX LEDYes
Potential separation
Potential separation existsYes
Isolation
Isolation tested with750 V DC (type test) and according to EN 50155 (routine test)
Degree and class of protection
IP degree of protectionIP20
Ecological footprint
environmental product declarationYes
Global warming potential
— global warming potential, (total) [CO2 eq]50.8 kg
— global warming potential, (during production) [CO2 eq]14.4 kg
— global warming potential, (during operation) [CO2 eq]36.8 kg
— global warming potential, (after end of life cycle) [CO2 eq]-0.52 kg
Railway application
EN 50121-3-2Yes; EMC for rail vehicles
EN 50121-4Yes; EMC for signal and telecommunications systems
EN 50124-1Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC
EN 50125-1Yes; Rail vehicles - see ambient conditions
EN 50125-2Yes; Stationary electrical equipment - see ambient conditions
EN 50125-3Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track)
EN 50155Yes; Rail vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
EN 61373Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B
Fire protection acc. to EN 45545-2Yes; For proof of conformity, see Service & Support
Ambient temperature during operation
horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost)
horizontal installation, max.70 °C; = Tmax; +85 °C for 10 min (OT4, ST1/ST2 acc. to EN 50155)
vertical installation, min.-40 °C; = Tmin
vertical installation, max.55 °C; = Tmax
ceiling installation, min.-40 °C; = Tmin
ceiling installation, max.45 °C; = Tmax
floor installation, min.-40 °C; = Tmin
floor installation, max.45 °C; = Tmax
Ambient temperature during storage/transportation
min.-40 °C
max.85 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.2 000 m
Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
Relative humidity
With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
Use on land craft, rail vehicles and special-purpose vehicles
— to biologically active substances according to EN 60721-3-5Yes; Class 5B2 mold, fungus and dry rot spores (with the exception of fauna); Class 5B3 on request
— to chemically active substances according to EN 60721-3-5Yes; Class 5C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust; *
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
Electronic equipment on rolling stock acc. to EN 50155Yes; Class PC2 protective coating acc. to EN 50155:2017
Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Dimensions
Width70 mm
Height112 mm
Depth75 mm
Weights
Weight, approx.212 g
Other
Note:for use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A, Online Support article 109736776