product brand nameSIPLUS
transfer rate
at the 1st interface10 ... 100 Mbit/s
interfaces
number of interfaces / according to Industrial Ethernet1
at the 1st interface / according to Industrial Ethernet2
at the 1st interface / according to Industrial Ethernetvia ET 200SP bus adapter (RJ45, FC, SCRJ), integrated switch
supply voltage, current consumption, power loss
type of voltage / of the supply voltageDC
supply voltage24 V
supply voltage19.2 ... 28.8 V
power loss [W]6 W
ambient conditions
for vertical installation / during operation-40 ... +50 °C
for horizontally arranged busbars / during operation-40 ... +70 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
note+85 °C for 10 min (OT4, ST1/ST2 according to EN 50155)
installation altitude / at height above sea level / maximum2000 m
ambient condition / relating to ambient temperature - air pressure - installation altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m)
with condensation / according to IEC 60068-2-38 / maximum100 %; RH including condensation/frost (no commissioning when condensation is present), horizontal installation
chemical resistance / to commercially available cooling lubricantsYes; incl. airborne diesel and oil droplets
conformity according to EN 60721-3-3Yes; Class 3B2 mold and fungal spores (excluding fauna), Class 3B3 on request
conformity according to EN 60721-3-5Yes; Class 5B2 mold and fungal spores (excluding fauna), Class 5B3 on request
conformity according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray in accordance with EN 60068-2-52 (Severity 3). The supplied plug covers must remain in place on the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5C3 (RH < 75%) including salt spray acc. to EN 60068-2-52 (Severity level 3). The supplied plug covers must remain in place over the unused interfaces during operation!
conformity according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation.
conformity according to EN 60721-3-5Yes; Class 5S3 incl. sand, dust. The supplied plug covers must remain in place over the unused interfaces during operation!
coating / for equipped printed circuit board / according to EN 61086Yes; Class 2 for high availability
type of coating / protection against pollution according to EN 60664-3Yes; Protection of the type 1
type of coating / for electronic devices in railway applications according to EN 50155Yes; Protective coating of the Class PC2 according to EN 50155:2017
type of test / of the coating / according to MIL-I-46058CYes; Coating discoloration during service life possible
product conformity / of the coating / Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, class A
protection class IPIP20
design, dimensions and weights
width60 mm
height117 mm
depth74 mm
net weight0.18 kg
35 mm DIN-rail mountingYes
product features, product functions, product components / general
per CPU / maximum2
note2 CPs can be pluged in per CPU, simultaneous operation with BA Send and CM DP is possible
performance data / open communication
by means of T blocks / maximum32
as user data per ISO on TCP connection / for open communication / by means of T blocks / maximum65536 byte
performance data / S7 communication
maximum16
with OP connections / maximum16
performance data / multi-protocol mode
number of active connections / with multi-protocol mode32
performance data / IT functions
as email client / maximum1
performance data / telecontrol
node stationNo
substationYes
TIM control centerNo
control center connectionIEC 60870-5, DNP3, (Modbus TCP by block solutions of the CPU) capable control stations, connection to Telecontrol Server Basic and ST7 capable control station
by means of a permanent connectionsupported
by means of demand-oriented connectionsupported
noteConnection to SCADA system by IEC 60870-5 104, DNP3, Telecontrol Server Basic and ST7 capable control center
DNP3Yes
IEC 60870-5Yes
SINAUT ST7 protocolYes
product function / data buffering if connection is abortedYes; TCSB 64000 events, SINAUT ST7 32000 telegrams, DNP3 100000 events, IEC 60870-5 100000 events
number of data points per device / maximum1500
in send direction / maximum3
in receive direction / maximum15
product functions / management, configuration, engineering
product function / MIB supportYes
SNMP v1Yes
SNMP v3Yes
DCPYes
LLDPYes
requiredSTEP 7 Professional V14 (TIA Portal) or higher
I&M0 - device-specific informationYes
I&M1 - higher level designation/location designationYes
product function / is supported / identification linkYes; acc. to IEC 61406-1:2022
product functions / diagnostics
product function / web-based diagnosticsYes; via ET 200SP CPU
product functions / security
product function / with VPN connectionSINEMA RC
blocking of communication via physical portsYes
product functions / time
product function / SICLOCK supportYes
product function / pass on time synchronizationYes
NTPYes
NTP (secure)No
from NTP-serverYes
from control centerYes
product functions / position detection
certificate of suitability / railway application in accordance with EN 50121-3-2Yes; EMC for railway vehicles
certificate of suitability / railway application in accordance with EN 50121-4Yes; EMC for signaling and telecommunications equipment
certificate of suitability / railway application in accordance with EN 50124-1Yes; Railway applications - Overvoltage category OV2 pollution degree PD2 rated impulse voltage UNi = 0.5 kVUNm = DC 24
certificate of suitability / railway application in accordance with EN 50125-1Yes; Railway vehicles - See ambient conditions
certificate of suitability / railway application in accordance with EN 50125-2Yes; Fixed-electrical installations - see ambient conditions
certificate of suitability / railway application in accordance with EN 50125-3Yes; Signal and telecommunications equipment - see Ambient conditions vibrations and shocks: Application point outside the rails (distance 1 m to 3 m from rail)
certificate of suitability / railway application in accordance with EN 50155Yes; Railway vehicles - temperature class OT4, ST1/ST2, horizontal mounting position
certificate of suitability / railway application in accordance with EN 61373Yes; Railway vehicles - Vibrations and shocks Category 1 Class A/B
certificate of suitability / fire protection in accordance with EN 45545-2Yes; Railway vehicles - for proof, see Service & Support